Noteaboutthisspecification:
GUIDESPECIFICATIONS–50LC**14-26
Thesespecifications arewrittenin“Masterformat”aspublishedbytheConstructionSpecificationInstitute.Pleasefeelfree tocopythisspecificationdirectlyintoyourbuildingspec.
WeatherExpert®UltraHigh-EfficiencyCoolingOnly/ElectricHeatPackagedRooftop
HVACGuideSpecifications:
SizeRange:12.5to23NominalTons SectionDescription
230680SchedulesforDecentralized HVACEquipment
230680.13DecentralizedUnitaryHVACEquipmentSchedule
230680.13.A.Rooftopunitschedule
1.Scheduleispertheprojectspecificationrequirements.
230716HVACEquipmentInsulation
230716.13Decentralized,RooftopUnits:
230716.13.A.Evaporatorfancompartment:
1.Interiorcabinetsurfacesshallbeinsulatedwithaminimum1/2-in.thick,minimum11/2lbdensityaluminum foil-facedinsulationontheairside.
2.InsulationandadhesiveshallmeetNFPA90Arequirementsforflamespreadandsmokegeneration.
3.Unitinternalinsulationliningsshallberesistanttomoldgrowthinaccordancewith“moldgrowthandhumidity” testinASTMC1338,G21,andUL181orcomparabletestmethod.Airstreamsurfacesshallbeevaluatedin accordancewiththe“ErosionTest”inUL181,aspartofASTMC1071.
230716.13.B.Electricheatcompartment:
1.Aluminumfoil-facedfiberglassinsulationshallbeused.
2.InsulationandadhesiveshallmeetNFPA90Arequirementsforflamespreadandsmokegeneration.
230913InstrumentationandControlDevicesforHVAC
230913.23SensorsandTransmitters
230913.23.A.Thermostats
1.Thermostatmust
a.energizeboth“W”and“G”whencallingforheat.
b.havecapabilitytoenergize3differentstagesofcooling,and2differentstagesofheating.
c.includecapabilityforoccupancyscheduling.
230923DirectDigitalControl(DDC)SystemforHVAC
230923.13Decentralized,RooftopUnits:
230923.13.A.SystemVu™ intelligentintegratedDirectDigitalControl(DDC)shallprovide:
1.Integratedunitoperation for comfortcooling,heating ventilation aswellasallmonitoring,recordingand reportingcapabilities.Controllershallalsoprovidediagnosticsandalarmsofabnormalunitoperationthrough thecontroller.Controllershallhaveanintuitiveuserdisplayandbeabletobeusedinastandaloneoperationor viabuildingautomationsystem(BAS).
2.QuickUnitStatusLED’sof:Run–meaningallsystemsarego,ALERT–thatindicatesthereiscurrentlya non-criticalissuewiththeunit,likefiltersneedtobereplacedandFAULT–thatindicatestheunithasacritical issueandwillpossiblyshutdown.
3.Sixlargenavigationkeysforeasyaccess.Navigationkeysshallconsistof:TEST,BACK,ENTER,andMENU alongwithUPandDOWNarrows.
4.Fullbacklituserdisplaywith4lineby30charactertextcapabilities.Displaymenushallbedesignedtoprovide guidedmajormenusandsubmenusmainmenusprovidedbelow:
—ShutdownUnit
—RunStatus
—Settings
—Alerts/Faults
—Service
—Inputs
—Outputs
—USB
5.Thecapabilityforstandaloneoperationwithconventionalthermostat/sensororusewithbuildingautomation systems(BAS)ofCarrieri-Vu®,BACnet*andCarrierComfortNetwork®(CCN)systems.Nospecialmodules orboardsarerequiredforthesecapabilities.
6.TheabilitytoreadrefrigerantpressuresatdisplayorviaBASnetworkof;DischargePressure,SuctionPressure andLiquidLinePressure.Theneedfortraditionalrefrigerantgaugesisnotrequired.
7.USBDataPortforflashdriveexchange.Thiswillallowthetransferofdataforuploads,downloads,performsoftware upgrades,back-upandrestoredataandfiletransferdatasuchascomponentnumberofstartsandrunhours.
8.ReverseRotationProtectionofcompressorsiffieldthreephasewiringismisapplied.
9.ProvideServiceCapabilitiesof:
—Autoruntest
—Manualruntest
—Componentrunhoursandstarts
—Commissioningreports
—Datalogging
—Alarmhistory
10.Economizercontrolanddiagnostics.Setupeconomizeroperation,receivefeedbackfromactuator.Alsomeets themostrecentCaliforniaTitle24FaultDetectionandDiagnostic(FDD)requirements.
11.Unitcoolingoperationdownto0°F(-18°C)
12.ControllershallhaveeasyaccessconnectionsaroundthecontrollerperimeterareaandconsistofMate-N-Lok, terminalblockandRJstylemodularjackconnections.
13.365dayrealtimeclock,20holidayschedulesalongwithoccupiedandunoccupiedscheduling.
14.Auto-Recognitionforeasyinstallationandcommissioningofdeviceslikeeconomizers,spacesensorsetc.
15.A5°FtemperaturedifferencebetweencoolingandheatingsetpointstomeetthelatestASHRAE90.1-2013 EnergyStandard.
