International Design Studio

K10 Plasterboard dry linings/partitions/ceilings K10

TYPES OFDRY LINING

215 SUSPENDED CEILING SYSTEM – FLAT IMPERFORATE

- Ceiling type: Proprietary MF type double grid.

- Structural performance: The complete suspended ceiling must safely support loads including services fittings.

- Loads:

Wind/ upward pressure: No.

Uniformly distributed loads (kN/m²): To be confirmed by the Contractor.

Additional loads/ pressures: Lighting fittings as Electrical specification.

- Deflection (maximum) of suspension grid between points of support: Span/400 mm. Test: To BS 8290-2, Appendix A.

- Airborne sound insulation performance:

- Contributing to overall sound insulation of floor assembly: Performance for complete assembly As required by Acoustic Consultant’s design and performance requirements at locations described on Acoustic plans and performance in Acoustic specification,

- Other requirements: None.

- Suspension system: Grids, hangers, perimeter channels, fixings, etc. as recommended for the purpose by the board manufacturer.

- Material: Galvanized mild steel sheet to BS EN 10142.

- Coating designation: DX51D+Z275-N-A-C.

- Linings: 1 no. layer 12.5 mm gypsum wallboard as clause 401, substitute gypsum plasterboard (moisture resistant) as clause 403 in wet areas or areas of high humidity

- Insulation: 80 mm glass mineral wool general purpose roll where required for acoustic insulation.

- Access units: As Clauses 433,

- Finishing: Refer to finishes schedule for locations of the following

- Taped seamless finish to entire plasterboard surfaces: As clause 670

- Skim coat plaster finish to entire plasterboard surfaces: As clause 680

- Primer/ sealer: Required only for taped seamless finish – apply 1 full coat of plasterboard primer/ sealer recommended by the plasterboard manufacturer

- Accessories: Beads and stops as clause 692.

- Integrated services fittings: Lights, smoke and heat detectors, sprinkler heads, PA speakers, air grilles, locations as shown on services drawings.

- Other requirements: Shadow gap (15 mm) stop beads to perimeter abutments. Access units to have concealed frames (no stop beads) flush with ceiling

220 SUSPENDED CEILING SYSTEM – PLASTERBOARD PERIMETERS TO METAL PANEL CEILINGS OR ACOUSTIC PERFORATED/SLOTTED PLASTERBOARD CEILINGS; FLAT IMPERFORATE

- Ceiling type: Proprietary MF type double grid.

- Structural performance: The complete suspended ceiling must safely support loads including services fittings.

- Loads:

Wind/ upward pressure: No.

Uniformly distributed loads (kN/m²): To be confirmed by the Contractor.

Additional loads/ pressures: Lighting fittings as Electrical specification.

- Deflection (maximum) of suspension grid between points of support: Span/400 Test: To BS 8290-2, Appendix A.

- Airborne sound insulation performance:

- Contributing to overall sound insulation of floor assembly: Performance for complete assembly As required by Acoustic Consultant’s design and performance requirements at locations described on Acoustic plans and performance in Acoustic specification

- Other requirements: None.

- Suspension system: Grids, hangers, perimeter channels, fixings, etc. as recommended for the purpose by the board manufacturer.

- Material: Galvanized mild steel sheet to BS EN 10142.

- Coating designation: DX51D+Z275-N-A-C.

- Linings: 1 no. layer 12.5 mm gypsum wallboard as clause 401, substitute gypsum plasterboard (moisture resistant) as clause 403 in wet areas or areas of high humidity

- Insulation: 80 mm glass mineral wool general purpose roll where required for acoustic insulation.

- Access units: As Clause 433,

- Finishing: Refer to finishes schedule for locations of the following

- Taped seamless finish to entire plasterboard surfaces: As clause 670

- Skim coat plaster finish to entire plasterboard surfaces: As clause 680

- Primer/ sealer: Required only for taped seamless finish – apply 1 full coat of plasterboard primer/ sealer recommended by the plasterboard manufacturer

- Accessories: Beads and stops as clause 692. Proprietary transition trims between plasterboard perimeter and metal panel ceilings as specified in section K40

- Integrated services fittings: Lights, smoke and heat detectors, sprinkler heads, PA speakers, air grilles, locations as shown on services drawings.

