Project 1 –Contingency Ranking byTime Domain Simulations
Problem and Approach:
Consider the 179-bus WECC system model. Powerflow and dynamic data in PSS/E format will be provided.
Its loads can be represented by one of the following load models:
- Load Model #1: P load is represented as 100% Constant Current load; Q load is represented as 100% Constant Z; convert P load to 100% Constant Z when the bus voltage is lower than 0.7pu
- Load Model #2: All loads P and Q represented as Constant Impedance
- Load Model #3: All loads P and Q represented at Constant Current
- Load Model #4: All loads P and Q represented at Constant Power
Task 1: Rank N-1 contingencies
Adopt Load Model #1 for all buses. Consider the following N-1 contingencies:
- Add a three-phase short-circuit fault at each end (zero distance to one bus) of every transmission line rated at 500kV
- After a fault duration time (clearing time), trip the line at both ends to isolate the fault
Note: if the line trip with a contingency splits the system into two segments, e.g. a contingency on line 73-75, it should not be counted in the N-1 list (since it is already addressed by grid design or planning).
Rank all contingencies by this stability criterion: Let the fault clearing time be 5 cycles. Simulate each contingency for 10 seconds and calculate stability margin index by the largest angle distance max, as illustrated by the figure and table below.
Identify the number (denoted by N) of contingencies that cause angular instability (<0) and the top-5 critical contingencies from the ranking. Analyze why those 5 contingencies more easily cause instability than the others.
Task 2: Determine the Critical Clearing Time (CCT)
For each of the top-5 critical contingencies, determine its critical clearing time (CCT), i.e. the longest fault clearing time with ≥0. An approach could be to simulate the contingency for 10 seconds with a fault clearing timethat is gradually increased from 1 cycles to 20 cycles at a small stepuntilthe frist time <0. Rank the 5 critical contingencies by their CCTs and compare the ranking with that based on values of .
Task 3: Compare different load models
For the top-5critical contingencies identified, check theirCCTs and stability margin indices for simulations withLoad Models #2 ~ #4. Compare the results with those from Load Model #1.
Deliverable
- Project presentation on 4/24
- A no more than 6pages report by 4/30. Use the IEEE paper template at
Hints:
You may use either PSS/E or Powertech’s TSAT software to do simulations. TSAT software integrates that stability criterion and can do automatic CCT search.