N 141/02 KNX / DALI Gateway
for communication via KNX EIB with electronic ballasts with a DALI interface,
with DALI output acc. to IEC 60929, for communication with up to 64 DALI ballasts,
with an integrated power supply with input voltage AC/DC 110 – 240V, 50 – 400Hz, for powering the gateway electronics and DALI output,
with a maximum DALI output voltage of 16V, short circuit resistant,
with a green LED for displaying the operating voltage,
with a pushbutton for switching between bus and direct operating mode,
with a yellow LED for displaying direct mode,
with one pair of push buttons for switching On/Off of all connected DALI ballasts,
with one red LED in the switching button for displaying the switching state of all DALI ballasts (permanent LED light) and displaying a DALI fault condition by blinking,
with control (switching, dimming, and setting dimming value) as well as feedback of status and lamp failure of up to 64 DALI ballasts,
with operation of each DALI ballast either as individual device or as member of one of up to 16 DALI groups,
with configurable assignment of the DALI ballasts to up to 16 DALI groups, which can only be switched and dimmed in groups including reporting status and lamp failures in groups,
with control (switching, dimming, setting dimming value) of self-contained emergency luminaires as individual luminaires or as member of a DALI group,
with distinction between self-contained emergency luminaires with one or two DALI devices,
with starting the self-conducted testing of each individual inverter and reporting the test result via bus,
with distinction between function test, short duration test, and long duration test,
with optional configuration of any DALI ballast to dim to a preset dimming value in case of emergency mode,
with locking of switching and dimming commands as well as configuration while emergency mode is activated,
with activation of emergency mode based on a configurable number of failed DALI ballasts,
with transformation of dimming commands into a temporary set point adjustment for ballasts with integrated constant light level control and directly connected light level sensor,
with one or two level timer,
with integrated scene control for up to 16 scenes,
with integrated one time or cyclical control of repeatable sequences or color effects,
with possible assignment of a CIN to a DALI ballast and with commissioning of DALI ballasts and test of channel, scene, and effect functionality within ETS,
with integrated bus coupling unit with only half a standard bus load, bus connection via bus terminal and contact system to data rail, for mounting on DIN rail EN 60715-TH35-7.5.
Width 4 MW ( 1 Modular Width = 18mm)

Manufacturer: Siemens
Order no.: 5WG1 141-1AB02

Supply, install, assign parameters,
commission and document
Material:...... / Labour:...... ….
EP:...... …... / GP:......