SECTION 15540
HIGH INTENSITY INFRARED GAS HEATER
***** Fostoria Industries, Inc. manufacturers two types of gas fired infrared heaters used for comfort heating. The heater covered by this guide specification, is a high intensity gas infrared heater. Multiple units can be used for total areas or single units can be used for spot heating. The other type manufactured by Fostoria Industries, Inc. are low intensity, positive pressure gas infrared tube heating systems consisting of a gas burner which heats a continuous metal tube and a reflector which directs infrared energy onto the floor or other objects.
This guide specification, SECTION 15540 - HIGH INTENSITY INFRARED GAS HEATER, can be used to specify Fostoria FS Series High Intensity Gas Infrared Heaters, an overhead gas-fired heater with cast aluminum burners, ceramic ray-heads, and aluminum reflector.
Infrared radiation is invisible electromagnetic radiation with wavelengths longer than those of visible light. Infrared rays pass through the air and do not create heat until they strike an opaque object. Infrared heaters direct energy onto people and objects. Re-radiation from floors and other objects in turn heats the surrounding air. Infrared energy travels at the speed of light in straight lines from the heat source. This energy diffuses as a function of the square of the distance it travels from the heat source. Intensity, therefore decreases in a proportional manner. For example, at 20 feet from the heat source energy intensity is 1/4 the intensity developed at 10 feet.
Heating levels will be determined by mounting height, spacing, reflector beam pattern, and gas input. For each Fostoria heater there are options for gas input, sizes, reflectors, controls, and method of installation. Refer to Fostoria product literature for availability of options, standard sizes, and guidelines for selection of heater model. Various options are listed in this specification section, but not all options apply to all heaters. The specifier will need to select the appropriate options, verify their availability, and delete non-applicable models and options. *****
PART 1 - GENERAL1.1 / SUMMARY
A. / Section includes: Overhead mounted, gas-fired, high intensity, infrared heaters including controls and mounting hardware.
***** List other specification sections dealing with work directly related to this section such as the following. *****
B. / Related sections:
***** Suspension rods, bracing, and other support components for mounting heaters may need to be designed for specific applications, detailed on Drawings, and specified in other sections. *****
1. / Section 05500 - Metal Fabrications: Metal [channels] [angles] [rods] [bracing] [fasteners] and other components for supporting heaters.
2. / Section 15190 - Fuel Piping: [Natural] [Liquid petroleum] gas piping and specialties for servicing infrared heaters.
3. / Section 16100 - Wiring Methods: Electrical supply, conduit, wiring, boxes, and wiring devices for infrared heater controls.
1.2 / SUBMITTALS
A. / Submit in accordance with Section 01330 - Submittal Procedures:
1. / List of proposed products and product data.
2. / Shop drawings showing heating fixture layout, spacing, dimensions, method of attachment, structural support, and gas connections.
3. / Electrical wiring diagrams for connection of heater controls.
4. / Manufacturer's safety, installation, and maintenance instructions.
1.3 / QUALITY ASSURANCE
A. / Source limitation: Obtain infrared heating system from single manufacturer as a complete unit including heaters, controls, mounting hardware, and other accessories.
B. / Infrared heating fixtures shall be certified for use in the United States and Canada as an unvented, gas fired, infrared heater by Canadian Standards Association (CSA) shall bear CSA label.
PART 2 - PRODUCTS
2.1 / ACCEPTABLE MANUFACTURERS
A. / Fostoria Industries, Inc., P.O. Box 986, Fostoria, Ohio 44830; 800-495-4525;
B. / Manufacturers of equivalent products submitted and approved in accordance with Section 01630 - Product Substitution Procedures.
2.2 / INFRARED GAS HEATERS
**** Fostoria-FS Series High Intensity Gas Infrared Heater generates high intensity heat of approximately 1,850° F at burner surface which is essential for infrared heating. Twenty-four different models of the High Intensity Gas Infrared Heater are provided by Fostoria Industries, Inc. The specifier will need to select the model numbers and associated attributes from Fostoria product literature. Model numbers are in the format [XXX]-[GI]-[GCP] where:
XXX is the Series designation: FS or FSM (Marquee)
GI is Gas Input in BTU/Hr multiplied by 1000: (20-40-60-80-100-120)
GCP is type of Gas and Control Package: (NED, PED, NSG, PSG)
A. / Type: Overhead mounted, gas-fired, high intensity, infrared, pre-wired, pre-piped heaters including controls; Fostoria High Intensity Gas Infrared Heater:
B. / B. Series Designation: [_____]
***** Depending of heater model and type of fuel, BTUH input can vary from 17,500 to 120,000. Select appropriate value from table in Fostoria product literature. *****
C. / BTU per hour input: [_____].
***** Fostoria provides four control packages to control operation of infrared heaters. Refer to Fostoria product literature for available options and applications. For selected control package, include appropriate paragraph from the following and delete others. *****
D. / CONTROL PACKAGE [_____].
***** Include the following paragraph for control package NED. *****
- Type NED: Control package for Natural Gas fired heater with Direct Spark Ignition, 24 volt supply, 24 volt gas valve with 120V / 24V transformer included; Model NED as manufactured by Fostoria Industries, Inc.
***** Include the following paragraph for control package PED *****
- Type PED: Control package for Liquid Petroleum Gas fired heater with Direct Spark Ignition, 24 volt supply, 24 volt gas valve with 120V / 24V transformer included; Model PED as manufactured by Fostoria Industries, Inc.