16.Containreturnairsensor,supplyairsensorandoutdoorairsensortohelpmonitorandprovidedatafortheunit comfortoperation,diagnosticandalarms.
17.UseofCarrier’sfieldaccessoryhand-heldNavigator™ display.
18.ControloftheoperationofunitVFD(VariableFrequencyDrive)toworkinconjunctionwiththecooling,heatingand ventilationmodes.
19.3-yearlimitedpartwarranty
230923.13.B.RTUOpen-multi-protocol,directdigitalcontroller:
1.ShallbeASHRAE62compliant.
2.Shallaccept18-30VAC,50-60Hz,andconsume15VAorlesspower.
3.Shallhaveanoperatingtemperaturerangefrom-40°F(-40°C)to130°F(54°C),10%-90%RH(non-condensing).
4.Shallincludebuilt-inprotocolforBACnet(MS/TPandPTPmodes),Modbus†(RTUandASCII),JohnsonN2 andLonWorks**.LonWorksEchelonprocessorrequiredforallLonapplicationsshallbecontainedinseparate communicationboard.
5.Shallallowaccessofupto62networkvariables(SNVT).Shallbecompatiblewithallopencontrollers
6.BaudrateControllershallbeselectableusingadipswitch.
7.ShallhaveanLEDdisplayindependentlyshowingthestatusofserialcommunication,running,errors,power,all digitaloutputs,andallanaloginputs.
8.Shallacceptthefollowinginputs:spacetemperature,setpointadjustment,outdoorairtemperature,indoorair quality,outdoorairquality,compressorlock-out,fireshutdown,enthalpyswitch,andfanstatus/filterstatus/ humidity/remoteoccupancy.
9.Shallprovidethefollowingoutputs:economizer,fan,coolingstage1,coolingstage2,heatstage1,heatstage2, heatstage3/exhaust/reversingvalve.
* BACnet is a registered trademark of ASHRAE (American Society ofHeating, Refrigerating and Air- Conditioning Engineers).
†Modbus is a registered trademark of Schneider Electric.
** LonWorks is a registered trademark of Echelon Corporation.
10.Shallhavebuilt-insurgeprotectioncircuitrythroughsolidstatepolyswitches.Polyswitchesshallbeusedon incomingpowerandnetworkconnections.Polyswitcheswillreturntonormalwhenthe“trip”conditionclears.
11.Shallhaveabatteryback-upcapableofaminimumof10,000hoursofdataandtimeclockretentionduring poweroutages.
12.Shallhavebuilt-insupportforCarriertechniciantool.
13.ShallincludeanRS-485protocolcommunicationport,anaccessportforconnectionofeitheracomputerora Carriertechniciantool,anEIA-485portfornetworkcommunicationtointelligentspacesensorsanddisplays, andaporttoconnectanoptionalLonWorkscommunicationscard.
14.Softwareupgradeswillbeaccomplishedbyeitherlocalorremotedownload.Nosoftwareupgradesthroughchip replacementsareallowed.
230933IntegratedStagingControl(ISC)SystemforHVAC(Electro-Mechanicalunits)
230933.13Decentralized,RooftopUnits:
230933.13.A.General:
1.Shallbecompletewithself-containedlow-voltagecontrolcircuitprotectedbyaresettablecircuitbreakeronthe 24-vtransformerside.Transformershallhave75VAcapability.
2.Shallutilizecolor-codedwiring.
3.ShallincludeanISCelectro-mechanicalcontrolboard,toconvenientlyandsafelyprovideconnectionpointsforvital controlfunctionssuchas:smokedetectors,phasemonitor,gascontroller,economizer,thermostat,andsafetyswitches. Shallcontrolallthreestagesofcompressorlogic,twoorthreestagesoftheindoorfanmotorlogicaswellasstaging oftheoutdoorfanmotor.ShallalsohaveagreenLEDindicatortoindicateGOoperationaswellasafaultLED indicatorforthermostatmis-wiring,nofanoperationandsafetyswitches.
NOTE:DoesnotapplytounitsequippedwithSystemVu™ controls.
4.Unitshallincludeaminimumofone8-pinscrewterminalconnectionboardforconnectionofcontrolwiring. 230933.13.B. Safeties:
1.Compressorover-temperature,overcurrent.
2.Low-pressureswitch.
a.Low-pressureswitchshallusedifferentcolorwirethanthehigh-pressureswitch.Thepurposeistoassist theinstallerandservicetechniciantocorrectlywireandortroubleshoottherooftopunit.
NOTE:DoesnotapplytounitsequippedwithSystemVucontrols.
3.High-pressureswitch.
a.High-pressureswitchshallusedifferentcolorwirethanthelowpressureswitch.Thepurposeistoassistthe installerandservicetechniciantocorrectlywireandortroubleshoottherooftopunit.
4.Automaticreset,motorthermaloverloadprotector.
230993SequenceofOperationsforHVACControls
230993.13Decentralized,RooftopUnits:
230993.13.A.INSERTSEQUENCEOFOPERATION
234013PanelAirFilters
234013.13Decentralized,RooftopUnits:
234013.13.A.Standardfiltersection
1.Shallconsistoffactory-installed,lowvelocity,throwaway2-in.thickfiberglassfiltersofcommerciallyavailable sizes.
