CENTRIA Versapanel® Factory Foamed Metal Roof Panel System
CENTRIA Versapanel Metal Roof Panel System provides an aesthetically pleasing, prefinished steel face, energy efficient, long span, roof panel with double-interlocking side joints, integral vapor seals, snap-on batten cap and concealed structural fastening, is especially well suited for high humidity conditions, design applications for highly insulated structures, and roof structural designs where long spans are required. Versapanel can be attached directly to the roof purlins without the need for a metal deck and provides an attractive exposed roof deck. The factory manufactured double interlocking joint does not require a field applied mechanical seam and can be installed by a single work crew in a single operation accelerating installation. The Versapanel System includes separate options for industrial ventilation (Continuous Clam Shell and Continuous Ridge Ventilators) and rooftop solar-electric collection systems (SolarCrest solar roof panels).
Often recommended for industrial applications, CENTRIA Versapanel Factory Foamed Panel System clearly defined by bold ribs that add an attractive linear definition to large structures is also recommended for low- and mid-rise buildings where style, economy, and good insulation values are important. Shopping centers, schools, and warehouses are common applications for Centria Versapanel roof systems.
The Versapanel Systems are available as an embossed panel with a subtly striated exterior surface. Panels are available in Kynar 500® or Hylar 5000®polyvinylidene fluoride (PVDF) finishes. Highly UV resistant and durable in the face chemical and air borne pollution, salt spray and wind-driven sand, PVDF coatings are the Gold Standard of the architectural exterior industry. CENTRIA Versapanel systems are available in over 60 standard colors, and wide array of custom colors.
Consult your local CENTRIA architectural representative for design assistance. Contact CENTRIA, Pittsburgh, PA, (800)759-7474, Email: , www.centria.com for a list of offices. CENTRIA is a world leader in the manufacture of metal building products and systems for nonresidential walls and roofs. CENTRIA is also a world-class coil coater, coating a wide range of products for customers in numerous industries.
CENTRIA products appear in the following MasterFormat sections:
● Section 07 41 13 – Metal Roof Panels (SRS2, SRS3)
● Section 07 41 16 – Insulated Core Metal Roof Panels (Versapanel)
● Section 07 42 13 – Metal Wall Panels (Concept Series, IW Series, Exposed Fastener Panels)
● Section 07 42 16 – Insulated-Core Metal Wall Panels (Formawall Dimension Series, Formawall
Graphics Series, Versawall, Versapanel)
● Section 07 42 17 – Insulated Composite Backup Panel (MetalWrap)
● Section 07 42 43 – Composite Wall Panels (FormaBond)
Specifier: This document is organized according to CSI MasterFormat™ 2004 and SectionFormat™ 2008. Edit section number and title as appropriate to the Project. Bold items require specifier selection. Convert bold to plain text and delete notes before publishing. This document is compatible with certain MasterSpec® and SpecText® editing tools.
Versapanel® is a registered trademark of CENTRIA.
Kynar 500® is a registered trademark of Arkema, Inc.
Hylar 5000® is a registered trademark of Solvay S.A.
MasterFormat™ and SectionFormat™ are trademarks of the Construction Specifications Institute.
MasterSpec® is a registered trademark of the American Institute of Architects.
SpecText® is a registered trademark of the Construction Sciences Research Foundation.
This document is Copyright© 2009 CENTRIA All rights reserved.
SECTION 07 41 16
INSULATED CORE METAL ROOF PANEL
PART 1 - GENERAL
1.1 SECTION INCLUDES
- Foamed-insulation-core batten seam metal roof panel, with related metal trim and accessories.
1.2 RELATED REQUIREMENTS
Specifier: Edit list below to correspond to Project.
- Division 01 Section "Sustainable Design Requirements" for related LEED general requirements.
- Division07 Section "Metal Wall Panels" for factory-formed metal soffit panels.
- Division 05 Section "Cold-Formed Metal Framing" for cold-formed metal framing supporting metal roof panels.
- Division 07 Section "Sheet Metal Flashing and Trim" for sheet metal copings, flashings, reglets and roof drainage items not specified in this Section.
- Division 07 Section "Manufactured Roof Specialties" for manufactured copings, reglets, and roof drainage items.
- Division 07 Section "Roof Accessories" for roof hatches, smoke vents, equipment curbs, and equipment supports.
- Division 07 Section "Joint Sealants" for field-applied joint sealants.
1.3 REFERENCES
- American Architectural Manufacturer's Association (AAMA):
- AAMA 621 - Voluntary Specifications for High Performance Organic Coatings on Coil Coated Architectural Hot Dipped Galvanized (HDG) & Zinc-Aluminum Coated Steel Substrates.
- American Society of Civil Engineers (ASCE):
- ASCE 7 - Minimum Design Loads for Buildings and Other Structures.
- ASTM International (ASTM):
- ASTMA653 - Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
- ASTMA755 - Specification for Steel Sheet, Metallic Coated by the Hot-Dip Process and Prepainted by the Coil-Coating Process for Exterior Exposed Building Products.
