SECTION 13400

LOW VOLTAGE ELECTRIC METERING

Display hidden notes to specifier. (Don't know how? Click Here)

Copyright 2017 - 2017 ARCAT, Inc. - All rights reserved

** NOTE TO SPECIFIER ** Honeywell Building Control Systems; building management systems.
This section is based on the products of Honeywell Building Control Systems, which is located at:
1985 Douglas Dr. N.
Minneapolis, MN 55422
Toll Free Tel: 888-793-8193
Email: request info ()
Web: buildingcontrols.honeywell.com
[ Click Here ] for additional information.
Honeywell Building Control Solutions provides integrated product solutions in heating and heating processes, ventilation, cooling and refrigeration, air purification, zoning, humidification, air conditioning, water controls and processes, electrical devices and systems, lighting control, switches, sensors and controllers. Our technologies are found in more than 10 million buildings and a multitude of manufacturing plants around the world. Customers include original equipment manufacturers, commercial, contractors, retail, trade building managers, consulting engineers and distributors.
BACnet is a registered trademark of American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE). LON, LONMARK, LONTALK, and LONWORKS are registered trademarks of Echelon Corporation. NiagaraAX Framework is a registered trademark of Honeywell International.

PART 1 GENERAL

1.1   SECTION INCLUDES

A.   Low voltage energy monitoring submeters of the following types:

** NOTE TO SPECIFIER ** Delete items below not required for project.

1.   Single phase meters.

2.   Three phase meters.

3.   Smart meters.

4.   Compact smart meters.

1.2   RELATED SECTIONS

** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.

A.   Section 15900 - Building Management System.

B.   Section 15901 - Building Management System (WEBsN4).

1.3   REFERENCES

** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.

A.   ANSI C12.20 - American National Standard for Electricity Meters - 0.2 and 0.5 Accuracy Classes.

B.   California Energy Commission.

C.   California Type Evaluation Program (CTEP).

D.   Federal Communications Commission (FCC).

E.   Underwriters Laboratories (UL).

F.   Underwriters Laboratories Canada (cUL).

1.4   SUBMITTALS

A.   Submit under provisions of Section 01300.

B.   Product Data: Manufacturer's data sheets on each product to be used, including:

1.   Manufacturer's printed installation instructions, showing required preparation and installation procedures.

2.   Storage and handling requirements and recommendations.

3.   Installation methods.

4.   Cleaning and maintenance instructions.

C.   Closeout Submittals: Documentation of manufacturer's warranty.

1.5   QUALITY ASSURANCE

A.   Installer: Minimum 2 years experience with metering system installations.

B.   Pre-Installation Meetings: Conduct pre-installation meetings to verify project requirements, substrate conditions, construction documents, details and manufacturer's warranty requirements.

1.6   DELIVERY, STORAGE, AND HANDLING

A.   Delivery: Deliver materials in manufacturer's original, unopened, undamaged rolls/pallets with identification labels intact.

B.   Storage and Protection: Store materials protected from exposure to harmful environmental conditions and at temperature and humidity conditions recommended by the manufacturer.

1.7   PROJECT CONDITIONS

A.   Environmental Conditions: Maintain conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

1.8   WARRANTY

A.   Manufacturer's Warranty: Manufacturer's standard warranty document executed by authorized company official.

1.   PRODUCTS

1.9   MANUFACTURERS

A.   Acceptable Manufacturer: Honeywell Building Control Systems, which is located at: 1985 Douglas Dr. N.; Minneapolis, MN 55422; Toll Free Tel: 888-793-8193; Email: request info (); Web: buildingcontrols.honeywell.com

** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 01 section on product options and substitutions.

B.   Substitutions: Not permitted.

C.   Requests for substitutions will be considered in accordance with provisions of Section 01600.

** NOTE TO SPECIFIER ** Delete article if not required.

1.10   SINGLE PHASE METERS

A.   Basis of Design: Class 1000 Single Phase E-Mon Submeter by Honeywell. Provides kW and kWh data for single-phase power, revenue-grade accuracy, and self-power supply maintains reading in the event of power failure.