2.Unitshalluseonlyonefiltersize.Multiplesizesarenotacceptable.
3.Filtersshallbeaccessiblethroughadedicated,weathertightpanel.
4.4-infiltercapabilitiesshallbecapablewithpre-engineeredandapprovedCarrierfiltertrackfield-installedaccessory.
Thiskitrequiresfieldfurnishedfilters.
238119Self-ContainedAirConditioners
238119.13Medium-CapacitySelf-ContainedAirConditioners(50LC**14-26)
238119.13.A.General
1.Outdoor,rooftopmounted,ISCelectricallycontrolled,heatingandcoolingunitutilizinghermeticscroll compressorsforcoolingdutyandoptionalelectricheatforheatingduty.
2.Factoryassembled,single-pieceheatingandcoolingrooftopunit.Containedwithintheunitenclosureshallbe allfactorywiring,piping,controls,andspecialfeaturesrequiredpriortofieldstart-up.
3.UnitshallusePuron® (R-410A)refrigerant.
4.Unitshallbeinstalledinaccordancewiththemanufacturer’sinstructions.
5.Unitmustbeselectedandinstalledincompliancewithlocal,state,andfederalcodes. 238119.13.B.QualityAssurance
1.UnitmeetsandexceedsASHRAE90.1-2013minimumefficiencyrequirements.
2.UnitshallberatedinaccordancewithAHRIStandard340/360.
3.UnitshallbedesignedtoconformtoASHRAE15.
4.UnitshallbeETL-testedandcertifiedinaccordancewithANSIZ21.47StandardsandETL-listedandcertified underCanadianstandardsasatotalpackageforsafetyrequirements.
5.InsulationandadhesiveshallmeetNFPA90Arequirementsforflamespreadandsmokegeneration.
6.Unitinternalinsulationliningsshallberesistanttomoldgrowthinaccordancewith“moldgrowthandhumidity” testinASTMC1338,G21,andUL181orcomparabletestmethod.Airstreamsurfacesshallbeevaluatedin accordancewiththe“ErosionTest”inUL181,aspartofASTMC1071.
7.Unitcasingshallbecapableofwithstanding500-hoursaltsprayexposureperASTMB117(scribedspecimen).
8.RoofcurbshallbedesignedtoconformtoNRCAStandards.
9.Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will be stored at the factory, and must be available upon request.
10.UnitshallbedesignedinaccordancewithULStandard1995,includingtestedtowithstandrain.
11.Unitshallbeconstructedtopreventintrusionofsnowandtestedtopreventsnowintrusionintothecontrolbox upto40mph.
12.Unitshaketestedtoassurancelevel1,ASTMD4169toensureshippingreliability.
13.High-EfficiencyMotorslistedshallmeetsection313oftheEnergyIndependenceandSecurityActof2007 (EISA2007)
238119.13.C.Delivery,Storage,andHandling
1.Unitshallbestoredandhandledpermanufacturer’srecommendations.
2.Liftedbycranerequireseithershippingtoppanelorspreaderbars.
3.Unitshallonlybestoredorpositionedintheuprightposition. 238119.13.D.ProjectConditions
1. Asspecifiedinthecontract.
238119.13.E.OperatingCharacteristics
1.Unitshallbecapableofstarting andrunningat125°F(52°C)ambientoutdoortemperature,meetingmaximum
loadcriteriaofAHRIStandard340/360at±10%voltage.
2.Compressorwithstandardcontrolsshallbecapableofoperationfrom40°F(4°C),ambientoutdoortemperatures.For
loweroperationanintegratedeconomizershallbeutilizedtoallowlowertemperaturesandaccommodateindoorair
qualityinitiatives
3.Unitshalldischargesupplyairverticallyorhorizontallyasshownoncontractdrawings.
4.Unitshallbefactoryconfiguredandorderedforverticalsupplyreturnconfigurations.
5.Unit shall be factory furnished for either vertical or horizontal configuration without the use of special conversionkits.Nofieldkitsconversionispossible.
6.Unitshallbecapableofmixedoperation:verticalsupplywithhorizontalreturnorhorizontalsupplywithvertical return.
238119.13.F.ElectricalRequirements
1.Mainpowersupplyvoltage,phase,andfrequencymustmatchthoserequiredbythemanufacturer. 238119.13.G.UnitCabinet
1.Unitcabinetshallbeconstructedofgalvanizedsteel,andshallbebonderizedandcoatedwithapre-painted
bakedenamelfinishonallexternallyexposedsurfaces.
2.Unitcabinet exteriorpaintshallbe:filmthickness,(dry)0.003 inchesminimum,gloss(per ASTMD523,60°F):
60,Hardness:H-2HPencilhardness.
3.EvaporatorfancompartmentinteriorcabinetinsulationshallconformtoAHRIStandards340/360minimumexterior sweatcriteria.Interiorsurfacesshallbeinsulatedwithaminimum1/2-in.thick,1lbdensityaluminumfoil-faced fiberglassinsulation.Aluminumfoil-facedfiberglassinsulationshallalsobeusedintheheatcompartment.
