SNMP Object Definition

for the

Data Aire DAP-II

Revision 1

June 17, 2005

Prepared for

Data Aire, Inc.

230 West Blueridge Avenue

Orange, California 92865

by

MMI Development Group, Inc.

REVISION HISTORY
Rev / By / Date / Description
1 / S. Johnson / 6/17/05 / Initial Release

Table of Contents

1Introduction

1.1Scope

1.2References

2SNMP Object Definitions

2.1Status (Read Only)

2.2Control (Read/Write)

2.3Configuration (Read/Write)

2.4Configuration (Read Only)

2.5Relay Expansion Card Status (Read Only)

2.6Analog Expansion Card Status (Read Only)

1Introduction

1.1Scope

This document describes the SNMP MIB for the Data Air Processor II (DAP-II).

1.2References

2SNMP Object Definitions

2.1Status (Read Only)

Object Identifier / Type / Description / Units
1.3.6.1.4.1.22731.1.1.1.1 / INTEGER
off(0)
on(non-zero) / Dehumidifying / N/A
1.3.6.1.4.1.22731.1.1.1.2 / INTEGER
off(0)
on(non-zero) / Humidifying / N/A
1.3.6.1.4.1.22731.1.1.1.3 / INTEGER
off(0)
on(non-zero) / Energy Saver / N/A
1.3.6.1.4.1.22731.1.1.1.4 / INTEGER
off(0)
on(non-zero) / Cooling Held / N/A
1.3.6.1.4.1.22731.1.1.1.5 / INTEGER
off(0)
on(non-zero) / Heating Held / N/A
1.3.6.1.4.1.22731.1.1.1.6 / INTEGER
off(0)
on(non-zero) / Humidification Held / N/A
1.3.6.1.4.1.22731.1.1.1.7 / INTEGER
off(0)
on(non-zero) / Dehumidification Held / N/A
1.3.6.1.4.1.22731.1.1.1.8 / INTEGER
off(0)
on(non-zero) / Reheating During Dehumidification / N/A
1.3.6.1.4.1.22731.1.1.1.9 / INTEGER
unknown(1)
dap2(2)
dap2WithRelay(3)
dap2WithAnalog(4)
dap2WithRelayAndAnalog(5) / Unit Type / N/A
1.3.6.1.4.1.22731.1.1.1.10 / INTEGER / Return Temperature / 0.1°F
1.3.6.1.4.1.22731.1.1.1.11 / INTEGER / Discharge Temperature / 0.1°F
1.3.6.1.4.1.22731.1.1.1.12 / INTEGER / Current Humidity / 0.1%RH
1.3.6.1.4.1.22731.1.1.1.13 / INTEGER (0..5) / Cooling Stages On / N/A
1.3.6.1.4.1.22731.1.1.1.14 / INTEGER (0..4) / Heating Stages On / N/A
1.3.6.1.4.1.22731.1.1.1.15 / INTEGER / Water Valve Open / %
1.3.6.1.4.1.22731.1.1.1.16 / INTEGER / Humidifier Valve Open / %
1.3.6.1.4.1.22731.1.1.1.17 / INTEGER / High Temperature Over Last 24 Hours / 0.1°F
1.3.6.1.4.1.22731.1.1.1.18 / INTEGER / Low Temperature Over Last 24 Hours / 0.1°F
1.3.6.1.4.1.22731.1.1.1.19 / INTEGER / High Humidity Over Last 24 Hours / 0.1°F
1.3.6.1.4.1.22731.1.1.1.20 / INTEGER / Low Humidity Over Last 24 Hours / 0.1°F
1.3.6.1.4.1.22731.1.1.1.21 / INTEGER / Cooling Utilization Over Last 24 Hours / %
1.3.6.1.4.1.22731.1.1.1.22 / INTEGER / Heating Utilization Over Last 24 Hours / %
1.3.6.1.4.1.22731.1.1.1.23 / INTEGER / Chilled Water Utilization Over Last 24 Hours / %
1.3.6.1.4.1.22731.1.1.1.24 / INTEGER / Humidifier Utilization Over Last 24 Hours / %
1.3.6.1.4.1.22731.1.1.1.25 / INTEGER / Compressor 1 Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.26 / INTEGER / Compressor 2 Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.27 / INTEGER / Compressor 3Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.28 / INTEGER / Compressor 4 Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.29 / INTEGER / Heater 1 Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.30 / INTEGER / Heater 2 Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.31 / INTEGER / Heater 3 Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.32 / INTEGER / Humidifier Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.33 / INTEGER / Blower Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.34 / INTEGER / Condenser Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.35 / INTEGER / Dehumidifier Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.36 / INTEGER / Energy Saver Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.37 / INTEGER / Chilled Water Runtime / Hours
1.3.6.1.4.1.22731.1.1.1.38 / OCTET STRING
Each octet represents the index of one current alarm from the following table.
reheatAndHumidInhibited(1)
shortCycle(2)
customAlarm1(3)
customAlarm2(4)
customAlarm3(5)
customAlarm4(6)
dirtyFilter(7)
dischargeSensor(8)
fanOverload(9)
fireAlarm(10)
highHumidity(11)
highPressureC1(12)
highPressureC2(13)
highTemperature(14)
humidInhibited(15)
humidifierProblem(16)
humiditySensor(17)
localAlarm1(18)
localAlarm2(19)
localAlarm3(20)
localAlarm4(21)
lowHumidity(22)
lowPressureC1(23)
lowPressureC2(24)
lowTemperature(25)
lowDischargeAlarm(26)
lowVoltage(27)
maintenanceRequired(28)
manualOverride(29)
noAirFlow(30)
noWaterFlow(31)
powerProblem(32)
reheatInhibited(33)
smokeDetect(34)
standbyPumpOn(35)
temperatureSensor(36)
upsOn(37)
waterDetected(38)
highCondensate(39)
unitInStandbyHeldOff(40) / Alarm Status / N/A

