In response to the pre bid meeting held on 14.08.2012 at ICSIL, certain queries were received from various firms / OEM. After careful examination of queries and suggestions put forth by the intending bidders, following amendments/additions have been made in the tender as noted below. All intending vendors are requested to take a note of it and quote their rates accordingly.

Sr. No. / Clause No. / Page No. / Original clause / Amendment/Clarification
1. / 24 / 5 / Earnest Money Deposit: All the OEM bidders will have to submit an earnest money deposit (EMD) of Rs. 2,00,000/- only (Rs. Two Lac only) in favour of “ICSIL, Delhi”, in the form of an unconditional and irrevocable Bank Guarantee issued by a nationalized commercial bank and valid for a period of three months. / This clause has been waived off.
2. / 25 / 5 / Performance Guarantee:OEMsshortlisted for empanelment under rate contract shall have to deposit a performance Bank Guarantee of Rupees Five Lakhs (Rs.5,00,000/-) valid for a period of fourteen months with a liability for extension up to the extended contract period.
The EMD will be released after empanelment of the OEMs under Rate Contract and subject to submission of performance bank guarantee of prescribed amount valid for a period of Contract/extended contract period. / Performance Guarantee:AllOEMs / Authorized vendor of OEM (Even if they are registered with NSIC) shortlisted for empanelment under rate contract shall have to deposit a performance Bank Guarantee of Rupees Five Lakhs (Rs.5,00,000/-) valid for a period of fourteen months with a liability for extension up to the extended contract period.
3 / 27 (iii) / 6 / OEMs shortlisted, may authorize twooftheir business partners in case they do not deal directly with the supply of the empanelled items. Details of the Business partner/authorized vendor should be submitted as per the format given at Annexure-IX.Distribution of work amongst the two vendors shall be done on equitable basis to the maximum possible of work order value. / It is not compulsory for OEM to nominate two vendors. They are at liberty to nominate one / two of their authorized vendor. ICSIL, if desires, may opt for change of vendor not suited to it.Distribution of work amongst the two vendors shall be done on equitable basis to the maximum possible of work order value.
4 / 27 (ii) / 6 / If the variation in prices of L2, L3, L4…OEMs is in the range of 20% of the rates quoted by L1 OEM, all such L2, L3, L4… OEMs may offer their prices to match at par with the rates quoted by L1 OEM of similar specification. / Matching of L1 prices will be done separately for the MNC and Indigenous brands of Desktops, Laptops, etc. if felt necessary.
5 / 18 / 4 / Warranty Period:The warranty of complete system, including software support, would be 3 years / 5 Years (As the case may be) from the date of installation and acceptance. Warranty will cover repair/replacement of all defective parts, if any, with the same branded make for any part replaced. Software media will be replaced by the supplier against any manufacturing defects. The warranty includes onsite maintenance.Limited/ carry-in warranty will not be accepted. The supplier will provide after-sale service during the warranty period from Delhi or from the nearest place of installation site. The supplier will attend the service call during warranty and maintenance period immediately but not later than one working day for Delhi and NCR, failing which, penalty shall be levied @ Rs.500/- (Rs. Five Hundred only ) per day delay for totally down system and @ 200/- per day delay for partially down systems. / The UPS are to be
quoted with 3 and 5
years warranty.
However the warranty
of battery shall be for
one year as it is a
consumable item.
6 / 14 / 3 / Preventive Maintenance:-The vendor will visit the computer installation site at least once in a quarter for preventive maintenance (cleaning, dusting etc.) during warranty & AMC period even if no complaint lodged by the purchaser/user department. The Bank Guarantee of 10% of total order value submitted by the vendors for a period of 38 months will be released by ICSIL only after verifying adherence to the preventive maintenance reports and call reports in respect of the Computer Systems supplied or on submission of a certificate of satisfactory completion of services by the vendor during warranty period of 36 months. The purchasing Departments/organizations shall maintain logs/registers wherein the service visits (both preventive and call services) would be recorded. / Clause 14, Page No.3 of Tender Document is not applicable to UPS as batteries being used will be 100% sealed maintenance free.

