SECTION 15410 (22 42 43)
THERMOSTATIC MIXING VALVES
Specifier Notes: This section coversMoen CommercialModel 104451 adjustable-temperature thermostatic mixing valve. ConsultMoen Commercial for assistance in editing this section for the specific application.
PART 1GENERAL
1.1SECTION INCLUDES
A.Adjustable-temperature thermostatic mixing valves.
1.2RELATED REQUIREMENTS
Specifier Notes: Edit the following list of related sections as required. Delete related sections not required. List other sections with work directly related to this section.
A.Section 15140 (22 11 00) – Domestic Water Piping (Facility Water Distribution): Supply connections to commercial plumbing fixtures.
1.3REFERENCE STANDARDS
Specifier Notes: List reference standards mentioned in this section, complete with designations and titles. Delete reference standards not included in this edited section. This article does not require compliance with reference standards, but is merely a listing of those used.
A.ASSE 1070 – Performance Requirementsfor Water Temperature Limiting Devices.
1.4SUBMITTALS
Specifier Notes: Edit submittal requirements as required. Delete submittals not required.
A.Comply with Section 01330 (01 33 00)–Submittal Procedures.
B.Product Data: Submit manufacturer’s product data, including installation instructions.
C.Manufacturer’s Certification: Submit manufacturer’s certification that materials comply with specified requirements and are suitable for intended application.
D.Operation and Maintenance Instructions: Submit manufacturer’s operation and maintenance instructions, includingparts list.
E.Warranty Documentation: Submit manufacturer’s standard warranty.
1.5QUALITY ASSURANCE
A.Manufacturer’s Qualifications: Manufacturer regularly engaged for past 10 years in manufacture of commercial plumbing fixtures of similar type to that specified.
1.6DELIVERY, STORAGE, AND HANDLING
A.Delivery and Acceptance Requirements: Deliver materials to site in manufacturer’s original, unopenedcontainers and packaging, with labels clearly identifying product name and manufacturer.
B.Storage and Handling Requirements:
1.Store and handle materials in accordance with manufacturer’s instructions.
2.Keep materials in manufacturer’s original, unopened containers and packaging until installation.
3.Store materials in clean, dry area indoors.
4.Protect materials during storage, handling,and installation to prevent damage.
1.7WARRANTY
A.Warranty Period: 5 years.
PART 2PRODUCTS
2.1MANUFACTURER
A.Moen Incorporated, 25300 Al Moen Drive, North Olmsted, Ohio44070. Toll Free (800) 289-6636. Website E-mail .
2.2THERMOSTATIC MIXING VALVES
A.Adjustable-Temperature Thermostatic Mixing Valves: Model 104451.
1.Thermostatic mixing valve with adjustable-temperature control cartridge.
2.Brass construction.
3.Cap: Vandalresistant.
4.1/2-inch FNPT connections with 3/8-inch compression adapter.
5.Hot and Cold Check Valves: Preventpossible backflow on water supply inlets.
6.Internal Strainer: Stainless steel. Protect against line trash.
7.Operation:
a.Factory Preset: 105 degrees F (40 degrees C).
b.Adjustable from 95 degrees F (35 degrees C) to 115 degrees F (46 degrees C), with plus or minus 3.5-degree F (2-degree C) temperature accuracy.
c.Working Pressure:
1)Maximum: 125 psi.
2)Minimum: 45 psi.
d.Flow Rate at 45 psi: 3.7 gpm.
e.Cold Water Supply: 39 to 80 degrees F (4 to 27 degrees C).
f.Hot Water Supply: 120 to 180 degrees F (49 to 82 degrees C).
8.Cartridge: Paraffin-based thermostatic engine.
9.Compliance: ASSE 1070.
PART 3EXECUTION
3.1EXAMINATION
A.Examine areas to receiveadjustable-temperature thermostatic mixing valves.
B.Notify Architect of conditions that would adversely affect installation or subsequent use.
C.Do not begin installation until unacceptable conditions are corrected.
3.2INSTALLATION
A.Installadjustable-temperature thermostatic mixing valves in accordance with manufacturer’s instructions at locations indicated on the Drawings.
B.Install adjustable-temperature thermostatic mixing valves level, plumb, and without leaks.
3.3ADJUSTING
A.Adjust adjustable-temperature thermostatic mixing valves for proper operation in accordance with manufacturer’s instructions.
B.Remove and replace damaged components that cannot be successfully repaired.
3.4PROTECTION
A.Protect installedadjustable-temperature thermostatic mixing valves from damage during construction.
END OF SECTION
Model 10445115410 (22 42 43) - 1