2.2Control (Read/Write)

Network Variable / Network Variable Type / Description / Units
1.3.6.1.4.1.22731.1.1.1.39 / INTEGER
off(0)
on(non-zero) / Cooling Inhibited / N/A
1.3.6.1.4.1.22731.1.1.1.40 / INTEGER
off(0)
on(non-zero) / Heating Inhibited / N/A
1.3.6.1.4.1.22731.1.1.1.41 / INTEGER
off(0)
on(non-zero) / Humidification Inhibited / N/A
1.3.6.1.4.1.22731.1.1.1.42 / INTEGER
off(0)
on(non-zero) / Dehumidification Inhibited / N/A
1.3.6.1.4.1.22731.1.1.1.43 / INTEGER
off(0)
on(non-zero) / Fan Inhibited / N/A
1.3.6.1.4.1.22731.1.1.1.44 / INTEGER
on(1)
off(2)
standby(3) / Standby Mode / N/A

2.3Configuration (Read/Write)

Network Variable / Network Variable Type / Description / Units
1.3.6.1.4.1.22731.1.1.1.45 / INTEGER (0..59) / Time of Day: Seconds / N/A
1.3.6.1.4.1.22731.1.1.1.46 / INTEGER (0..59) / Time of day: Minutes / N/A
1.3.6.1.4.1.22731.1.1.1.47 / INTEGER (0..23) / Time of day: Hours / N/A
1.3.6.1.4.1.22731.1.1.1.48 / INTEGER (1..31) / Time of day: Day / N/A
1.3.6.1.4.1.22731.1.1.1.49 / INTEGER (1..12) / Time of day: Month / N/A
1.3.6.1.4.1.22731.1.1.1.50 / INTEGER / Time of day: Year / N/A
1.3.6.1.4.1.22731.1.1.1.51 / INTEGER
sunday(1)
monday(2)
tuesday(3)
wednesday(4)
thursday(5)
friday(6)
saturday(7) / Day of week / N/A
1.3.6.1.4.1.22731.1.1.1.52 / INTEGER
none(1)
every6hours(2)
every12hours(3)
every24hours(4)
every36hours(5)
every48hours(6)
every60hours(7)
every72hours(8)
every84hours(9)
every96hours(10) / Autoflush Time / N/A
1.3.6.1.4.1.22731.1.1.1.53 / INTEGER (100..150) / Fire Temperature Limit / °F
1.3.6.1.4.1.22731.1.1.1.54 / INTEGER (10..90) / High Humidity Limit / %RH
1.3.6.1.4.1.22731.1.1.1.55 / INTEGER (50..90) / High Temperature Limit / °F
1.3.6.1.4.1.22731.1.1.1.56 / INTEGER (45..61) / Low Discharge Temp Limit / °F
1.3.6.1.4.1.22731.1.1.1.57 / INTEGER (10..90) / Low Humidity Limit / %RH
1.3.6.1.4.1.22731.1.1.1.58 / INTEGER (50..90) / Low Temperature Limit / °F
1.3.6.1.4.1.22731.1.1.1.59 / INTEGER (1..15) / Humidity Deadband / %RH
1.3.6.1.4.1.22731.1.1.1.60 / INTEGER (25..70) / Humidity Setpoint / %RH
1.3.6.1.4.1.22731.1.1.1.61 / INTEGER (1..5) / Temperature Deadband / °F
1.3.6.1.4.1.22731.1.1.1.62 / INTEGER (65..85) / Temperature Setpoint / °F
1.3.6.1.4.1.22731.1.1.1.63 / INTEGER (5..600) / Start Delay / Seconds