- ASTMC645 - Specification for Nonstructural Steel Framing Members.
- ASTMC920 - Specification for Elastomeric Joint Sealants.
- ASTM C 1363 - Standard Test Method for Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus.
- ASTM D 1929 - Standard Test Method for Determining Ignition Temperature of Plastics.
- ASTM D 2244 - Test Method for Calculation of Color Differences from Instrumentally Measured Color Coordinates.
- ASTM D 4214 - Test Methods for Evaluating Degree of Chalking of Exterior Paint Films.
- ASTM E 72 - Standard Test Methods of Conducting Strength Tests of Panels for Building Construction.
- ASTM E 84 - Test Methods for Surface Burning Characteristics of Building Materials.
- ASTME119 - Test Methods for Fire Tests of Building Construction and Materials.
- ASTME1646 - Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference.
- ASTME1680 - Standard Test Method for Rate of Air Leakage Through Exterior Metal Roof Panel Systems.
- ASTM E 1980 - Practice for Calculating Solar Reflectance Index of Horizontal and Low-Sloped Opaque Surfaces.
- Factory Mutual Global (FMG):
- ANSI/FMG 4471 Class 1 Panel Roofs.
- ANSI/FMG4880 Standard for Evaluating Insulated Wall and Roof/Ceiling Assemblies.
- Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA):
- Architectural Sheet Metal Manual.
- Underwriters Laboratories, Inc. (UL):
- UL263 - Fire Tests of Building Construction and Materials.
- UL1256 - Fire Test of Roof Deck Constructions.
- US Environmental Protection Agency:
- Energy Star Reflective Roof Products.
- US Green Building Council (USGBC):
- Leadership in Energy and Environmental Design (LEED) Green Building Rating System.
1.4 PERFORMANCE REQUIREMENTS
- General: Provide metal roof panel system meeting performance requirements as determined by application of specified tests by a qualified testing agency on manufacturer's standard assemblies.
- Air Infiltration: Maximum 0.03cfm/sq.ft. (0.3L/spersq.m) per ASTME1680 at a static-air-pressure difference of 1.56lbf/sq.ft. (100Pa).
- Water Penetration Static Pressure: No uncontrolled water penetration at a static pressure of 6.24lbf/sq.ft(299 Pa) when tested per ASTM E 1646.
- Ignition Temperature: Provide values for foam plastic insulation that have been established in accordance with ASTM D 1929.
- Structural Performance: Provide metal wall panel assemblies capable of withstanding the effects of indicated loads and stresses within limits and under conditions indicated, per ASTME72:
Specifier: Consult structural engineer and edit below as required by local codes. Insert structural data below if not indicated on drawings.
- Wind Loads: Determine loads based on uniform pressure, importance factor, exposure category, and basic wind speed indicated on drawings.
- Deflection Limits: Withstand test pressures of 150 percent of inward and outward wind-load design pressures with maximum deflection of 1/180 of the span with no evidence of failure.
Specifier: Verify seismic performance requirements of authorities having jurisdiction.
- Seismic Performance: Comply with ASCE 7 Sections 9, "Earthquake Loads."
- Wind Uplift Resistance: Comply with UL 580 for wind-uplift class UL-90.
Specifier: Retain FMG listing requirement for FMG-insured projects and where FMG requirements are used as minimum design standard. Select required windstorm classification based upon calculation method in FMG Loss Prevention Sheet 1-28; note that FMG windstorm classification does not correlate directly to design wind speed nor design wind uplift pressure.
- FMG Listing: Comply with FMG 4471. Provide metal roof panel assembly listed in FMG’s "Approval Guide."
- Fire and Windstorm Classification: Class 1A-[90] [120].
- Hail Resistance: SH.
- Thermal Movements: Allow for thermal movements from variations in both ambient and internal temperatures. Accommodate movement of support structure caused by thermal expansion and contraction.
- Thermal Performance: Thermal-resistance (R) value indicated, per ASTMC 1363, corrected to 15 mph (6.7 m/s) wind outside and still air inside.
Specifier: Retain one or more energy performance subparagraphs below based on project requirements. Retain Solar Reflectance Index for LEED projects. Retain Energy Star reference for projects seeking Energy Star rating; products must be listed on EPA Energy Star website. Retain CEC compliance for projects required to comply with CEC requirements. Verify values with manufacturer for selected panel finishes.
- Energy Performance:
- Solar Reflectance Index: Minimum 78 for roof slopes of 2:12 or less and 29 for roof slopes greater than 2:12 per ASTM E 1980.
- Energy Star Qualified: Listed on USDoE ENERGY STAR Roof Products Qualified Product List www.energystar.com.
- California Energy Commission Compliance: Minimum initial solar reflectance of [0.70] and emissivity of [0.75] per CRRC-1, www.coolroofs.org.
1.5 QUALITY ASSURANCE
- Manufacturer/Source: Provide metal roof panel assembly and accessories from a single manufacturer.
Specifier: Retain paragraph below if Owner allows substitutions but requires strict control over qualifying of substitutions.
