T – 1956 TARGET
trumbull, ct
SUMMARY
The Target Store T-1956 on 120 Hawley Lane in Trumbull, Connecticut, was inspected by Thomas Branham of Elevator Consulting Services, Inc. on April16th, 2011. My QEI number is 1339 and am certified by NAESA. NAESA is the National Association of Elevator Safety Authorities. We have identified corrective items that in our opinion need to be addressed by the Elevator Contractor. They are free to offer an explanation or dispute any individual item within the report but we can offer a code, specification or reasonable reason for each and every negative evaluation. They are evaluated on and for the ASME 17.2 Code for Inspectors Manual and industry standards for acceptable installation and maintenance procedures.
Invoicing Service Company – Schindler
Exit 51 off Merritt Parkway – turn right onto Huntington 108 – turn left onto Hawley Lane – go to top of the hill – store on left.
T-1956 TRUMBALL, CT
PASSENGER ELEVATORS 1 & 2
CORRECTIVE ITEMS
The following minimum items need corrective action taken. Documentation of completion is required. ANLT 1 – 4//22/10 Due
2 – 4/22/10 Due
General
1.Only 4 entries of PM in 2010, none for 2011. Last entry is September 2010 for Elevator 1 and June 2010 for Elevator 2. Improve frequency and performance, per contract.
Completed ______Initialed ______
2.Provide MSDS sheets for the oil and insert into a plastic sheet holder fastened to the controller cover or tank unit per contract.
Completed ______Initialed ______
Elevator 1 – Up Starts10-21-10506,284
4-16-11504,996
3.Perform the annual no load test as required by ASME 17.1. Properly tag and provide a copy of the test for review.
Completed ______Initialed ______
4.Adjust the P side car door upthrusts , too much play on back side of door.
Completed ______Initialed ______
5.Adjust the front (Target level) side car door upthrusts , too much play on slow speed door. Can come off very easily.
Completed ______Initialed ______
6.Lube rails.
Completed ______Initialed ______
7.Lube all door closure devices. Specifically the lower roll pin that is wearing the pivot plate at the bottom of the closure device. Flush with WD-40 first.
Completed ______Initialed ______
8.Lube the door operator chains. Flush out with penetrating oil first, follow up with a higher viscosity oil.
Completed ______Initialed ______
9.Provide the MSDS sheets for the oil and insert into a plastic sheet holder fastened to the controller cover.
Completed ______Initialed ______
10.Still has LOT faults, add oil, monitor quantity of faults.
Completed ______Initialed ______
11.Replace the closure springs or spray with WD-40, severe rust is present.
Completed ______Initialed ______
12.Special precautions and efforts should be performed due to “element” conditions. Increase all rust prevention efforts and roller gibs on the hoistway and car doors to eliminate air pressure issues per Target contract.
Completed ______Initialed ______
13.Clean the pit. Includes seepage from the right side piston pan. Use oil dry or Portland cement to dry the pit floor. Check the pan for where it is leaking and fix it so there is no more leakage. Replace packing as needed.
Completed ______Initialed ______
Elevator Two – Up Starts10-21-10467,199
4-16-11550,298
14.Perform the annual no load test as required by ASME 17.1. Properly tag and provide a copy of the test for review.
Completed ______Initialed ______
15.Elevator went into pit on normal run and levels up. Adjust leveling and stop.
Completed ______Initialed ______
16.Adjust the P side car door upthrusts , too much play on back side of door.
Completed ______Initialed ______
17.Adjust the front side (Target level) car door upthrusts , too much play on slow speed doors.
Completed ______Initialed ______
18.Lube rails.
Completed ______Initialed ______
19.Lube all door closure devices. Specifically the lower roll pin that is wearing the pivot plate at the bottom of the closure device. Spray with WD-40.
Completed ______Initialed ______
20.Clean the pit.
Completed ______Initialed ______
21.Lube the door operator chains. Flush out with penetrating oil first, follow up with a higher viscosity oil.
Completed ______Initialed ______
22.Put covers on the piston pans in the pit.
Completed ______Initialed ______
23.Special precautions and efforts should be performed due to “element” conditions. Increase all rust prevention efforts and roller gibs on the hoistway and car doors to eliminate air pressure issues per Target contract.
Completed ______Initialed ______
T-1956 TRUMBALL, CT
FREIGHT ELEVATORS 3 & 4
CORRECTIVE ITEMS
The following minimum items need corrective action taken. Documentation of completion is required. ANLT 3 – 3/11/10 – Due
4 – 3/11/10 - Due
General
24.Remove the bad door motor, garbage from the machine room.
Completed ______Initialed ______
25.Only 4 entries of maintenance for 2010. 1 for 2011 (callback). Increase frequency and documentation.
Completed ______Initialed ______
Elevator Three – Up Starts10-21-10139,669
4-16-11147,489
26.Perform the annual no load test as required by ASME 17.1. Properly tag and provide a copy of the test for review.
Completed ______Initialed ______
27.Adjust the gate open operation. No slow down in the close, slams hard at 1st floor. SECOND REQUEST
Completed ______Initialed ______
28.Repair, restore the battery rescuvator to proper working order. NP, LGC lights are not on. SECOND REQUEST
Completed ______Initialed ______
29.Replace the hoistway door panel guide shoes at 1st floor.
Completed ______Initialed ______
30.Flush the hoistway door chains with WD-40 to free up links. Wipe off excess.
Completed ______Initialed ______
31.Adjust door lock gap, chains at 1st floor.
Completed ______Initialed ______
32.Clean the door controller.
Completed ______Initialed ______
Elevator Four – Up Starts10-21-1043,851
4-16-1148,992
33.Clean up all standing oil in the pit. Includes saturated absorbent pads. (Should not use Target’s dumpster without permission) Use oil dry, portland cement, other means to dry up the pit floor.
Completed ______Initialed ______
34.Perform the annual no load test as required by ASME 17.1. Properly tag and provide a copy of the test for review.
Completed ______Initialed ______
35.Replace the jack packing.SECOND REQUEST
Completed ______Initialed ______
36.Flush the hoistway door chains with WD-40 to free up links and flush rust. Wipe off excess.
Completed ______Initialed ______
37.Clean the door controller.
Completed ______Initialed ______
APRIL 2011Page 1 of 6T-1956 TRUMBULL,CT