2.4Configuration (Read Only)

Network Variable / Network Variable Type / Description / Units
1.3.6.1.4.1.22731.1.1.1.64 / INTEGER
off(1)
on(2) / Humidity Anticipation Enable / N/A
1.3.6.1.4.1.22731.1.1.1.65 / INTEGER
off(1)
on(2) / Self-Test Auto Acknowledge / N/A
1.3.6.1.4.1.22731.1.1.1.66 / INTEGER
Fahrenheit(1)
Centigrade(2) / Temperature Mode / N/A
1.3.6.1.4.1.22731.1.1.1.67 / INTEGER
off(1)
on(2) / Short Cycle Alarm Enabled / N/A
1.3.6.1.4.1.22731.1.1.1.68 / DisplayString
(SIZE (0..40)) / Custom Alarm Message 1 / N/A
1.3.6.1.4.1.22731.1.1.1.69 / DisplayString
(SIZE (0..40)) / Custom Alarm Message 2 / N/A
1.3.6.1.4.1.22731.1.1.1.70 / DisplayString
(SIZE (0..40)) / Custom Alarm Message 3 / N/A
1.3.6.1.4.1.22731.1.1.1.71 / DisplayString
(SIZE (0..40)) / Custom Alarm Message 4 / N/A
1.3.6.1.4.1.22731.1.1.1.72 / DisplayString
(SIZE (0..25)) / Custom Contact / N/A
1.3.6.1.4.1.22731.1.1.1.73 / INTEGER (0..5) / Adjustment rate / Minutes
1.3.6.1.4.1.22731.1.1.1.74 / INTEGER (0..900) / Optional Alarm 1 Delay / Seconds
1.3.6.1.4.1.22731.1.1.1.75 / INTEGER (0..900) / Optional Alarm 2 Delay / Seconds
1.3.6.1.4.1.22731.1.1.1.76 / INTEGER (0..900) / Optional Alarm 3 Delay / Seconds
1.3.6.1.4.1.22731.1.1.1.77 / INTEGER (0..900) / Optional Alarm 4 Delay / Seconds
1.3.6.1.4.1.22731.1.1.1.78 / INTEGER
customAlarm1(1)
fanMotorOverload(2)
humidLockout(3)
localAlarm(4)
heatAndHumidLockout(5)
heatLockout(6)
standbyPumpOn(7)
upsOn(8)
unitInStandby(9) / Optional Alarm 1 Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.79 / INTEGER
customAlarm2(1)
fanMotorOverload(2)
humidLockout(3)
localAlarm(4)
heatAndHumidLockout(5)
heatLockout(6)
standbyPumpOn(7)
upsOn(8) / Optional Alarm 2 Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.80 / INTEGER
customAlarm3(1)
fanMotorOverload(2)
humidLockout(3)
localAlarm(4)
heatAndHumidLockout(5)
heatLockout(6)
standbyPumpOn(7)
upsOn(8) / Optional Alarm 3 Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.81 / INTEGER
customAlarm4(1)
fanMotorOverload(2)
humidLockout(3)
localAlarm(4)
heatAndHumidLockout(5)
heatLockout(6)
standbyPumpOn(7)
upsOn(8)
highCondensateLevel(9) / Optional Alarm 4 Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.82 / INTEGER / Discharge Temperature Sensor Calibration / 0.1°F
1.3.6.1.4.1.22731.1.1.1.83 / INTEGER / Humidity Sensor Calibration / 0.1%RH
1.3.6.1.4.1.22731.1.1.1.84 / INTEGER / Return Temperature Sensor Calibration / 0.1°F
1.3.6.1.4.1.22731.1.1.1.85 / INTEGER
none(1)
pri(2)
pri-sec(3)
pri-pri(4)