Printers

Item Description / Item Code / Tender Page No. / Original Configuration / Amendment/Clarification
Fargo Printers / FP – Mod 2 / 36 / Single Side Printer / Double Side Printer
Dot matrix Printer
(New Model) / DMP – 8 / To be added / Pin24 ,Colum:136,Speed at 10cpi : 600CPS, and Speed at 15 cpi : 900CPS,Port : Parallel Centronics (Bi. Directional) and Serial Rs232
Dot matrix Printer
(New Model) / DMP – 9 / To be added / Pin 24, Colum:136,Speed at 10cpi: 800, and Speed at 15 cpi: 1100CPS,Port : Parallel Centronics (Bi. Directional) and Ethernet 10/1000 BaseT
Laserjet Printer / LJP-1 / 29 / Print Speed in PPM (A4 size)-14 / Print Speed in PPM (A4 size)-12
Laserjet Printer / LJP-2 / 29 / Print Speed in PPM (A4 size)-32
Memory - NA / Print Speed in PPM (A4 size)-35 Memory 192 MB
Laserjet Printer / LJP – 5 / 29 / Network card 10/100-NA / With Network card 10/100
Laserjet Printer / LJP – 12 / 30 / Print Speed in PPM (A4 size)-24 / Print Speed in PPM (A$ size)-35PPM
Multifunction Printer / MFP – Mono 03 / 34 / 1200 X 1200 dpi / 600 X 600 dpi
Multifunction Printer / MFP – Mono 05 / 34 / 75000 PPM duty cycle / 20000 PPM duty cycle
Multifunction Colour Laser Printer / MFP-Color-3 / 34 / A4 20PPM in Mono &Colour
160 MB RAM / A4 16PPM in Mono &Colour
128 MB RAM
Multifunction Colour Laser Printer / MFP-Color-5 / 35 / Network-NA
160 MB RAM / Network Card 10/100
128 MB RAM
Document Scanner / DSCAN – 1 / 32 / Speed in PPM – NA / Speed in PPM – 8
Document Scanner / DSCAN-3 / 33 / Resolution in dpi 300 Speed in PPM 20, ADF Capacity 50 Flat Bed Size N.A Document Size Legal / Resolution in dpi 600 x 600 Speed in PPM 25, ADF Capacity 30 Flat Bed Size N.A Document Size Legal
Document Scanner / DSCAN-4 / 33 / Resolution in dpi 300 Speed in PPM 30, ADF Capacity 50 Flat Bed Size legal Document Size Legal / Resolution 600 x 600 dpi, Speed 30 Pages, ADF capacity 50 Sheets, , Flat bed through USB Port Document Size Legal
Document Scanner / DSCAN-5 / 33 / Resolution in dpi 300 Speed in PPM 25, ADF Capacity 50 Flat Bed Size A4 Document Size A4 / Resolution 600 x 600 dpi, Speed 30 Pages, ADF capacity 50 Sheets, , Flat bed through USB Port, Document Size A4
Document Scanner / DSCAN-7 / 33 / Resolution in dpi 600 Speed in PPM 60, ADF Capacity 50 Flat Bed Size A4 Document Size Legal / Resolution 600 x 600 dpi, Speed 60 Pages, ADF capacity 150 Sheets, USB Port, Document Size legal,
Document Scanner / DSCAN-9 / 33 / Speed in PPM - NA / Speed in PPM – 8
Document Scanner
(New Model) / DSCAN -10 / To be added / Resolution in dpi 600 x 600 Speed in PPM 25, ADF Capacity 30 ,Flat Bed Size A4, Document Size Legal Thru ADF
Document Scanner
(New Model) / DSCAN -11 / To be added / Resolution in dpi 600 x 600 Speed in PPM 30, ADF Capacity 50, Flat Bed Size A4, Document Size Legal Thru ADF
Duplex Document Scanner
(New Model) / DSCAN -12 / To be added / Resolution in dpi 600 x 600 Speed in 45 pages/90 images, ADF Capacity 150, Flat Bed Size A4 ,Document Size Legal Thru ADF
Duplex Document Scanner
(New Model) / DSCAN -13 / To be added / Resolution in dpi 600 x 600 Speed in 50 pages/100 images, ADF Capacity 50 ,Flat Bed Size A4, Document Size Legal Thru ADF
Duplex Document Scanner
(New Model) / DSCAN -14 / To be added / Resolution in dpi 600 x 600 Speed in 50 pages/100 images, ADF Capacity 50, Flat Bed Size A4, Document Size Legal Thru ADF
Desktop Middle Level / DTM/i5-2320/Q67/6 / 14 / Intel Original Motherboard / OEM Motherboard