- Manufacturer Qualifications: Approved manufacturer listed in this Section with minimum 5 years experience in manufacture of similar products in successful use in similar applications.
- Approval of Comparable Products: Submit the following in accordance with project substitution requirements, within time allowed for substitution review:
- Product data, including certified independent test data indicating compliance with requirements.
- Samples of each component.
- Sample submittal from similar project.
- Project references: Minimum of 5 installations not less than 5 years old, with Owner and Architect contact information.
- Sample warranty.
- Substitutions following award of contract are not allowed except as stipulated in Division 01 General Requirements.
- Approved manufacturers must meet separate requirements of Submittals Article.
- Installer Qualifications: Experienced Installer with minimum of 5 years experience with successfully completed projects of a similar nature and scope.
- Preconstruction Field-Adhesion Testing: Before installing sealants, field test their adhesion to Project joint substrates as specified in Division 07 Section "Joint Sealants."
- Fire Performance Characteristics: Provide metal wall or roof systems with the following fire-test characteristics determined by indicated test standard as applied by UL or other testing and inspection agency acceptable to authorities having jurisdiction.
- Surface-Burning Characteristics: Provide metal wall or roof system panels with the following characteristics when tested per ASTM E 84.
- Flame spread index: 25 or less.
- Smoke developed index: 450 or less.
- Fire Performance of Insulated Roof: Class 1 roof panel per ANSI/FM 4880.
Specifier: Retain below when metal roof panels are part of a fire-resistance-rated wall assembly.
- Fire Resistance Ratings: Provide metal roof panels tested per ASTM E 119 or UL Standard 263.
1.6 ADMINISTRATIVE REQUIREMENTS
- Preinstallation Meeting: Prior to erection of wall or roof framing, conduct preinstallation meeting at site attended by Owner, Architect, manufacturer's technical representative, inspection agency and related trade contractors.
- Coordinate building framing in relation to Metal Roof Panel system.
- Coordinate openings and penetrations of metal roof panel system.
- Coordinate work of Division 07 Sections "Roof Specialties" and "Roof Accessories" and roof openings and penetrations and manufacturer's accessories with installation of metal roof panels.
1.7 ACTION SUBMITTALS
- Product Data: Manufacturer’s data sheets for specified products.
Specifier: Retain and edit below to comply with Project requirements for LEED or other sustainable design requirements.
- LEED Submittals:
- Credit SS 7.2: Product data indicating compliance with solar reflectance index requirement.
- Credit MR 4: Product data indicating the following:
- Percentages by weight of post-consumer and pre-consumer recycled content.
- Total weight of products provided.
- Include statement indicating costs for each product having recycled content.
- Shop Drawings: Show layouts of metal roof panels. Include details of each condition of installation, panel profiles, and attachment to building. Provide details at a minimum scale 1-1/2-inch per foot of edge conditions, joints, fastener and sealant placement, flashings, penetrations, and special details. Make distinctions between factory and field assembled work.
- Include data indicating compliance with performance requirements.
- Indicate points of supporting structure that must coordinate with standing seam metal roof system installation.
- Include structural data indicating compliance with performance requirements and requirements of local authorities having jurisdiction.
- Samples for Initial Selection: For each product specified including sealants and gaskets. Provide representative color charts of manufacturer's full range of colors.
- Samples for Verification: Provide 12-inch- (305 mm-) long section of metal wall or roof panel showing finishes, vertical joint return, injected core material, and anchoring details. Provide 12-inch- (305-mm-) long pieces of each extruded aluminum trim.
1.8 INFORMATIONAL SUBMITTALS
- Product Test Reports: Indicating compliance of products with requirements, from a qualified independent testing agency.
Specifier: Include requirement for coordination drawings for complex installations or installations involving an unusual amount of coordination between separate installers.
- Coordination Drawings: Layout drawings and detail drawings coordinating the installation of [wall and] roof panels with purlins, rafters, and other secondary framing. Coordinate penetrations, openings, and mechanical attachments.
Specifier: Retain paragraphs below when Project requirements include compliance with Federal Buy American provisions. CENTRIA Versapanel complies with requirement.
- Buy American Act Certification: Submit documentation certifying that products comply with provisions of the Buy American Act 41 U.S.C 10a – 10d.
- Qualification Information: For Installer firm, Installer’s field supervisor.
- Manufacturer's warranty: Submit sample warranty.
1.9 CLOSEOUT SUBMITTALS
- Maintenance data.
1.10 DELIVERY, STORAGE, AND HANDLING
- Protect products of metal roof panel system during shipping, handling, and storage to prevent staining, denting, deterioration of components or other damage. Protect panels and trim bundles during shipping with water resistant paper. Protect painted surfaces with a strippable protective covering before shipping.
- Deliver, unload, store, and erect metal roof panel system and accessory items without misshaping panels or exposing panels to surface damage from weather or construction operations.
- Store in accordance with Manufacturer's written instruction. Provide wood collars for stacking and handling in the field.
- Shield foam insulated metal roof panels from direct sunlight until installation.
1.11 WARRANTY