4.Unitinternalinsulationliningsshallberesistanttomoldgrowthinaccordancewith“moldgrowthandhumidity” testinASTMC1338,G21,andUL181orcomparabletestmethod.Airstreamsurfacesshallbeevaluatedin accordancewiththe“ErosionTest”inUL181,aspartofASTMC1071.
5.Baseofunitshallhaveaminimumoffourlocationsforfactorythru-the-baseelectricalconnections.Connections shallbeinternaltothecabinettoprotectfromenvironmentalissues.
6.BaseRail
a.Unitshallhavebaserailsonaminimumof2sides.
b.Holesshallbeprovidedinthebaserailsforriggingshacklestofacilitatemaneuveringandoverheadrigging.
c.Holesshallbeprovidedinthebaserailformovingtherooftopbyforktruck.
d.Baserailshallbeaminimumof16gaugethickness.
7.Condensatepanandconnections:
a.Shallbeaslopedcondensatedrainpanmadeofanon-corrosivematerial.
b.ShallcomplywithASHRAEStandard62.
c.Shallusea3/4-in-14NPTdrainconnectionattheendofthedrainpan.Connectionshallbemadeper manufacturer’srecommendations.
8.Toppanel:
a.Shallbeamulti-piecetoppanellinkedwithwatertightflangesandinterlockingsystems.
9.ElectricalConnections
a.Allunitpowerwiringshallenterunitcabinetatasingle,factory-prepared,knockoutlocation.
b.Thru-the-basecapability
(1.) Thru-the-baseprovisions/connectionsareavailableasstandardwitheveryunit.Whenbottomconnections arerequired,fieldfurnishedcouplingsarerequired.
(2.) Nobasepanpenetration,otherthanthoseauthorizedbythemanufacturer,ispermitted.
10.Componentaccesspanels(standard)
a.Cabinetpanelsshallbeeasilyremovableforservicing.
b.Unitshallhaveonefactory-installed,tool-less,removable,filteraccesspanel.
c.Panelscoveringcontrolboxandfiltersshallhavemoldedcompositehandleswhilethebloweraccessdoor shallhaveanintegratedflangeforeasyremoval.
d.HandlesshallbeUVmodified,composite,permanentlyattached,andrecessedintothepanel.
e.Screwsontheverticalportionofallremovableaccesspanelshallengageintoheatresistant,molded compositecollars.
f.Collarsshallberemovableandeasilyreplaceableusingmanufacturerrecommendedparts. 238119.13.H.Coils
1.StandardAluminumFin/CopperTubeCoils:
a.Standardevaporatorandcondensercoilsshallhavealuminumlancedplatefinsmechanicallybondedto seamlessinternallygrooved5/16”diametercoppertubeswithalljointsbrazed.
b.Evaporatorcoilsshallbeleaktestedto150psig,pressuretestedto450psig,andqualifiedtoUL1995burst testat1775psig.
c.Condensercoilsshallbeleaktestedto150psig,pressuretestedto650psig,andqualifiedtoUL1995burst testat1980psig.
2.OptionalPre-coatedaluminum-fincondensercoils:
a.Shallhaveadurableepoxy-phenoliccoatingtoprovideprotectioninmildlycorrosivecoastalenvironments.
b.Coatingshallbeappliedtothealuminumfinstockpriortothefinstampingprocesstocreateaninertbarrier betweenthealuminumfinandcoppertube.
c.Epoxy-phenolicbarriershallminimizegalvanicactionbetweendissimilarmetals.
d.Corrosiondurabilityoffinstockshallbeconfirmedthroughtestingtobenolessthan1000hourssaltspray perASTMB117-90.
e.Corrosiondurabilityoffinstockshallbeconfirmedthroughtestingtohavenovisiblecorrosionafter48 hourimmersioninaroomtemperaturesolutionof5%salt,1%aceticacid.
f.Finstockcoatingshallpass2000hoursofthefollowing:oneweekexposureintheprohesionchamber followedbyoneweekofacceleratedultravioletlighttesting.Prohesionchamber:thesolutionshallcontain 3.5%sodiumchlorideand0.35%ammoniumsulfate.Theexposurecycleisonehourofsaltfogapplication
atambientfollowedbyonehourdryingat95°F(35°C).
3.OptionalCopper-finevaporatorandcondensercoils:
a.Shallbeconstructedofcopperfinsmechanicallybondedtocoppertubesandcoppertubesheets.
b.Galvanizedsteeltubesheetsshallnotbeacceptable.
c.Apolymerstripshallpreventcoilassemblyfromcontactingthesheetmetalcoilpantominimizepotential forgalvaniccorrosionbetweencoilandpan.
4.OptionalE-coatedaluminum-finevaporatorandcondensercoils:
a.Shallhaveaflexibleepoxypolymercoatinguniformlyappliedtoallcoilsurfaceareaswithoutmaterial bridgingbetweenfins.
b.Coatingprocessshallensurecompletecoilencapsulationoftubes,finsandheaders.
c.ColorshallbehighglossblackwithglossperASTMD523-89.
d.Uniformdryfilmthicknessfrom0.8to1.2milonallsurfaceareasincludingfinedges.
e.Superiorhardnesscharacteristicsof2HperASTMD3363-92Aandcross-hatchadhesionof4B-5Bper ASTMD3359-93.
f.Impactresistanceshallbeupto160in. -lb(ASTMD2794-93).
g.Humidityandwaterimmersionresistanceshallbeuptominimum1000and250hoursrespectively(ASTM D2247-92andASTMD870-92).
h.Corrosiondurabilityshallbeconfirmedthroughtestingtobenolessthan6000hourssaltsprayperASTM B117-90.