Modified specification of Online and line interactive UPS are as follows:

On-Line UPS SYSTEM

Sr. No. / Product description / Compliance Y/N
UPS-OL-1. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 8000
UPS-OL-2. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 16000
UPS-OL-3. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type Rating of UPS 10KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 32000
UPS-OL-4. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 15KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 12000
UPS-OL-5. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 15KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 24000
UPS-OL-6. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 15KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 48000
UPS-OL-7. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 20KVA, Indicative back up time30 minutes. Minimum Battery VAH - 16000
UPS-OL-8. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 20KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 32000
UPS-OL-9. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 20KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 64000
UPS-OL-10. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 30KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 24000
UPS-OL-11. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 30KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 48000
UPS-OL-12. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 30KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 96000
UPS-OL-13. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 8000
UPS-OL-14. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output. Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 16000
UPS-OL-15. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 32000
UPS-OL-16. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 15KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 12000
UPS-OL-17. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 15KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 24000
UPS-OL-18. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 15KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 48000
UPS-OL-19. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 20KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 16000
UPS-OL-20. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 20KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 32000
UPS-OL-21. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 20KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 64000
UPS-OL-22. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 30KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 24000
UPS-OL-23. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 30KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 48000
UPS-OL-24. / On-Line UPS with isolation transformer suitable for Three Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 30KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 96000
UPS-OL-25. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 1.0KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 800
UPS-OL-26. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 1.0KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 1600
UPS-OL-27. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 1.0KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 3200
UPS-OL-28. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 2.0KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 1600
UPS-OL-29. / On-Line upS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 2.0KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 3200
UPS-OL-30. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 2.0KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 6400
UPS-OL-31. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 3.0KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 2400
UPS-OL-32. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 3.0KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 4800
UPS-OL-33. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 3.0KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 9600
UPS-OL-34. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 5.0KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 4000
UPS-OL-35. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 5.0KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 8000
UPS-OL-36. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 5.0KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 16000
UPS-OL-37. / On-Lme UPS with isolation transformer suitable for Three Phase AC Input and Three Phase AC Output, Floor Mounted type. Rating of UPS 6.0KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 4800
UPS-OL-38. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 6.0 KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 9600