***** Include the following paragraph for control package NSG Millivolt. *****
- Type NSG: Control package for Natural Gas fired heaters with Manual Pilot Ignition, self-generating controls, and wall thermostat; Model NSG Millivolt as manufactured by Fostoria Industries, Inc.
***** Include the following paragraph for control package PSG Millivolt. *****
- Type PSG: Control package for Liquid Petroleum gas fired heaters with Manual Pilot Ignition, self-generating controls, and wall thermostat; Model PSG Millivolt as manufactured by Fostoria Industries, Inc
Select appropriate dimensions for selected model from table in Fostoria product literature.
D. / Nominal dimensions: [_____] [inches] [mm] wide by [_____] [inches] [mm] long by [_____] [inches] [mm] high with [_____] [inches] [mm] high reflector.
E. / Construction:
1. / Cast aluminum burner body with steel venturi tubes.
2. / Ceramic ray-head with 190 orifices per square inch protruding through roughened burner surface.
3. / Bright-one-side (BOS) aluminum reflector.
2.3 / HEATER ACCESSORIES
***** Fostoria High Intensity Gas Infrared Heaters are typically suspended from ceilings with chains. *****
A. / Mounting Chain Kit
B. / 24V Thermostat (NED & PED models)
C. / 120V Thermostat (NED & PED models)
D. / Millivolt Thermostat (PSG & NSG models-included)
E.
F.
G. / Flexible 24” Gas Supply Hose
Gas Ball Valve 1/2 " NPT
Burner Protector Screens
PART 3 - EXECUTION
3.1 / PREPARATION
A. / Coordinate layout and installation of [wall] [ceiling] mounted infrared heating fixtures with [lighting fixtures,] [mechanical equipment,] [air diffusers] [ductwork,] [fire-suppression system,] and other adjacent construction components to ensure there are no conflicts and minimum distances from infrared heating fixtures are maintained.
B. / Coordinate requirements for blocking, structural supports, and bracing to ensure adequate means for support and installation of infrared heating fixtures.
C. / Coordinate requirements for power supply, conduit, disconnect switches, and wiring required for infrared heating fixtures and controls.
3.2 / INSTALLATION
A. / Comply with manufacturer's written safety and installation instructions and shop drawings.
***** Recommended mounting heights above floor surface vary from 10 to 30 feet depending on heater model. Recommendations are listed in Fostoria product literature. Heights may be indicated on drawings or listed in this section. In order to avoid potential conflicts, mounting heights should not be indicated in both drawings and specifications. *****
B. / Install infrared heating fixtures at locations and heights indicated on Drawings. Ensure that the following minimum clearances from combustible surfaces are maintained:
***** Clearances may be reduced for noncombustible surfaces. Consult Fostoria Product literature for variations to the following minimum clearances. *****
1. / Side: [36 inches] [889 mm].
***** Rear clearance to combustible surface is 36 inches (889 mm) for Model FS-20 and is 40 inches (1016 mm) for all other Fostoria High Intensity Gas Infrared Heater models.*****
2. / Rear: [[36] [40] inches] [[889] [1016 mm].
***** Top clearance to combustible surface is 36 inches (889 mm) for Model FS-20, 44 inches (1118 mm) for Model FS-120, and 40 inches (1016 mm) for all other Fostoria High Intensity Gas Infrared Heater models. *****
3. / Rear: [[36] [40] [44] inches] [[889] [1016] [1118] mm].
***** Below clearance to combustible surface is 36 inches (889 mm) for Model FS-20, 40 inches (1016 mm) for Model FS-40, 72 inches (1829 mm) for Model FS-60, and 108 inches (2743 mm) for all other Fostoria High Intensity Gas Infrared Heater models. *****
4. / Below: [[36] [40] [72] [108] inches] [[889] [1016] [1829] [2743] mm].
C. / Install heating fixtures securely to supporting substrate so that fixtures are level and aligned with each other and adjacent building elements. Use type and length of fastener as recommended by manufacturer for type of substrate.
***** Include the following paragraph if heating fixtures are suspended from ceilings with chain or rods. *****
D. / Suspended ceiling installation: Suspend heating fixtures from ceiling with [chains] [rods] [supports] [_____] as detailed on Drawings and specified in Section [05500 - Metal Fabrications] [_____]. Attach suspension members to mounting brackets integral with fixture.
E. / Where gas piping and electrical conduit is exposed, align vertically and horizontally and parallel with lines of building. Coordinate mounting heights and spacing of components so that finished work is neat and orderly and presents an organized appearance.
F. / Connect to control devices in accordance with Section [16100 - Wiring Methods] [_____].
G. / Controls: Install controls [and thermostats] in accordance with manufacturer's wiring diagrams and instructions.
3.3 / TESTING AND DEMONSTRATION
A. / Inspect installation to verify secure and proper mounting. Test heating system to verify operation, control functions, infrared pattern coverage, and that operating components are functional. Correct deficiencies.
B. / Demonstrate operation of heating system to Owner's designated representatives.
3.4 / PROTECTING
A. / Protect infrared heating fixtures after installation from damage caused by construction operations. If damage occurs, remove and replace damaged components as required to provide system in original, undamaged condition.
END OF SECTION