SELECTIVE COORDINATION INSPECTION FORM
This form provides documentation to assure compliance with the following 2014 NFPA 70, National Electrical Code®requirements for selective coordination found in articles 620, 645, 695, 700, 701,708and “coordination” per article 517.
JOB #: ______NAME: ______
LOCATION: ______FIRM: ______
COMPLIANCE CHECKLIST
------
1. Selective Coordination Definition – Article 100
------
“Coordination (Selective).The localization of an overcurrentcondition to restrict outages to the circuit or equipmentaffected, accomplished by the selection and installation ofovercurrent protective devices and their ratings or settingsfor the full range of available overcurrents, from overloadto the maximum available fault current, and for the fullrange of overcurrent protective device opening times associatedwith those overcurrents."
------
2. Verify Selective Coordination Requirements
------
ARTICLE 620 – ELEVATORS, DUMBWAITERS, ESCALATORS, MOVING WALKWAYS,
WHEELCHAIR LIFTS AND STAIRWAY CHAIR LIFTS YES NO N/A
620.62 Selective Coordination. Requires the overcurrent devices in each disconnecting
means to be selectively coordinated with any other supply sided overcurrent protective devices
wheremore than one driving machine disconnectingmeans is supplied by a single feeder.
ARTICLE 645 – INFORMATION TECHNOLOGY EQUIPMENT
645.27 Selective Coordination. Requires critical operations data system(s) overcurrentYES NO N/A
devicesto be selectively coordinated with all supply side overcurrent protective devices.
ARTICLE 695 – FIRE PUMPS
695.3(C)Multibuilding Campus-Style Complexes.YES NO N/A
(3) Selective Coordination. Requires the overcurrent protectivedevice(s) in eachdisconnecting
meansto be selectivelycoordinated with any other supply-side overcurrent protectivedevice(s).
ARTICLE 700 – EMERGENCY SYSTEMS
700.28 Selective Coordination. Requires emergency systems overcurrent devices to YES NO N/A
beselectivelycoordinated with all supply side overcurrent protective devices.
ARTICLE 701 – LEGALLY REQUIRED STANDBY SYSTEMS
701.27Selective Coordination. Requires legally required standby system(s) YES NO N/A
overcurrentdevices to be selectively coordinated with all supply side overcurrent protective devices.
ARTICLE 708 – CRITICAL OPERATIONS POWER SYSTEMS (COPS)
708.54 Selective Coordination. Requires critical operations power system(s) YES NO N/A
overcurrentdevices to be selectively coordinated with all supply side overcurrent protective devices.
ARTICLE 517 – HEALTHCARE FACILITIES
517.30 Essential Electrical Systems for Hospitals.YES NO N/A
(G) Coordination. Requires overcurrent protective devices servingthe essential electrical system
to be coordinated for theperiod of time that a fault’s duration extends beyond0.1 second.
Informational Note: The terms coordination and coordinatedas used in this section do not cover the full range ofovercurrent conditions.
------
3. Verify Selective Coordination Documentation
------
Per 620.62, 700.28, 701.27 and 708.54
Selective coordination is required to be selected by a licensedprofessional engineer or other YES NO N/A
qualified persons engagedprimarily in the design, installation, or maintenance of electricalsystems. The selection must be documented and madeavailable to those authorized to design, install, inspect, maintain, and operate the system.
Note: Documentation can include short-circiut study, time-current curves, manufacturer selective coordination tables, and required types, ratings and settings of overcurrent protection devices to achieve selective coordination.
______Signature ______Date