UPS-OL-39. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 6.0KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 19200
UPS-OL-40. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 7.5KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 6000
UPS-OL-41. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 7.5KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 12000
UPS-OL-42. / On-Line UPS with isolation transformer suitable for Single Phstee AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 7.5KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 24000
UPS-OL-43. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 30 minutes. Minimum Battery VAH - 8000
UPS-OL-44. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 60 minutes. Minimum Battery VAH - 16000
UPS-OL-45. / On-Line UPS with isolation transformer suitable for Single Phase AC Input and Single Phase AC Output, Floor Mounted type. Rating of UPS 10KVA, Indicative back up time 120 minutes. Minimum Battery VAH - 32000
UPS-OL-46. / On Line UPS Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 1.0 KVA, Indicative Back Up Time 30 minutes. Minimum Battery VAH - 800
UPS-OL-47. / On Line UPS. Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 1.0 KVA, Indicative Back Up Time 60 minutes. Minimum Battery VAH - 1600
UPS-OL-48. / On Line UPS. Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 1.0 KVA, Indicative Back Up Time120 minutes. Minimum Battery VAH - 3200
UPS-OL-49. / On Line UPS. Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 2.0 KVA, Indicative Back Up Time 30 minutes. Minimum Battery VAH - 1600
UPS-OL-50. / On Line UPS. Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 2.0 KVA, Indicative Back Up Time 60 minutes. Minimum Battery VAH - 3200
UPS-OL-51. / On Line UPS, Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 2.0 KVA, Indicative Back Up Time 120 minutes. Minimum Battery VAH - 6400
UPS-OL-52. / On Line UPS, Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 3.0 KVA, Indicative Back Up Time 30 minutes. Minimum Battery VAH - 2400
UPS-OL-53. / On Line UPS. Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 3.0 KVA, Indicative Back Up Time 60 minutes. Minimum Battery VAH - 4800
UPS-OL-54. / On Line UPS, Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 3.0 KVA, Indicative Back Up Time 120 minutes. Minimum Battery VAH - 9600
UPS-OL-55. / On Line UPS. Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 5.0 KVA, Indicative Back Up Time 30 minutes. Minimum Battery VAH - 4000
UPS-OL-56. / On Line UPS. Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 5.0 KVA, Indicative Back Up Time 60 minutes. Minimum Battery VAH - 8000
UPS-OL-57. / On Line UPS, Solid State, Single Phase Input, Single Phase Output without Isolation Transformer. Rating of UPS : 5.0 KVA, Indicative Back Up Time 120 minutes. Minimum Battery VAH - 16000
TECHNICAL SPECIFICATIONS OF ONLINE UPS SYSTEMS
Sl No. / SPECIFICATIONS
1 / GENERAL / UPS SHOULD BE FREE FROM WORKMANSHIP DEFECTS, SHARP EDGES, NICKS, SCRATCHES, BURS ETC. ALL FASTENENRS SHOULD BE FIXED PROPERLY. ALL PARTS OF EQUIPMENT SHOULD BE COMPLETE AND FUNCTIONAL
2 / BYPASS / MANUAL BYPASS SHOULD BE PROVIDED
3 / OUTPUT POWER & CHARGING CURRENT / UPS SHOULD SUPPLY OUTPUT POWER & CHARGING CURRENT AT THE SAME TIME
4 / SWITCHING DEVICE / IGBT
5 / SWITCHING FREQUENCY : / SWITCHING FREQUENCY SHOULD BE GREATER THAN 10 kHz.
6 / KW RATING OF THE UPS : / KW RATING OF THE UPS SHOULD BE 0.70 TIMES THE KVA RATING
7 / INPUT VOLTAGE : / 160 - 260 V, 50 + 3 Hz. SINGLE PHASE A.C
8 / OUTPUT VOLTAGE : / OUTPUT VOLTAGE : 230V + 1 %, 50 + 0.5 Hz., SINGLE PHASE ( WITH ALTERNATIVE SETTING FOR 220 + 1.0% )
9 / TOTAL HARMONIC DISTORTION AT OUTPUT : / 2 % MAXIMUM FOR UPS UPTO 5 KVA AND 3% MAXIMUM FOR UPS UPTO 10 KVA ON RESISTIVE LOAD. IF THE TOTAL INPUT HARMONICS ARE LESS THAN OR EQUAL TO 10 %
10 / EFFICIENCY AT RATED OUTPUT VOLTAGE & FREQUENCY / GREATER THAN 80 %
11 / OVERLOAD : / OVERLOAD : UPS SHOULD WITHSTAND 20 % OVERLOAD FOR 10 MIN
12 / OVERVOLTAGE, SHORT CIRCUIT & OVERLOAD PROTECTION : / OVERVOLTAGE, SHORT CIRCUIT & OVERLOAD PROTECTION AT OUTPUT TERMINAL SHOULD BE PROVIDED
13 / INDICATORS PROVIDED / MAINS PRESENCE, BATTERY CHARGING & DISCHARGING, OUTPUT OVERLOAD & LOW BATTERY VOLTAGE
14 / DIGITAL METERING / DIGITAL METER TO BE PROVIDED FOR MONITORING : INPUT AC VOLTAGE , OUTPUT AC VOLTAGE, CHARGING CURRENT, FREQUENCY & BATTERY VOLTAGE
15 / BATTERIES / BATTERIES SUPPLIED WITH THE UPS SHALL BE SMF, 12 V , VRLA TYPE ONLY.
16 / TROLLEY / RACK FOR THE BATTERY BANK / TROLLEY / RACK FOR THE BATTERY BANK TO BE PROVIDED ALONG WITH THE UPS
17 / INSULATION RESISTANCE : / Minimum 100 Mega Ohm
HIGH VOLTAGE : / WITHSTANDS 1.5 KV WHEN APPLIED BETWEEN LIVE PARTS & BODY
LEAKAGE CURRENT : / LESS THAN 125 Microamps

Annexure-IV (A)