pri-sec-pri-sec(5) / Compressor Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.86 / INTEGER
off(1)
one-with-limits(2)
two-with-limits(3)
one-no-limits(4)
two-no-limits(5) / Dehumidifier Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.87 / INTEGER
none(1)
one-compressor(2)
two-compressors(3) / Energy Saver Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.88 / INTEGER
none(1)
one-heat-strip(2)
two-heat-strips(3)
three-heat-strips(4)
hot-water(5) / Heater Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.89 / INTEGER
none(1)
computer-non-modutating(2)
computer-modulating(3)
comfort-non-modulating(4)
comfort-modulating(5) / Humidifier Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.90 / INTEGER
none(1)
chilled-water(2)
energy-saver(3)
aux-chilled-water(4) / Chilled Water Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.91 / INTEGER
0-10 VDC(1)
4-7 VDC(2)
6-9 VDC(3)
7-10 VDC(4) / Water Valve Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.92 / INTEGER
normal(1)
reverse(2) / Reverse Water Valve Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.93 / INTEGER
smart(1)
pid(2)
setpoint-deviation(3) / Control Logic Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.94 / INTEGER
auto(1)
one-leads(2)
two-leads(3) / Lead-Lag Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.95 / INTEGER (0..1000) / Maintenance Interval / Hours
1.3.6.1.4.1.22731.1.1.1.96 / INTEGER (0..99) / Front Panel Password / N/A
1.3.6.1.4.1.22731.1.1.1.97 / INTEGER
not-used(1)
data-processing-manager(2)
maintenance-engineer(3)
service-company(4)
custom-contact-message(5) / Person To Contact / N/A
1.3.6.1.4.1.22731.1.1.1.98 / INTEGER
auto-no-message-or-alarm(1)
auto-message-and-alarm(2) manual-msg-alarm-relay(3) / Reset Mode / N/A
1.3.6.1.4.1.22731.1.1.1.99 / INTEGER
off(1),
short(2)
long(3)
full(4) / Buzzer Configuration / N/A
1.3.6.1.4.1.22731.1.1.1.100 / OCTET STRING
Each octet represents one alarm selection. See Alarm Status (1.3.6.1.4.1.22731.1.1.1.38) for specific alarm codes. / Alarm Relay 1 Settings / N/A

2.5Relay Expansion Card Status (Read Only)

Object Identifier / Type / Description / Units
1.3.6.1.4.1.22731.1.1.2.1 / OCTET STRING
Each octet represents one alarm selection. See Alarm Status (1.3.6.1.4.1.22731.1.1.1.38) for specific alarm codes. / Alarm Relay 2 Settings / N/A
1.3.6.1.4.1.22731.1.1.2.2 / OCTET STRING
Each octet represents one alarm selection. See Alarm Status (1.3.6.1.4.1.22731.1.1.1.38) for specific alarm codes. / Alarm Relay 3 Settings / N/A

2.6Analog Expansion Card Status (Read Only)