238119.13.I.RefrigerantComponents
1.Refrigerantcircuitshallincludethefollowingcontrol,safety,andmaintenancefeatures:
a.ThermostaticExpansionValve(TXV)shallhelpprovideoptimumperformanceacrosstheentireoperating range.Shallcontainremovablepowerelementtoallowchangeoutofpowerelementandbulbwithout removingthevalvebody.
b.Refrigerantfilterdrier.
c.Servicegaugeconnectionsonsuctionanddischargelines.
d.Pressuregaugeaccessthroughaspeciallydesignedscreenonthesideoftheunit.
e.Singlecircuitdesignwithtandemcompressorandfullyactivatedevaporatorcoil
2.Compressors
a.ModelsshalluseonefullyhermetictandemscrollcompressorsoptimizedforcomfortstagingandIEER energysavings.
b.Modelsshallbeavailablewithasinglerefrigerantcircuitandthreestagecoolingoperationonallmodels.
c.Compressormotorsshallbecooledbyrefrigerantgaspassingthroughmotorwindings.
d.Compressorsshallbeinternallyprotectedfromhighdischargetemperatureconditions.
e.Compressorsshallbeprotectedfromanover-temperatureandover-amperageconditionsbyaninternal, motoroverloaddevice.
f.Compressorshallbefactorymountedonrubbergrommets.
g.Compressormotorsshallhaveinternallinebreakthermal,currentoverloadandhighpressuredifferential protection.
h.Crankcaseheatersshallbestandardoneachcompressoranddeactivatedwheneveracompressorisinoperation. 238119.13.J. FilterSection
1.Filtersaccessisspecifiedintheunitcabinetsectionofthisspecification.
2.Filtersshallbeheldinplacebyapreformedslideoutfiltertray,facilitatingeasyremovalandinstallation.
3.Shallconsistoffactory-installed,lowvelocity,throw-away2-in.thickfiberglassfilters.
4.Filtersshallbestandard,commerciallyavailablesizes.
5.Onlyonesizefilterperunitisallowed.
6.4-infiltercapabilityispossiblewithafield-installedpre-engineeredslideoutfiltertrackaccessory.4-infilters arefieldfurnished.
238119.13.K.EvaporatorFanandMotor
1.Evaporatorfanmotor:
a.Shallhavepermanentlylubricatedbearings.
b.Shallhaveinherentautomatic-resetthermaloverloadprotectionorcircuitbreaker.
c.Shallhaveamaximumcontinuousbhpratingforcontinuousdutyoperation;nosafetyfactorsabovethat ratingshallberequired.
d.ShallbeVariableFrequencydutytomatchthethreestagecompressionlogic.
e.Shallcontainmotorshaftgroundingringtopreventelectricalbearingflutingdamagebysafelydiverting harmfulshaftvoltagesandbearingcurrentstoground.
2.VariableFrequencyDrive(VFD).ForindoorfanmotorStagedAirVolume(SAV™)operation:
a.Shallbeinstalledinsidetheunitcabinet,mounted,wiredandtested.
b.ShallcontainElectromagneticInterference(EMI)frequencyprotection.
c.InsulatedGateBi-PolarTransistors(IGBT)usedtoproducetheoutputpulsewidthmodulated(PWM) waveform,allowingforquietmotoroperation.
d.Self-diagnosticswithfaultandpowercodeLEDindicator.FieldaccessoryDisplayKitavailableforfurther diagnosticsandspecialsetupapplications.
e.RS485capabilitystandard.
f.Electronicthermaloverloadprotection.
g.5%swingingchokesforharmonicreductionandimprovedpowerfactor.
h.Allprintedcircuitboardsshallbeconformalcoated.
i.Shallnotcontainvisualdisplaytoadjustinternalsetting.Onlyavailableasfield-installedkit.
3.Belt-drivenEvaporatorFan:
a.Beltdriveshallincludeanadjustable-pitchmotorpulleyandbeltbreakprotectionsystem.
b.Shalluserigidpillowblockbearingsystemwithlubricatefittingsatareaccessibleorlubricationline.
c.Blowerfanshallbedouble-inlettypewithforward-curvedblades.
d.Shallbeconstructedfromsteelwithacorrosionresistantfinishanddynamicallybalanced. 238119.13.L.CondenserFansandMotors
1.Condenserfanmotors:
a.Shallbeatotallyenclosed–multi-speedECMmotor.
b.Shallusepermanentlylubricatedbearings.
c.Shallhaveinherentthermaloverloadprotectionwithanautomaticresetfeature.
d.Shalluseashaft-downdesign.
2.CondenserFans:
a.Shallbeadirect-drivenpropellertypefan.
b.Shallhavegalvanizedaluminum(galvalum)bladesrivetedtocorrosion-resistantsteelspidersandshallbe dynamicallybalanced.
