TARGET CORPORATION
MAY 2006
Elevator QEI / Turnover Performance Report
PASSENGER
ELEVATOR #3
TARGET T-2171
BUCKHEAD SOUTH
LINDBERG PLAZA
EXIT 86 & INTERSTATE 85
ATLANTA, GEORGIA
By: ELEVATOR CONSULTING SERVICES, INC.
Equipment Inventory
Control Type:SELECTIVE COLLECTIVE
Contract Speed:125 FPM / .609 M/S
Machine Type:OTIS 211 CONTROLLER
OTIS PUMP UNIT
Door Equipment:OTIS A / B
Door Size/Type:60” WIDE X 84” HIGH
Number of Openings:TWO (2) – ONE (1) FRONT – ONE (1) REAR
Travel:13’6”
Floors Served:*1, 2
SHOULD BE REVERSED
City/State Number:483006
Atlanta
Capacity:5000 LBS
Emergency Light:OK
Two Way Communication:PUSH TO TALK
PROGRAM TO ALERT ONE
Alarm Bell:OK
Maintenance Log:NONE
ITEMS IN RED ARE THE RESPONSIBILITY OF THE ELEVATOR CONTRACTOR
ITEMS IN BLUE ARE THE RESPONSIBILITY OF THE BUILDING OWNER
PERFORMANCE
Speed Up: 125 FPM
Speed Down: 125 FPM
Perform Up:SEC
Perform Down:SEC
Door Open:SEC – F
SEC - R
Door Close:SEC – F
SEC - R
Hall Call Dwell:SEC
Car Call Dwell:SEC
Nudging:SEC – F
SEC - R
SCANNERS IN FAIL SAFE
Door Torque:LBS – F
LBS - R
Ride Quality
Ride:OK
Deceleration Up:OK
Deceleration Down:OK
Acceleration Up:OK
Acceleration Down:OK
Stop:OK
Leveling:OK
Equipment Room
Access:OK
Headroom:OK
Enclosure:OK
Lighting:OK
Cleanliness:FAIR
Air Circulation,Ventilation:OK
Pipes, Ducts, Non Elev:NONE
Parts:NONE
GFIC Receptacles:YES
Fire Extinguisher:OK
NEW 5-06
Guarding:OK
Self Closing, Locking door:OK
Numbering of units:OK
Sprinkler in room:NO
Lockable, Fused Disconnect:YES
110 Volt Disconnect:YES
110 Volt Disconnect Oil Cooler:NO
Shunt trip protection:YES
MSDS documentation:OIL NEEDED
Oil monitoring sheet:NO
Signage on door:OK
Control Panel
Type of Control:MICROPROCESSOR
211 ELEVONIC
Manufacturer:OTIS
Install Date:4-06
Install Code:ASME 17.1 / 2000
Cleanliness:OK
Identification:OK
OTISJOB# 483006
OTIS SERIAL #51940550
Software Version: NO ID
Guarding:OK
CSA / U. L. Label:CSA
Components-Controller
Relays:OK
Enclosure / Open Style:ENCLOSED
Contacts:OK
Resistors:OK
P.C. Boards / Timers:OK
Wiring:OK
Performance:OK
Camera Wire:NI
Telephone:OK
Programmed Site:UNKNOWN
Phone #:NO ID
Starters
Type:ELECTRONIC
Size:AC53a 6-6 30-80
Mfg:SIEMENS
SERIES E02
Contacts:OK
Wiring:OK
Mounting:OK
Up Starts:887 - 5/21/06
Pump Unit
Model:OTIS
20390
Cleanliness:OK
Leaks:NONE
Noise:OK
Oil level:OK
Oil:OK
Belts:N/A
Sheave:N/A
Pump:OK
ALLWEILER
SUB210R46
Shut Offs:YES
Subs / Dry:SUB
Valves:OK
MAXTON
UC-4M B44
Muffler:PANCAKE
Seals:OK
Covers:OK
Acceptance Test:4-18-06
Tagged:DISCONNECT ONLY
Annual No Load Test:N/A
Tagged:N/A
Oil Coolers
Existing:NO
Mfg:N/A
Model #:N/A
Hoses:N/A
Wiring:N/A
Leaks:N/A
Air Filter:N/A
Oil Filter:N/A
Motor HP:N/A
Motor
Isolation:OK
Grounded:OK
Covers:OK
HP:50
RPM:3460
AMPS:130/65
Starts/Hr:80
Frame:160ZBO
Hoistway
Selector Car Top Device
Cleanliness:OK
Tape:OK
Magnets:OK
Guides:OK
Limit Switches
Noise, Rollers:OK
Operation:OK
Type:OTIS STND
Rails
Cleanliness:OK
Lubrication:OK
Type:T / 15T
Fastening:OK
Shoes:OK
Cable Condition
Traveling:OK
Suspension:OK
Spares:OK
Kellum Grips:OK
Hoistway Equipment
Car Top
Cleanliness:FAIR
Maintenance Station:OK
Stop Switch:OK
Data Plate:OK
Light:OK
Light Guards:OK
Guides:OK
GFIC Recept:NO
Escape door locked:OK
Windows in Hoistway:NO
Multiple Hoistways:N/A
Stenciled:NO
Hoistway Venting