1.   Standards Compliance: UL and cUL listed and ANSI C12.20.

** NOTE TO SPECIFIER ** Delete voltages not required.

2.   Voltage (L-N/L-L): 120/NA.

3.   Voltage (L-N/L-L): 120/208-240.

4.   Voltage (L-N/L-L): 277/480.

** NOTE TO SPECIFIER ** Delete currents not required.

5.   Current (Amps): 25.

6.   Current (Amps): 50.

7.   Current (Amps): 100.

8.   Current (Amps): 200.

** NOTE TO SPECIFIER ** Delete enclosure types not required.

9.   Enclosure Types: JIC steel.

10.   Enclosure Types: NEMA 4X.

11.   Enclosure Types: MMU.

12.   Communications: Pulse output.

13.   Protocols Available: Pulse output.

14.   Current Sensor Output: 0 - 2 volts.

15.   Current Sensors: One piece.

** NOTE TO SPECIFIER ** Delete sensors not required.

a.   Split Core (Amps): 25.

b.   Split Core (Amps): 50.

c.   Split Core (Amps): 100.

d.   Split Core (Amps): 200.

e.   Split Core (Amps): 400.

f.   Split Core (Amps): 800.

g.   Split Core (Amps): 1600.

h.   Split Core (Amps): 3200.

i.   Solid Core (Amps): 100.

j.   Solid Core (Amps): 200.

16.   Data Recorder: N/A.

17.   External Inputs: N/A.

18.   Pulse Outputs: 1.

19.   Modem: N/A.

20.   Display: 2-line LCD display.

21.   On-Board Setup: N/A.

22.   Phase Loss Alarm (N.O. Contact): N/A.

23.   Power Quality Measurement: N/A.

24.   Peak Demand Measurement: N/A.

25.   Circuit Single Phase, 2-Wire: Yes.

26.   Circuit Single Phase, 3-Wire: Yes.

27.   Circuit 3-Phase, 3-Wire (Delta): N/A.

28.   Circuit 3-Phase, 4-Wire (Wye): N/A.

29.   CE Approval: N/A.

** NOTE TO SPECIFIER ** Delete article if not required.

1.11   THREE PHASE METERS

A.   Basis of Design: Class 2000 Three-Phase E-Mon Submeter by Honeywell. Provides kW and kWh data for three-phase power, revenue-grade accuracy, California CTEP approved for use with solid-core current sensors (200 Amp). Listed by the California Energy Commission, and self-power supply maintains reading in the event of power failure.

1.   Standards Compliance: UL and cUL Listed and ANSI C12.20.

** NOTE TO SPECIFIER ** Delete voltages not required

2.   Voltage (L-N/L-L): 120/208 - 240.

3.   Voltage (L-N/L-L): 277/480.

4.   Voltage (L-N/L-L): 347/600.

** NOTE TO SPECIFIER ** Delete currents not required.

5.   Current (Amps): 100.

6.   Current (Amps): 200.

7.   Current (Amps): 400.

8.   Current (Amps): 800.

9.   Current (Amps): 1600.

10.   Current (Amps): 3200.

** NOTE TO SPECIFIER ** Delete enclosure types not required.

11.   Enclosure Types: JIC Steel.

12.   Enclosure Types: NEMA 4X.

13.   Enclosure Types: MMU.

14.   Communications: Pulse Output.

15.   Protocol: Pulse Output.

16.   Current Sensor Output: 0 - 2 volts.

17.   Current Sensors: One-piece.

** NOTE TO SPECIFIER ** Delete sensors not required.

a.   Split Core (Amps): 100.

b.   Split Core (Amps): 200.

c.   Split Core (Amps): 400.

d.   Split Core (Amps): 800.

e.   Split Core (Amps): 1600.

f.   Split Core (Amps): 3200.

g.   Solid Core (Amps): 100.

h.   Solid Core (Amps): 200.

