FUNCTIONAL TEST – Vivarium CHW System
University of Michigan Plant Extension
Commissioning and Plan Review Department
Phone (734) 615-7168 Fax (734) 936-3334
This is not a punch list. The engineer of record, not the commissioning team, performs Punch listing.
Project Name: XXX Project Number: XXXX-XX-XXX
Tag No. Model No. Serial No.
Attendees:
1) ______2)______
3) ______4)______
5) ______6)______
7) ______8)______
Is system operating or is this initial start-up? ______
Is the Pre-Start Checklist Complete? ______
Is all piping complete? ______
Pump CHWP-3
Pump mfg. start-up report obtained: ______
Pump data plate legible: ______
Pump rotation verified: ______
Flexible connections not torqued/mis-aligned: ______
Flexible connection restraining bolts not over tighten: ______
Inertia base clears floor and is free to move? ______
Dead head pump, run at full speed, record pressure differential: ______
Pump dead head pressure matches curve dead head?: ______
System at maximum flow, pump at full speed, record motor current:
Motor Amp Draw: L1______L2 ______L3______
Rated Motor Amps: ______each phase
Are the amp reading at each phase similar?______
Are the amp reading at or below the rated motor amps? ______
Unusual vibration? ______
Unusual noise? ______
Pump CHWP-4
Pump mfg. start-up report obtained: ______
Pump data plate legible: ______
Pump rotation verified: ______
Flexible connections not torqued/mis-aligned: ______
Flexible connection restraining bolts not over tighten: ______
Inertia base clears floor and is free to move? ______
Dead head pump, run at full speed, record pressure differential: ______
Pump dead head pressure matches curve dead head?: ______
System at maximum flow, pump at full speed, record motor current:
Motor Amp Draw: L1______L2 ______L3______
Rated Motor Amps: ______each phase
Are the amp reading at each phase similar?______
Are the amp reading at or below the rated motor amps? ______
Unusual vibration? ______
Unusual noise? ______
VSD for CHWP-3
VSD mfg. start-up report obtained ______
VSD H-O-A tested ______
VSD bypass switch test ______
VSD Start-Stop by DDC ______
VSD Status to DDC ______
VSD input signal (AO) test ______
VSD output (AI)______
Early break contacts verified______
No vibration through-out speed range ______
UM plant approves drive installation ______
VSD for CHWP-4
VSD mfg. start-up report obtained ______
VSD H-O-A tested ______
VSD bypass switch test ______
VSD Start-Stop by DDC ______
VSD Status to DDC ______
VSD input signal (AO) test ______
VSD output (AI)______
Early break contacts verified______
No vibration through-out speed range ______
UM plant approves drive installation ______
Flow meters
Pump CHWP-3 flow meter installed in correct flow direction? ______
Pump CHWP-4 flow meter installed in correct flow direction? ______
Correct upstream and downstream straight pipe for pump flow meters? ______
Loop by-pass meter install in correct flow direction? ______
Loop by-pass meter is powered up? ______
Minimum of 10 pipe diameters upstream and downstream of loop flow meter? ______
General
Vents at high points? ______
Drains at low points? ______
Pump vents installed per detail? ______
Gages positioned to be readable______
Gage scale ranges reasonable______
Dirt/grime cleaned up______
Remarks:
Completed by (print): ______Company: ______
Signed: ______Date: ______
Last printed March 24, 2003 1:36 PM Functional Test-CHW Vivarium System.doc