- Other requirements: Shadow gap (15 mm) stop beads to perimeter abutments. Access units to have concealed frames (no stop beads) flush with ceiling

221 SUSPENDED CEILING SYSTEM – FLAT WITH SLOTTED ACOUSTIC PANEL INSERTS

- Ceiling type: Proprietary MF type double grid or equivalent.

- Structural performance: The complete suspended ceiling must safely support loads including services fittings.

- Loads:

Wind/ upward pressure: No.

Uniformly distributed loads (kN/m²): To be confirmed by the Contractor.

Additional loads/ pressures: Lighting fittings as Electrical specification.

-Deflection (maximum) of suspension grid between points of support: Span/400 mm.

-Test: To BS 8290-2, Appendix A.

- - Airborne sound insulation performance:

-- Contributing to overall sound insulation of floor assembly: Performance for complete assembly As required by Acoustic Consultant’s design and performance requirements at locations described on Acoustic plans and performance in Acoustic specification

- Other requirements: None

- Suspension system: Grids, hangers, perimeter channels, fixings, etc. as recommended for the purpose by the board manufacturer.

- Material: Galvanized mild steel sheet to BS EN 10142.

- Coating designation: DX51D+Z275-N-A-C.

- Linings: 1 no. layer 12.5 mm gypsum wallboard as clause 401 for blank areas. Acoustic panel inserts comprising decorative, perforated, high performance gypsum boards with integral sound absorbent tissue lining in black, perforation type and pattern as clause 420

- Insulation: 50 mm glass mineral wool where required for acoustic insulation, clause P10_221.

- Access units: As Clause 433,

- Finishing: Taped seamless finish to entire plasterboard surfaces as clause 670

- Primer/ sealer: Apply 1 full coat of plasterboard primer/ sealer recommended by the plasterboard manufacturer

- Accessories: Beads and stops as clause 692.

- Integrated services fittings: Lights, smoke and heat detectors, sprinkler heads, PA speakers, air grilles, locations as shown on services drawings.

- Other requirements: Shadow gap (15 mm) stop beads to perimeter abutments. Access units to have concealed frames (no stop beads) flush with ceiling

222 SUSPENDED CEILING SYSTEM – FLAT WITH PERFORATIONS OVER TOTAL AREA - ACOUSTIC PANEL

- Ceiling type: Proprietary Knauf acoustic double grid (system D127) or equivalent.

- Structural performance: The complete suspended ceiling must safely support loads including services fittings.

- Loads:

Wind/ upward pressure: No. U

Uniformly distributed loads (kN/m²): To be confirmed by the Contractor.

Additional loads/ pressures: Lighting fittings as Electrical specification.

-Deflection (maximum) of suspension grid between points of support: Span/400 mm.

-Test: To BS 8290-2, Appendix A.

- Airborne sound insulation performance:

- Contributing to overall sound insulation of floor assembly: Performance for complete assembly As required by Acoustic Consultant’s design and performance requirements at locations described on Acoustic plans and performance in Acoustic specification

- Other requirements: None

- Suspension system: Grids, hangers, perimeter channels, fixings, etc. as recommended for the purpose by the board manufacturer.

- Material: Galvanized mild steel sheet to BS EN 10142.

- Coating designation: DX51D+Z275-N-A-C.

- Linings: 1 no. layer 12.5 mm gypsum wallboard as clause 401 to perimeter areas. Acoustic panel inserts comprising decorative, perforated, high performance gypsum boards with integral sound absorbent tissue lining in black, perforation type and pattern as clause 422

- Insulation: 25 mm thick as Knauf system D127 .

- Access units: As Clause 433,

- Finishing: Taped seamless finish to entire plasterboard surfaces as clause 670

- Primer/ sealer: Apply 1 full coat of plasterboard primer/ sealer recommended by the plasterboard manufacturer

- Accessories: Beads and stops as clause 692.

- Integrated services fittings: Lights, smoke and heat detectors, sprinkler heads, PA speakers, air grilles, locations as shown on services drawings.

- Other requirements: Shadow gap (15 mm) stop beads to perimeter abutments.