Existing:NO
Motorized:N/A
Key Switch:N/A
Safety Bars:N/A
Size (3%):N/A
Door Operator / GAL MOVFF (N)R (S)
Cleanliness:OKOK
Door Protection:SCANNERSCANNER
Lubrication:OKOK
Belts:OKOK
Chains: OKOK
Hangers:OKOK
Arms:OKOK
Bearing:OKOK
Noise:OKOK
Tracks:OKOK
Cover:OKOK
Upthrusts:OKOK
Restrictor:OKOK
Gibs:OKOK
Car Enclosure
Ventilation:OK
FAN
Walls:STAND OFF PANELS
Car Lighting:OK
2 FLORESCENT
Ceiling:OK
SUSPENDED WITH PLASTIC EGG CRATE
Position Indicators:OK
DIGITAL
Handrails/Bumpers:2” BARSTOCK @ 32” TO TOP
Flooring:TILE
Car Doors:BAKED ENAMEL
Sills:ALUMINUM
Certificate Frame:NO
Entrance Equipment
Cleanliness:OK
Lubrication:OK
Tracks:OK
Hangers:OK
Gibs:OK
Interlocks:OK
Clutch Release Rollers:OK
Noise:OK
Upthrust:OK
Closers:OK
Braille:OK
Emergency Fire Box
Main Egress Landing:1ST FLOOR
Existing in lobby:YES
Machine room key:YES
Phase I, II keys:YES
Lunar key:YES
Tagged:NO
Car Operating Panel
Type:OTIS MODULAR
Condition:OK
Height Compliance:OK
Braille Identification:OK
Buttons:OK
Phone:PUSH TO TALK
Callback #:NO ID
Alarm Button:OK
35” TO CENTER
Stop Switch:KEYED
Emergency Light:OK
Capacity Plate / Engraved:YES
5000 LBS
Fire Fighters Instr:YES
STAINLESS SIGN
Phase II key sw:YES
OFF / HOLD / ON
Certificated:NO
Hall Buttons:
Type:OTIS MODULAR
Condition:OK
Illuminated:OK
Height:OK
Mechanical:OK
Lanterns:YES
Fire Signage:YES
PICTORIAL APPENDIX H
Phase I key switch:YES
Phase I instructions:BYPASS / OFF / ON
Pit Equipment
Cleanliness:OK
Car Buffer:OK
Cwt Buffer:N/A
Lights:OK
Light Switch:OK
Light Guards:OK
Stop Switch:OK
Ladder:OK
GFIC Recept:YES
Jack Seal:OK
PVC Liner:YES
Shut Offs:OK
Piston Pans:NONE
Rupture Valves:NO
Piston:OK
High Pressure Vics:NO
Return Line:OK
Pit bucket:NI
Bottom of Car
Cleanliness:OK
Static Weights:NO
Safeties:N/A
Trav cable suspension:OK
Toe guard length:OK
Isolation:OK
Light Fixture:NO
Light Guard:NO
Guides:OK
Receptacle:NO
GFI Receptacle:NO
T-2171 TARGET
BUCKHEAD SOUTH, GA
PASSENGER ELEVATOR 3
CORRECTIVE ITEMS
The following minimum items need corrective action taken. Documentation of completion is required.
Otis
- Vacuum out the controller. Has a lot of debris and metal filings.
- Make the battery rescuvator operational.
- Provide a pit bucket for the return line to the jack head.
- Make the top floor access switch operational. The key switch does not work.
- Program the phone with the message to a 24 hour number.
- Replace the temporary makeshift pipe stand in the pit with a permanent one that is not shimmed.
- Provide the MSDS sheets for the hydraulic oil in a plastic sleeve on the tank unit.
- Provide an oil monitoring sheet in a plastic insert on the tank unit.
- Verify the main egress is actually 1. I would think the main egress would be the top landing or street level. Change Braille designations and hall fixtures as needed.
T-2171 TARGET
BUCKHEAD SOUTH, GA
PASSENGER ELEVATOR 3
CONTRACTOR
- The electrical disconnects need the source data tag displayed on disconnect per NEC, includes main, 3 phase and 110.
- Relocate the smoke detectors in the machine room. The A / C unit will create a lot of false alarms. Either move the smokes over two feet or deflect the air down to the floor.
NI – NEEDS IMPROVEMENT1 T-2171 PASSENGER ELEVATOR 3
OK - SATISFACTORY MAY 2006 QEI / PERFORMANCE REVIEW