238119.13.M. SpecialFeatures,OptionsandAccessories
1.StandardLeakEconomizers:
a.Availableasfactory-installedoption(verticalorhorizontal)orfield-installedaccessory(verticalorhorizontal)onallelectro-mechanicalandRTUOpenmodels.SystemVu™field-installedaccessory(verticalor horizontal)alsoavailable.
b.StandardleakeconomizersareavailablewithEconoMi$erXcontrolsforelectro-mechanicalunits,or EconoMi$er2controlsforRTUOpenorSystemVuunits.
c.Integrated,geardrivenopposedbladedesigntypecapableofsimultaneouseconomizerandcompressor operation.
d.Damperbladesshallbegalvanizedsteelwithcompositegears.Plasticorcompositebladesonintakeorreturn shallnotbeacceptable.
e.Shallbeequippedwithgeardrivendampersforboththeoutdoorventilationairandthereturnairforpositive airstreamcontrol.
f.Standardleakratemodelsshallbeequippedwithleakagedampers,nottoexceed2%leakageat1in.wg pressuredifferential.
g.Shallbecapableofintroducingupto100%outdoorair.
h.Economizer’sbarometricreliefdampersshallbesizedtoallowupto100%relief(actualresultswillbe basedonspecificjobconditions).
2.Ultra-LowLeakEconomizers:
a.Availableasafactory-installedoption(verticalorhorizontal)orfield-installedaccessory(verticalorhorizontal)onallmodelsincluding:electro-mechanical,RTUOpen,andSystemVu.
b.Ultra-LowLeakeconomizerdampersmeetCalifornia’sTitle24section140.4prescriptiverequirementsfor leakage,reliabilitytesting,etc.,andASHRAE90.1-2013requirementsfordamperleakage.
c.EconomizersareavailablewithEconoMi$erXcontrolsforelectro-mechanicalunits,orEconoMi$er2controls forRTUOpenorSystemVuunits.
d.Integrated,geardrivenopposedbladedesigntypecapableofsimultaneouseconomizerandcompressor operation.
e.Damperbladesshallbegalvanizedsteelwithcompositegears.Plasticorcompositebladesonintakeorreturn shallnotbeacceptable.
f.Shallbeequippedwithgeardrivendampersforboththeoutdoorventilationairandthereturnairforpositive airstreamcontrol.
g.Shallbecapableofintroducingupto100%outdoorair.
h.Economizer’sbarometricreliefdampersshallbesizedtoallowupto100%relief(actualresultswillbe basedonspecificjobconditions).
(1.) EconoMi$erXEconomizerControls:
a.Forusewithfactory-installed(verticalorhorizontal)orfield-installedaccessory(verticalorhorizontal) onelectro-mechanicalunitswithstandardleakorUltra-LowLeakeconomizers.
b.MeetsCalifornia’sTitle24section120.2mandatoryrequirementsforeconomizerFaultDetectionand Diagnosis(FDD).
c.EconomizercontrollershallbeHoneywellW7220JADEthatprovides:
i.2-lineLCDinterfacescreenforsetup,configurationandtroubleshooting.
ii.On-boardFDDdetectsandalertswheneconomizerisnotoperatingproperly.
iii.Sensorfailurelossofcommunicationidentification.
iv.Automaticsensordetection.
v.Capabilitiesforusewithmulti-speedindoorfanunits.
d.CompressorlockouttemperatureonW7220isadjustablefrom-45to80°F,setatafactorydefaultof32°F.
e.Shallbedesignedtospringreturncloseoutsideairdamperduringlossofpower.
f.Actuatorshallbedirectcoupledtoeconomizergear.Nolinkagearmsorcontrolrodsshallbeacceptable.
g.Utilizesdigitaldrybulborenthalpyoutsideairsensors.Factory-installedeconomizersavailablewith drybulborenthalpy.Drybulbsensorsinstalledonallfield-installedeconomizeraccessories.
(2.) EconoMi$er2EconomizerControls:
a.Forusewithfactory-installed(verticalorhorizontal)orfield-installedaccessory(verticalorhorizontal) onRTUOpenorSystemVu™ unitswithstandardleakorUltra-LowLeakeconomizers.Note:Factory-installedEconoMi$er2isavailableonSystemVuunitswithUltra-LowLeakeconomizersonly.
b.EconoMi$er2economizersarecontrolledbyRTUOpenorSystemVuunitcontrollers,whichshallbe 4-20mAdesign.
c.RTUOpenandSystemVucontrolsmeetCalifornia’sTitle24section120.2mandatoryrequirementsfor economizerFaultDetectionandDiagnosis.
d.Availableonfactory-installed(verticalonly)economizerswithdrybulborenthalpyoutsideairsensors.
