FUNCTIONAL TEST CHECKLIST: FT SECDRS -
SECURITY DOORS (SECDRS) - ______
Specification Section _____
Project:______Project No:______
Associated Equipment:
____Door hardware
____Card readers
____Omron controller
____Other______
Other Related Tests: ______
1. Participants
Name
/ Firm / ParticipationParty filling out this form & witnessing ______Date of test ______
Approvals. This filled-out checklist has been reviewed. Its completion is approved. Exceptions are noted below or attached.
______
General Contractor [Construction Manager] Date
______
Commissioning Authority/Agent Date Owner’s Representative Date
2. Prerequisite Checklist
a) The prefunctional checklist for this security door is complete and approved: Yes / No
b) All A/E punchlist items for this and related equipment are corrected: Yes / No
c) Sequence of operation is attached: Yes / No
d) These functional test procedures reviewed and approved by installing contractor and applicable subcontractors: Yes / No
3. Functional Testing Procedure
Step / Mode / Test Procedure / Expected Response / Pass (Y/N)1 / Lock / Command/mode initiated remotely:
a) Swipe card in reader.
b) Manually attempt to open door (without using panic release). / Verify by visual inspection that:
a) Door does not open.
b) Door does not open.
2 / Open / Command/mode initiated remotely:
a) Push/pull door, without card swipe.
b) Activate automatic door opener, without card swipe. / Verify by visual inspection that:
a) Door opens.
b) Door opens.
3 / Unlock / Command/mode initiated remotely:
a) Push/pull door, without card swipe.
b) Activate automatic door opener, without card swipe / Verify by visual inspection that:
a) Door opens.
b) Door opens
4 / Normal / Command/mode initiated remotely:
a) Swipe card.
b) Manually attempt to open door (without using panic release). / Verify by visual inspection that:
a) Door opens, closes and locks.
b) Door does not open.
5 / Panic Release / Command/mode initiated remotely, door placed in Normal mode:
a) Manually push panic bar/button and open door.
b) Swipe card after horn sounds. / Verify locally that:
a) Door opens, alarm sounds.
b) Alarm stops after card swipe, and door locks upon closing.
6 / Panic Release / Command/mode initiated remotely, door placed in Lock mode:
a) Manually push panic bar/button and open door.
b) Swipe card after horn sounds. / Verify locally that:
a) Door opens, alarm sounds.
b) Alarm stops after card swipe, and door locks upon closing.
4. System Status
a) All items of functional test passed: Yes / No
b) System is activated and online, deficiencies, listed below, do not prevent operation:
Yes / No
c) System is placed in (circle mode):
Lock / Open / Unlock / Normal / Relock / Watch
Comments:
-- END OF TEST --
FUNCTIONAL TEST CHECKLIST – SECURITY DOORS
03/02 13998-01-1 OF 2 D:\DOCS\DIV1\03-02\13998-01.DOC