Access units to have concealed frames (no stop beads) flush with ceiling

- Where lights are positioned in perforated board open cells are to be filled to provide a visual solid base as drawings.

GENERAL/ PREPARATION

305 COMPLIANCE WITH PERFORMANCE REQUIREMENTS:

- Testing/ assessment: Submit UKAS accredited laboratory reports for the following: Fire and acoustics

- Materials, components and details: Use in accordance with the testing/ assessment reports. If discrepancies arise, give notice.

325 PREPARATION OF SOLID BACKGROUNDS TO RECEIVE WALL LININGS

- General: Suitable to receive lining system. Redundant fixtures and services removed. Cutting, chasing and making good completed.

- Holes, gaps, service penetrations, perimeter junctions and around openings: Seal completely.

- Adhesive fixings: Prepare to achieve effective bonding.

- Contaminants: Remove loose material, dirt, grease, oil, paper, etc.

- Absorption: Control by dampening, priming or using bonding agents as necessary.

335 ADDITIONAL SUPPORTS

- Framing: Accurately position and securely fix to fully support:

- Partition heads: Running parallel with, but offset from main structural supports.

- Fixtures, fittings and service outlets: To suit fixings. Mark framing positions clearly and accurately on linings.

- Board edges and lining perimeters: As recommended by board manufacturer to suit type and performance of board.

375 NEW WET LAID BASES

- Dpcs: Install under partitions/ freestanding wall linings, cut to full width of partition/ lining.

390 CERAMIC TILING TO PARTITIONS/WALL LININGS GENERALLY:

- Support centres and fixings: Reduce stud or support centres and provide additional support and fixings in accordance with the drylining system manufacturer’s recommendations.

- Boarding: Type, thickness and number of board layers must be as recommended by the drylining system manufacturer.

- Substitute moisture resistant board for intermittent moisture applications including splashbacks. Where other grades of plasterboard are used in these conditions surfaces and edges of board must be treated as recommended by the drylining system manufacturer

- Surface preparation of boards used for ceramic tiling: As recommended by the drylining system manufacturer

- Other requirements: Maximum weights, thicknesses and tiling heights recommended by the drylining system manufacturer must not be exceeded

COMPONENTS

401 GYPSUM PLASTERBOARD

- Type: To BS 1230-1, type 1.

- Core density (minimum): 650 kg/m³.

- Exposed surface and edge profiles: Suitable to receive specified finish.

402 GYPSUM PLASTERBOARD (VAPOUR CONTROL)

- Type: To BS 1230-1, type 1.

- Core density (minimum): 650 kg/m³.

- Moisture vapour resistance of backing layer (minimum): 60 MNs/g.

- Exposed surface and edge profiles: Suitable to receive specified finish.

403 GYPSUM PLASTERBOARD (MOISTURE RESISTANT)

- Type: To BS 1230-1, type 3 and 4.

- Core density (minimum): 710 kg/m³.

- Core: Moisture resistant.

- Paper facings: Moisture resistant.

- Exposed surface and edge profiles: Suitable to receive specified finish.

404 GYPSUM PLASTERBOARD (IMPROVED FIRE PROTECTION)

- Type: To BS 1230-1, type 5.

- Core density (minimum): 800 kg/m³.

- Core: Including fibres for improved cohesion.

- Exposed surface and edge profiles: Suitable to receive specified finish.

406 GYPSUM PLASTERBOARD (IMPROVED FIRE PROTECTION AND MOISTURE RESISTANT)

- Type: To BS 1230-1, type 3 and 5.

- Core density (minimum): 800 kg/m³.

- Core: Moisture resistant and including fibres for improve cohesion.

- Paper facings: Moisture resistant.

- Exposed surface and edge profiles: Suitable to receive specified finish.

407 GYPSUM PLASTERBOARD (IMPROVED FIRE PROTECTION AND VAPOUR CONTROL)

- Type: To BS 1230-1, type 5.

- Core density (minimum): 800 kg/m³.

- Moisture vapour resistance of backing layer (minimum): 60 MNs/g.

- Exposed surface and edge profiles: Suitable to receive specified finish.