18.   Data Recorder: N/A.

19.   External Inputs: N/A.

20.   Pulse Outputs: 1.

21.   Modem: N/A.

22.   Display: 2-Line LCD Display.

23.   On-Board Setup: Date and Time for Demand option.

24.   Phase Loss Alarm (N.O. Contact): N/A.

25.   Power Quality Measurement: N/A.

26.   Peak Demand Measurement: Optional.

27.   Circuit Single Phase, 2-wire. N/A.

28.   Circuit Single Phase, 3-wire. N/A.

29.   Circuit 3-Phase, 3-wire (delta).

30.   Circuit 3-Phase, 4-wire (wye).

31.   CE Approval: N/A.

** NOTE TO SPECIFIER ** For energy, power quality, and building automation system (BAS) integration. Delete article if not required.

1.12   SMART SUBMETERS

** NOTE TO SPECIFIER ** Delete paragraphs not required.

A.   Basis of Design: Class 3200 Smart E-Mon Submeter by Honeywell. Provides kW and kWh data for three-phase power, revenue-grade accuracy, and self-power supply maintains reading in the event of power failure. Available in a Multiple Meter Unit (MMU) version.

1.   Standards Compliance: UL and cUL Listed and ANSI C12.20 compliant.

** NOTE TO SPECIFIER ** Delete voltages not required

2.   Voltage (L-N/L-L): 120/208 - 240.

3.   Voltage (L-N/L-L): 277/480.

4.   Voltage (L-N/L-L): 347/600.

** NOTE TO SPECIFIER ** Delete currents not required.

5.   Current (Amps): 100.

6.   Current (Amps): 200.

7.   Current (Amps): 400.

8.   Current (Amps): 800.

9.   Current (Amps): 1600.

10.   Current (Amps): 3200.

** NOTE TO SPECIFIER ** Delete enclosure types not required.

11.   Enclosure Types: JIC Steel.

12.   Enclosure Types: NEMA 4X.

13.   Enclosure Types: MMU.

14.   Communications: RS-485.

15.   Protocol:

** NOTE TO SPECIFIER ** Delete protocols not required.

a.   EZ-7.

b.   Modbus RTU.

c.   BACnet MS/TP.

16.   Current Sensor Output: 0 - 2 volts.

17.   Current Sensors: One-piece.

** NOTE TO SPECIFIER ** Delete sensors not required.

a.   Split Core (Amps): 100.

b.   Split Core (Amps): 200.

c.   Split Core (Amps): 400.

d.   Split Core (Amps): 800.

e.   Split Core (Amps): 1600.

f.   Split Core (Amps): 3200.

g.   Solid Core (Amps): 100.

h.   Solid Core (Amps): 200.

18.   Data Recorder: Yes.

19.   External Inputs: N/A.

20.   Pulse Outputs: N/A.

21.   Modem: N/A.

22.   Display: 4-Line LCD Display with backlight.

23.   On-Board Setup: Yes.

24.   Phase Loss Alarm (N.O. Contact): N/A.

25.   Power Quality Measurement: N/A.

26.   Peak Demand Measurement: Yes.

27.   Circuit Single Phase, 2-wire: N/A.

28.   Circuit Single Phase, 3-wire: Yes with option SP.

29.   Circuit 3-Phase, 3-wire (delta): Yes.

30.   Circuit 3-Phase, 4-wire (wye): Yes.

31.   CE Approval: Yes.

B.   Basis of Design: Class 3400 Smart E-Mon Submeter by Honeywell. Provides kW and kWh data for three-phase power, revenue-grade accuracy, and self-power supply maintains reading in the event of power failure. Built-in functions for load control and two pulse output (kWh & kVARh). Records and stores kWh and kVARh data in 15-minute intervals up to 72 days. Dual protocol communications. Relay board available.