Object Identifier / Type / Description / Units
1.3.6.1.4.1.22731.1.1.3.1 / INTEGER / Analog Sensor 1 Value / N/A
1.3.6.1.4.1.22731.1.1.3.2 / INTEGER
not-installed(1)
input-voltage-a-b(2)
input-voltage-a-c(3)
input-voltage-b-c(4)
output-voltage-a-b(5)
output-voltage-a-c(6)
output-voltage-b-c(7)
input-current-a(8)
input-current-b(9)
input-current-c(10)
output-current-a(11)
output-current-b(12)
output-current-c(13)
neutral-current(14)
ground-current(15)
frequency(16)
power(17)
cond-water-supply-temp(18)
cond-water-return-temp(19)
chill-water-supply-temp(20)
chill-water-return-temp(21)
supply-air-temp(22)
return-air-temp(23)
cond-water-flow(24)
chill-water-flow(25)
zone-air-temp(26)
zone-air-humidity(27)
outside-air-temp(28)
outside-air-humidity(29)
discharge-pressure(30)
suction-pressure(31)
diff-pressure(32)
pressure(33)
flow(34) / Analog Sensor 1 Name / N/A
1.3.6.1.4.1.22731.1.1.3.3 / INTEGER
VAC(1)
amps(2)
Hz(3)
kW(4)
degrees F(5)
degrees C(6)
gpm(7)
percent-RH(8)
psig(9)
inches-water(10)
psi(11) / Analog Sensor 1 Units / N/A
1.3.6.1.4.1.22731.1.1.3.4 / INTEGER
0-10 VDC(1)
0-5 VDC(2)
4-20 mA(3) / Analog Sensor 1 Type / N/A
1.3.6.1.4.1.22731.1.1.3.5 / INTEGER / Analog Sensor 1 Minumum Value / N/A
1.3.6.1.4.1.22731.1.1.3.6 / INTEGER / Analog Sensor 1 Maximum Value / N/A
1.3.6.1.4.1.22731.1.1.3.7 / INTEGER / Analog Sensor 1 Calibration / N/A
1.3.6.1.4.1.22731.1.1.3.8 / INTEGER / Analog Sensor 2 Value / N/A
1.3.6.1.4.1.22731.1.1.3.9 / INTEGER
not-installed(1)
input-voltage-a-b(2)
input-voltage-a-c(3)
input-voltage-b-c(4)
output-voltage-a-b(5)
output-voltage-a-c(6)
output-voltage-b-c(7)
input-current-a(8)
input-current-b(9)
input-current-c(10)
output-current-a(11)
output-current-b(12)
output-current-c(13)
neutral-current(14)
ground-current(15)
frequency(16)
power(17)
cond-water-supply-temp(18)
cond-water-return-temp(19)
chill-water-supply-temp(20)
chill-water-return-temp(21)
supply-air-temp(22)
return-air-temp(23)
cond-water-flow(24)
chill-water-flow(25)
zone-air-temp(26)
zone-air-humidity(27)
outside-air-temp(28)
outside-air-humidity(29)
discharge-pressure(30)
suction-pressure(31)
diff-pressure(32)
pressure(33)
flow(34) / Analog Sensor 2 Name / N/A
1.3.6.1.4.1.22731.1.1.3.10 / INTEGER
VAC(1)
amps(2)
Hz(3)
kW(4)
degrees F(5)
degrees C(6)
gpm(7)
percent-RH(8)
psig(9)
inches-water(10)
psi(11) / Analog Sensor 2 Units / N/A
1.3.6.1.4.1.22731.1.1.3.11 / INTEGER
0-10 VDC(1)
0-5 VDC(2)
4-20 mA(3) / Analog Sensor 2 Type / N/A
1.3.6.1.4.1.22731.1.1.3.12 / INTEGER / Analog Sensor 2 Minumum Value / N/A
1.3.6.1.4.1.22731.1.1.3.13 / INTEGER / Analog Sensor 2 Maximum Value / N/A
1.3.6.1.4.1.22731.1.1.3.14 / INTEGER / Analog Sensor 2 Calibration / N/A
1.3.6.1.4.1.22731.1.1.3.15 / INTEGER / Water Detect Rope Value / N/A
1.3.6.1.4.1.22731.1.1.3.16 / INTEGER
1K(1)
2K(2)
5K(3)
10K(4)
20K(5)
50K(6)
100K(7)
200K(8)
500K(9)
1000K(10)
2000K(11)
5000K(12)
10000K(13)
20000K(14)
50000K(15) / Water Detect Rope Threshold / N/A