Field-installedaccessories(verticalorhorizontal)areavailablewithdrybulboutsideairsensorsonly.
e.Outdoorairsensorsetpointshallbeadjustableandshallrangefrom40to100°F(4to38°C).Additional sensoroptionsshallbeavailableasaccessories.
f.Shallbedesignedtospringreturncloseoutsideairdamperduringlossofpower.
g.Actuatorshallbedirectcoupledtoeconomizergear.Nolinkagearmsorcontrolrodsshallbeacceptable.
h.Theeconomizercontrollershallalsoprovidecontrolofanaccessorypowerexhaustunitfunction.Factoryset at100%,witharangeof0%to100%.
i.Theeconomizershallmaintainminimumairflowintothebuildingduringoccupiedperiodandprovide designventilationrateforfulloccupancy.
j.Controllershalldriveoutsideairdamperscompletelyclosedwhentheunitisintheunoccupiedmode.
k.Economizercontrollershallaccepta4-20mACO2 sensorinputforIAQ/DCVcontrol.Inthismode, dampersshallmodulatetheoutdoorairdampertoprovideventilationbasedonthesensorinput.
l.Economizercontrollershallprovideindicationswheninfreecoolingmode,intheDCVmode,orthe exhaustfancontactisclosed.
3.CondenserCoilHailGuardAssembly
a.Shallprotectagainstdamagefromhail.
b.Shallbelouveredstyledesign.
4.Unit-Mounted,Non-FusedDisconnectSwitch:
a.Switchshallbefactory-installed,internallymounted.
b.NationalElectricCode(NEC)andETLapprovednon-fusedswitchshallprovideunitpowershutoff.
c.Shallbeaccessiblefromoutsidetheunit
d.Shallprovidelocalshutdownandlockoutcapability
e.Sizedonlyfortheunitasorderedfromthefactory.Doesnotaccommodatefield-installeddevices
5.HACRBreaker
a.Thesemanualresetdevicesprovideoverloadandshortcircuitprotectionfortheunit.Factorywiredand mountedwiththeunits,withaccesscovertohelpprovideenvironmentalprotection.On575Vapplications, HACRbreakercanonlybeusedwithWYEpowerdistributionsystems.UseonDeltapowerdistribution systemsisprohibited.
b.Sizedonlyfortheunitasorderedfromthefactory.Doesnotaccommodatefield-installeddevices.
6.ConvenienceOutlet:
a.Poweredconvenienceoutlet.
(1.) Outletshallbepoweredfrommainlinepowertotherooftopunit.
(2.) Outletshallbepoweredfromlinesideofdisconnectbyinstallingcontractor,asrequiredbycode.If outletispoweredfromloadsideofdisconnect,unitelectricalratingsshallbeETLcertifiedandrated foradditionaloutletamperage.
(3.) Outletshallbefactory-installedandinternallymountedwitheasilyaccessible115-vfemalereceptacle. (4.) Outletshallinclude15ampGFIreceptacleswithindependentfuseprotection.
(5.) Voltagerequiredtooperateconvenienceoutletshallbeprovidedbyafactory-installedstep-down transformer.
(6.) Outletshallbeaccessiblefromoutsidetheunit.
(7.) Outletshallincludeafield-installed“WetinUse”cover.
b.Non-Poweredconvenienceoutlet.
(1.) Outletshallbepoweredfromaseparate115/120vpowersource. (2.) Atransformershallnotbeincluded.
(3.) Outletshallbefactory-installedandinternallymountedwitheasilyaccessible115-vfemalereceptacle. (4.) Outletshallinclude15ampGFIreceptacleswithindependentfuseprotection.
(5.) Outletshallbeaccessiblefromoutsidetheunit.
(6.) Outletshallincludeafield-installed“WetinUse”cover.
7.Fan/FilterStatusSwitch:
a.Switchshallprovidestatusofindoorevaporatorfan(ON/OFF)orfilter(CLEAN/DIRTY).
b.Statusshallbedisplayedeitherovercommunicationbus(whenusedwithdirectdigitalcontrols)orwithan indicatorlightatthethermostat.
8.CentrifugalPowerExhaust:
a.Powerexhaustshallbeusedinconjunctionwithanintegratedeconomizer.
b.Independentmodulesforverticalorhorizontalreturnconfigurationsshallbeavailable.
c.Horizontalpowerexhaustisshallbemountedinreturnductwork.
d.Powerexhaustshallbecontrolledbyeconomizercontrolleroperation.Exhaustfansshallbeenergizedwhen dampersopenpastthe0-100%adjustablesetpointontheeconomizercontrol.
9.RoofCurbs(Vertical):
a.Fullperimeterroofcurbwithexhaustcapabilityprovidingseparateairstreamsforenergyrecoveryfromthe exhaustairwithoutsupplyaircontamination.
b.Formedgalvanizedsteelwithwoodnailerstripandshallbecapableofsupportingentireunitweight.
c.Permitsinstallationandsecuringofductworktocurbpriortomountingunitonthecurb.
10.High-StaticIndoorFanMotor(s)andDrive(s):
a.High-staticmotor(s)anddrive(s)shallbefactory-installedtoprovideadditionalperformancerange.
11.OutdoorAirEnthalpySensor:
a.Theoutdoorairenthalpysensorshallbeusedtoprovidesingleenthalpycontrol.Whenusedinconjunction withareturnairenthalpysensor,theunitwillprovidedifferentialenthalpycontrol.Thesensorallowsthe unittodetermineifoutsideairissuitableforfreecooling.
12.ReturnAirEnthalpySensor:
a.Thereturnairenthalpysensorshallbeusedinconjunctionwithanoutdoorairenthalpysensortoprovide differentialenthalpycontrol.
