www.csgwebsite.com LETTER OF TRANSMITTAL

To: / City of Gilroy / Date: / April 25, 2016* 1st review
7351 Rosanna Street / CSG PC#: / 362372
Gilroy, CA 95020 / Agency PC#: / 196040056
Attn: / Building Department / Job Address: / 8585 Forest St.
Job Description: / Install 3 antennas, replace TMAs add 3 RRUs and 6 diplexers- “T-Mobile”
Status: / Plan is ready for permit issuance for the following:
Plan is approved. / Architectural
Plan is approved with conditions. See remarks. / Structural
Plan is approved with redlines. See remarks. / Electrical
Plan is approved with redlines and conditions. See remarks. / Plumbing
X / Plan requires corrections. See attached list. / Mechanical
Other: / Energy
CalGreen
Other:

We have received the following documents:

X / Plans 1 set dated 2/18/’16 / Set(s) Energy Calculation
Structural Calculations / Specifications
Soil Report / Other:

Special items to note:

Plan has been stamped and signed by CSG.
X / Special inspection required for / Epoxy anchor bolts
Environmental Health Services approval required.
Please collect a plan review fee for hrs. of plan check. / Amount: / $
Remarks:
FROM: / David Nesbet, P.E.
CSG Consultants, Inc.

550 Pilgrim Drive ¨ Foster City, CA 94404 ¨ Tel: 650-522-2500 ¨ Fax: 650-522-2599

¨ www.csgwebsite.com ¨

CITY OF GILROY

BUILDING INSPECTION DIVISION

CORRECTION LIST

Date: April 25, 2016

Subject: Install 3 antennas, replace TMAs, add 3 RRUs and 6 diplexers – “T-Mobile”

Address: 8585 Forest St.

Plan Checker: David Nesbet, P.E.

DIRECTIONS FOR RESUBMITTAL

IMPORTANT NOTICE: Please return both this correction list and any marked drawings or calculations along with your revised drawings when resubmitting. Please reference on the correction list where on the plans the corrections have been made to assist in providing a more timely review. Be advised that the plan review application for this project may expire 180 days from the date of original application.

PLAN CHECK COMMENTS

1.  Please submit a written response addressing each comment below. Refer to specific details on specific sheets in the responses. Note that plan review process may be significantly delayed if complete and thorough responses are not provided.

Response: ______

2.  Complete and submit a Special Inspection form for epoxy anchor bolts. This form is available from the building department and it must be submitted prior to permit issuance. Please make sure that the required signatures are provided and that the area of Special Inspection is clearly indicated on the form and on the cover sheet of plans.

Response: ______

3.  Provide a calculation to check the H-Frame anchorage that is shown in detail 4/C-3.

Response: ______

(End of Comments)

CSG: 362372.GLRY