AT&T INSTALLATION REQUIREMENT CHANGE NOTIFICATION - ATT-TP-76300-216
TO: ALL AT&T INSTALLATION SUPPLIERS Date: 2/25/14
EFFECTIVE DATE: 5 days from posted date or as per Supplier’s Contract
Submitter’s Name: Charles Matlack
TP: TP76300 Subject: Standby Engine/Alternator Sets Action: Add: Modification: Delete:
Section: U Section Title: Standby Engine/Alternator Sets
Subsection: 2 Section Title: Requirements
Subsection: 2.1 Subsection Title: General
Prior to Change:
N/A
Post Change:
2.1.2 Only cabling directly associated with the Engine / Alternator and fuel system shall be run into and out of the Engine/Alternator room/enclosure. Examples of permitted cable includes, the grounding cable, telecommunication cables (commonly referred to as telephones), Alarm Cabling, Telemetry, power for Engine/Alternator accessories, and the AC output of the Engine / Alternator set.
Questions relative to this IRCN should be addressed to Serena Kwong at (510) 796-1097.
Serena Kwong
ASSOC NTWK PROC & QUALITY MGR
Global Engineering Support
Access the TP's on the Extranet Site https://ebiznet.sbc.com/sbcnebs
Concurred
Mike Cassidy - Area Manager Network Process & Quality Date: 2/21/14
Steve Martin – Principal – Product Development Engineer Date: 2/19/14
Release Approved
Serena Kwong - Associate Network Process & Quality Manager Date: 2/25/14
Page 1 of 1