13.IndoorAirQuality(CO2)Sensor:
a.Shallbeabletoprovidedemandventilationindoorairquality(IAQ)control.
b.TheIAQsensorshallbeavailableinductmount,wallmount,orwallmountwithLEDdisplay.Thesetpoint shallhaveadjustmentcapability.
14.Smokedetectors:
a.ShallbeaFour-WireControllerandDetector.
b.Shallbeenvironmentalcompensatedwithdifferentialsensingforreliable,stable,anddrift-freesensitivity.
c.Shallusemagnet-activatedtest/resetsensorswitches.
d.Shallhavetool-lessconnectionterminalaccess.
e.Shallhavearecessedmomentaryswitchfortestingandresettingthedetector.
f.Controllershallinclude:
(1.) Onesetofnormallyopenalarminitiationcontactsforconnectiontoaninitiatingdevicecircuitona firealarmcontrolpanel.
(2.) TwoForm-Cauxiliaryalarmrelaysforinterfacewithrooftopunitorotherequipment.
(3.) OneForm-Csupervision(trouble)relaytocontroltheoperationoftheTroubleLEDonaremotetest/ resetstation.
(4.) Capableofdirectconnectiontotwoindividualdetectormodules.
(5.) Canbewiredtoupto14otherductsmokedetectorsformultiplefanshutdownapplications.
15.Horn/StrobeAnnunciator
a.Providesanaudible/visualsignalingdeviceforusewithfactory-installedoptionorfield-installedaccessory smokedetectors.
(1.) Requiresinstallationofafield-supplied24-vtransformersuitablefor4.2VA(AC)or3.0VA(DC)per horn/strobeaccessory.
(2.) Requiresfield-suppliedelectricalbox,NorthAmerican1-gangbox,2-in(51mm)x4-in(102mm). (3.) Shallhaveaclearcoloredlens.
16.TimeGuard
a.Shallpreventcompressorshortcyclingbyprovidinga5-minutedelay(±2minutes)beforerestartinga
compressoraftershutdownforanyreason.
b.Onedeviceshallberequiredpercompressor.
17.ElectricHeat:
a.HeatingSection
(1.) Heaterelementopencoilresistancewire,nickel-chromealloy,0.29inchesinsidediameter,strungthrough ceramicinsulatorsmountedonmetalframe.Coilendsarestakedandweldedtoterminalscrewslots.
(2.) Heaterassembliesareprovidedwithintegralfusingforprotectionofinternalheatercircuitsnot exceeding48ampseach.Autoresetthermolimitcontrols,magneticheatercontactors(24vcoil)and terminalblockallmountedinelectricheatercontrolbox(minimum18gagalvanizedsteel)attachedto endofheaterassembly.
18.BarometricHood(HorizontalEconomizerApplications)
a.Shallberequiredwhenahorizontaleconomizerandbarometricreliefarerequired.Barometricrelief dampermustbeinstalledinthereturnair(horizontal)ductwork.Thishoodprovidesweatherprotection.
19.HingedAccessPanels
a.Shallprovideeasyaccessthroughintegratedquarterturnlatches.
b.Shallbeonmajorpanelsof–filter,controlbox,fanmotorandcompressor
20.DisplayKitforVariableFrequencyDrive
a.KitallowstheabilitytoaccesstheVFDcontrollerprogramstoprovidespecialsetupcapabilitiesand diagnostics.
b.Kitcontainsdisplaymoduleandcommunicationcable.
c.DisplayKitcanbepermanentlyinstalledintheunitorusedonanySAV™ systemVFDcontrollerasneeded.
21.Thermostat:
a.Duetothethreestagecoolingcapacitydesignoftheseunits,athreestagecoolingthermostatisrequiredfor theunittoperformatlistedoperatingefficiencies.
b.CarrieroffersaHoneywellbrandedT7350D(3Cool/3Heat)CommercialProgrammableThermostat.This provides:
—7-dayprogrammable365-dayclockwithholidayprogramming
—AutomaticDaylightSavingTimeadjustment
—Backlitdisplay
—Changeoverselections:automaticormanual
—Fanconfigurable:continuousorintermittentduringoccupied
22.Humidi-MiZerAdaptive® DehumidificationSystem:
a.TheHumidi-MiZerAdaptiveDehumidificationSystemshallbefactoryinstalled,certifiedandtestedto providegreaterdehumidificationoftheoccupiedspacebyprovidingtwodistinctmodesofdehumidification operationinadditiontoitsnormaldesigncoolingmode:
(1.) Subcoolingmodefurthersubcoolsthehotliquidrefrigerantleavingthecondensercoilaswellas reheatleavingairstream.Itcanprovidebothbettercoolingcapacityaswellasdehumidification processwhenbothtemperatureandhumidityinthespacearenotsatisfied.
(2.) Hotgasreheatmodeshallmixaportionofhotgasfromthedischargeofcompressorwiththehot liquidrefrigerantleavingthecondensercoiltocreateatwo-phasewarmrefrigerantinthereheatcoil whichresultsinaneutralleavingairtemperaturewhenonlyhumidityinthespaceisnotsatisfied.