Specifications

Shop Fabricated Steel Double Wall Contained Rectangle Envirotank for Flammable and Combustible Liquids

Parts Manual

/ Tank to come with a parts manual.
Parts manual to include dip chart for calculating liters contained in the tank.
The tank manufacturer’s recommended maintenance and installation instructions must be included.
Shop drawings used to build the tank.
Parts manual must list items used to construct the tank along with name of original equipment manufacturer.
Parts manuals from third party manufacturers must also be included.
Tank specific quality control sheets are required.
Parts manual must also include tank warranty details.

Tank

/ Tank capacity of 5,000 Liters.
Tank height not to exceed 63”
Tank width not to exceed 48”
Tank length not to exceed 120”
Tank conforms to ULC-C142.18 specifications.
Tank air tested to 3-5 PSI.
Tank to be equipped with a water draw off and dipping port.
Tank to be equipped with lifting lugs.
Tank to be equipped with grounding lugs.
Standard ULC, Tank Content and Warning decals required.
Containment built to ULC-C142.18 specifications.
110% containment
Containment air tested to 3-5 PSI.

Exterior Finish

/ Sandblasted to SSPC-SP6 (brush blast)
Exterior to be finished with a two coat painting system to insure complete paint coverage.
Primer to be Phillips epoxy grey.
Primer to be applied to 2-3 total mils. (DFT)
Paint to be Phillips high build white enamel. (or customer specified colors)
Paint to be applied to 2-3 total mils. (DFT)

Access to Tank Top

(Other Options Available) / Tank to be equipped stairs and catwalk.
Stairs and catwalk are to be galvanized to eliminate rust.

Venting

/ Tank to be equipped with ULC approved emergency vent.
Containment to be vented as per ULC specifications.
Tank to be equipped with Vent cap and riser pipe.
If the liquid stored is prone to evaporation the vent cap must be a pressure vacuum vent.
The vent size must be equal or larger than the fill port.

Filling

(Other Options Available) / Lockable square spill box c/w removable fitting plate.
Fitting plate c/w 4” fill port, 2” dip port & ¾” spill box drain port

Overfill Prevention

(Other Options Available) / Tank to be equipped with an overfill prevention alarm.
Alarm control box must be designed to ship installed on the tank.
The control box must be suitable for a hazardous location as per “The Canadian Electrical Code”.
Overfill alarm to be set to sound when the tank’s fluid level reaches 95% thus indicating that filling procedure must be stopped.

Discharge

(Other Options Available) / Tank to be equipped with a 2” coupler.

Gauging

(Other Options Available) / One-piece metric dip stick with wear button required.

Note:

1.Replace the underlined text with the correct text from AGI’s dimensional chart.

2.If an alternative option is required please do not hesitate to contact us. The above specifications are for an average Envirotank. There are many options that may better suit the customer’s application.

3.For the most current specifications please visit our website at .