408 GYPSUM PLASTERBOARD (IMPACT RESISTANT)

- Type: To BS 1230-1, type 5.

- Core density (minimum): 900 kg/m³.

- Paper facings: Heavy duty.

- Exposed surface and edge profiles: Suitable to receive specified finish.

409 GYPSUM PLASTERBOARD (IMPROVED SOUND INSULATION)

- Type: To BS 1230-1, type 1.

- Core density (minimum): 820 kg/m³.

- Exposed surface and edge profiles: Suitable to receive specified finish.

410 GYPSUM PLASTERBOARD (IMPROVED SOUND INSULATION AND MOISTURE RESISTANT)

- Type: To BS 1230-1, type 3.

- Core density (minimum): 820 kg/m³.

- Core: Moisture resistant.

- Paper facings: Moisture resistant.

- Exposed surface and edge profiles. Suitable to receive specified finish.

420 GYPSUM PLASTERBOARD (PERFORATED ACOUSTIC BOARD)

- British Gypsum Line 6 or equivalent

- Type: To BS 1230-1, type 1.

- Core density (minimum): 650 kg/m³.

- Exposed surface and edge profiles: Suitable to receive specified finish.

- For areas of flat acoustic board or curved ceilings minimum 3600 mm radius

- Black fleece backed

421 GYPSUM PLASTERBOARD CURVED (PERFORATED ACOUSTIC BOARD)

- British Gypsum Line 7 or equivalent

- Type: To BS 1230-1, type 1.

- Core density (minimum): 650 kg/m³.

- Exposed surface and edge profiles: Suitable to receive specified finish.

- For areas of curved acoustic board minimum 1200 mm radius

- Black fleece backed

422 GYPSUM PLASTERBOARD (PERFORATED ACOUSTIC BOARD)

- Knauf Apertura Perforated Plasterboard Square 12, 25 ( item 00019498)

- Type: To BS 1230-1, type 1.

- Core density (minimum): 650 kg/m³.

- Exposed surface and edge profiles: Suitable to receive specified finish.

- For areas of flat acoustic board or curved ceilings up to 1800 mm radius

- Black fleece backed

430 ACCESS UNITS TO WALLS – NON FIRE RATED

- Type: PalcoRange 2, Ref WP2 A with concealed frame.

- Sizes: 450 X 450 mm & 600 X 600mm.

- Finish: Plasterboard face for decoration.

- Lock: Budget.

431 ACCESS UNITS TO WALLS – 1 HOUR FIRE RATED

- Type: PalcoRange 2, Ref WP2 A/F with concealed frame.

- Sizes: 450 X 450 mm & 600 X 600mm.

- Finish: Plasterboard face for decoration.

- Lock: Budget.

433 CEILING ACCESS UNITS – NON FIRE RATED

- Type: PalcoRange 1, Ref CP1 A with concealed frame.

- Sizes: 300 X 300 mm, 450 X 450 mm & 600 X 600mm.

- Finish: Plasterboard face for decoration.

- Lock: Budget.

INSTALATION

435 DRY LININGS GENERALLY

- General: Use fixing, jointing and finishing materials, components and installation methods recommended by board manufacturer.

- Cutting plasterboards: Neatly and accurately without damaging core or tearing paper facing.

- Cut edges: Minimize and position at internal angles wherever possible. Mask with bound edges of adjacent boards at external corners.

- Fixings plasterboards: Securely and firmly to suitably prepared and accurately levelled backgrounds.

- Finishing: Neatly to give flush, smooth, flat surfaces free from bowing and abrupt changes of level.

445 CEILINGS

- Sequence: Fix boards to ceilings before dry lined walls and partitions.

- Orientation of boards: Fix with bound edges at right angles to supports and with ends staggered in adjacent rows.

- Two layer boarding: Stagger joints between layers.

INSTALLATION

455 METAL FRAMING FOR PARTITIONS/ WALL LININGS

- Setting out: Accurately aligned and plumb.

- Stud positions: Equal centres to suit specified linings, maintaining sequence across openings

. - Additional studs: To support vertical edges of boards.

- Fixing centres at perimeters (maximum): 600 mm.