1.   Standards Compliance: UL and cUL Listed and ANSI C12.20.

** NOTE TO SPECIFIER ** Delete voltages not required

2.   Voltage (L-N/L-L): 120/208 - 240.

3.   Voltage (L-N/L-L): 277/480.

4.   Voltage (L-N/L-L): 347/600.

** NOTE TO SPECIFIER ** Delete currents not required.

5.   Current (Amps): 100.

6.   Current (Amps): 200.

7.   Current (Amps): 400.

8.   Current (Amps): 800.

9.   Current (Amps): 1600.

10.   Current (Amps): 3200.

** NOTE TO SPECIFIER ** Delete enclosure types not required.

11.   Enclosure Types: JIC Steel.

12.   Enclosure Types: NEMA 4X.

13.   Communications: RS-485 and ethernet.

14.   Protocol:

** NOTE TO SPECIFIER ** Delete protocols not required.

a.   EZ-7, EZ-7 Ethernet.

b.   Modbus RTU, EZ-7 Ethernet.

c.   BACnet MS/TP, EZ-7 Ethernet.

d.   EZ-7, Modbus TCP/IP.

e.   EZ-7, BACnet IP.

f.   Modbus RTU, Modbus TCP/IP.

g.   Lon TP/FT-10, EZ-7 Ethernet.

h.   Lon TP/FT-10, Modbus TCP/IP.

15.   Current Sensor Output: 0 - 2 volts.

16.   Current Sensors: One-piece.

** NOTE TO SPECIFIER ** Delete sensors not required.

a.   Split Core (Amps): 100.

b.   Split Core (Amps): 200.

c.   Split Core (Amps): 400.

d.   Split Core (Amps): 800.

e.   Split Core (Amps): 1600.

f.   Split Core (Amps): 3200.

g.   Solid Core (Amps): 100.

h.   Solid Core (Amps): 200.

17.   Data Recorder: Yes.

18.   External Inputs: 2 with option X Expanded Feature Package.

19.   Pulse Outputs: 2.

20.   Modem: Optional.

21.   Display: 4-line LCD display with backlight.

22.   On-Board Setup: Yes.

23.   Phase Loss Alarm (N.O. Contact): Optional.

24.   Power Quality Measurement: N/A.

25.   Peak Demand Measurement: Yes.

26.   Circuit Single Phase, 2-wire: N/A.

27.   Circuit Single Phase, 3-wire: Yes with option SP.

28.   Circuit 3-Phase, 3-wire (delta): Yes.

29.   Circuit 3-Phase, 4-wire (wye): Yes.

30.   CE Approval: N/A.

C.   Basis of Design: Class 5000 Smart E-Mon Submeter by Honeywell. Provides kW and kWh data for three-phase power, revenue-grade accuracy, and self-power supply maintains reading in the event of power failure Dual protocol communications, onboard installation diagnostics and advanced 4-line display.

1.   Standards Compliance: UL and cUL Listed and ANSI C12.20.

** NOTE TO SPECIFIER ** Delete voltages not required

2.   Voltage (L-N/L-L): 120/208 - 240.

3.   Voltage (L-N/L-L): 277/480.

4.   Voltage (L-N/L-L): 347/600.

** NOTE TO SPECIFIER ** Delete currents not required.

5.   Current (Amps): 100.

6.   Current (Amps): 200.

7.   Current (Amps): 400.

8.   Current (Amps): 800.

9.   Current (Amps): 1600.

10.   Current (Amps): 3200.

** NOTE TO SPECIFIER ** Delete enclosure types not required.

11.   Enclosure Types: JIC Steel.

12.   Enclosure Types: NEMA 4X.

13.   Communications: RS-485 and ethernet.

14.   Protocol:

** NOTE TO SPECIFIER ** Delete protocols not required.

a.   EZ-7, EZ-7 Ethernet.

b.   Modbus RTU, EZ-7 Ethernet.

c.   BACnet MS/TP, EZ-7 Ethernet.

d.   EZ-7, Modbus TCP/IP.

e.   EZ-7, BACnet IP.

f.   Modbus RTU, Modbus TCP/IP.

g.   Lon TP/FT-10, EZ-7 Ethernet.

h.   Lon TP/FT-10, Modbus TCP/IP.

15.   Current Sensor Output: 0 - 2 volts.

16.   Current Sensors: One-piece.

** NOTE TO SPECIFIER ** Delete sensors not required.

a.   Split Core (Amps): 100.

b.   Split Core (Amps): 200.

c.   Split Core (Amps): 400.