- Openings: Form accurately, including:

- Doorsets: Sleeved/ boxed metal studs and/ or suitable timber framing to achieve strength grade requirements for framing assembly and adequately support weight of door.

- Services penetrations: Allow for associated fire stopping.

465 STAGGERED STUD PARTITIONS

- Fixing horizontal frame members (noggins, bearers, etc.) and boards: Between alternate studs and not touching adjacent offset studs.

475 METAL FURRINGS FOR WALL LININGS

- Setting out: Accurately aligned and plumb.

- Vertical furring positions: Equal vertical centres to suit specified linings, maintaining sequence across openings. Position adjacent to angles, openings and movement joints, etc.

- Additional vertical furrings: At junctions with partitions.

- Horizontal furring positions: To provide continuous support to edges of boards.

- Adhesive bedding to furrings:

- Dabs (at least 200 mm long): To ends of furrings and thereafter at 450 mm (maximum) centres.

- Junctions with partitions: Continuous bed with no gaps across cavity.

485 SUSPENDED CEILING GRIDS

- Setting out: Accurately aligned and level.

- Grid members and hangers: Centres to suit specified linings and imposed loads.

- Additional grid members: To provide bracing and stiffening as necessary at upstands, partition heads, access hatches, etc.

- Fixing: Securely at perimeters, grid joints, top and bottom hanger fixings.

505 INSTALLING MINERAL WOOL INSULATION

- Fitting: Accurately and firmly with closely butted joints and no gaps.

- Widths: Lay insulation in the widest practical widths to suit grid member spacings.

- Services: Do not cover electrical cables that are not sized accordingly.

- Ceilings: Cut insulation carefully around electrical fittings, etc. Do not lay over luminaires.

- Fixing:

- Partitions/ wall linings: Fasten insulation at head of frame to prevent displacement, unless insulation is self supporting and friction fitted between studs.

- Ceilings (vertical/ sloping areas): Fasten insulation to prevent displacement.

510 SEALING GAPS AND AIR PATHS

- Application of sealant to dry lining systems: Continuous beads leaving no gaps or air paths.

- Acoustic sealant: Apply to perimeter abutments with walls, floors, ceilings and around openings. - Gaps greater than 6 mm wide: After application of sealant, complete sealing with jointing compound.

- Air pressure sealant: Apply to board to board and board to metal frame junctions in pressurised shafts, ducts, etc.

530 CAVITY FIRE BARRIERS WITHIN PARTITIONS/ WALL LININGS

- Metal framed systems:

- Material: to contractor’s specification to achieve fire divisions as required by the fire consultants’ requirements..

- Installation: Form accurately and fix securely with no gaps to provide a complete barrier to smoke and flame.

- Adhesive fixed wall lining systems:

- Material: Adhesive compound.

- Installation: Form in a continuous line with no gaps to provide a complete barrier to smoke and flame.

545 CAVITY FIRE BARRIERS WITHIN SUSPENDED CEILINGS

- Comply with the NFPA standard referred to in the Fire Strategy

- Ceiling void subdivision areas (maximum): As above.

- Material: Incombustible to Contractor’s specification

- Fixing:

- Generally: Form accurately and fix securely to channels or angles at abutments with building structure.

- Perimeters and joints: Provide permanent stability and continuity with no gaps. Provide a complete barrier to smoke and flame.

- Service penetrations: Cut and pack to maintain barrier integrity. Sleeve flexible materials. Adequately support services passing through barriers.

- Ceiling systems intended for fire protection: Do not impair fire resisting performance of ceiling system.

555 FIRE STOPPING AT PERIMETERS OF DRY LINING SYSTEMS

- Material: Tightly packed mineral wool or intumescent mastic/ sealant.

- Application: To perimeter abutments to provide a complete barrier to smoke and flame.

560 JOINTS BETWEEN BOARDS

- Tapered edged plasterboards:

- Bound edges: Lightly butted.

- Cut/ unbound edges: 3 mm gap.

- Square edged plasterboards: 3 mm gap.

- Square edged fibre reinforced gypsum boards: 5 mm gap.

565 VERTICAL JOINTS

- Centre joints on studs.

- Partitions: Stagger joints on opposite sides of studs.