Avaya UPS Planning Guide
6000 VA Online UPS
UPS
6000 VA UPS Technical SpecificationsElectrical Input
Power Rating / 6000 VA/4200 Watts
Nominal Voltage / 208V (auto-sensing 208-240V)
Voltage Range / 160-288V nominal
Nominal Frequency / 50/60 Hz, auto-sensing
Electrical input requirement / 32A D-Type SPN (single phase & neutral) MCB
Connections / L6-30P detachable input line cord or hardwired
Power Factor / >0.96
Electrical Output
Nominal voltage / See PPDM listings
Voltage Regulation / ±3% (nominal for normal and battery modes)
Voltage Waveform / Sine wave
Output Receptacles / See PPDM listings
Environmental and Safety
Operating Temperature / 0 to 40°CStorage Temperature / 0 to 25°C
Transit Temperature / 25 to 55°C
Relative Humidity / 5-95% non-condensing
Operating Altitude / Up to 3,000 meters above sea level
Transit Altitude / Up to 10,000 meters above sea level
Heat Dissipation (maximum) / 630W or 2160BTU/hr
Audible Noise / <50 dBA during normal mode; <60 dBA during battery mode
Leakage Current / <0.6 mA
Communications / Web/SNMP card and USB port standard
Surge Suppression / ANSI C62.41 Category B3; EN 61000-4-5 Level 3, Criteria B
Safety Conformance / UL1778; CAN/CSA C22.2, No. 107.1, 107.2; EN 50091-1-1
and IEC 60950; NOM-019-SCFUI
Agency Markings / UL, cUL, NOM-NYCE, CE
EMC (Class A) / EN 50091-2, FCC Part 15, ICES-003
Battery
Type / Sealed, maintenance-free, valve-regulated, lead-acid
UPS Configuration / (20) 12V, 7.2 Ah batteries (included as standard)
EBM Configuration / (20) 12V, 9 Ah batteries
UPS Battery Charging / <2 hours to 80% usable capacity at nominal line voltage
after full load discharge
EBM Battery Charging / No more than 15x discharge time to 90% usable capacity
at nominal line voltage after full load discharge
Options
4-Post Rail Kit / Allows you to install UPS in standard 19-inch equipment
(SAP 700315138) rack
Extended Battery Module / Connect up to four 3U modules to increase backup time
Modules (EBM)
Extended Battery Cabinet / Connect up to six large cabinets to increase backup
Cabinets (EBC) time up to 8 hours
Due continuing product improvement programs, specifications are subject to change withoutnotice.
6000 VA UPS Model Selection Guide and Specifications: Uninterruptible Power System (UPS) /
Model / Avaya SAP / Input Voltage
(Vac) / Output Voltage (Vac) / Input
Connection / Output Connection / Dimensions
HxWxD (mm) / Unit Wt
(kg) /
6000VA PnP / 700404627 / See PPDM / See PPDM / L6-30P / L6-30R / 218 (5U) x 442 x 683 / 89.4 /
6000VA HW / 700404635 / 208-240 / 208-240 / Hardwired / Hardwired / 218 (5U) x 442 x 683 / 89.4 /
Powerpass Distribution Modules (PPDM): Choose one to complete UPS configuration /
PPDM, HW / 700404650 / 208-240 / 208-240/120 / Hardwired / Hardwired / 133 (3U) x 442 x 683 / 46.7 /
PPDM, EURO Plug & Play / 700404700 / 208-240 / 208-240 / L6-30P / (8) IEC-320-C13, (4) IEC-320-C19,
(1) IEC-309, 32A / 133 (3U) x 442 x 683 / 46.7 /
Optional Batteries /
EBM / 700404726 / - / - / - / - / 133 (3U) x 442 x 683 / 69.9 /
EBC240 / 700404718 / - / - / - / - / 714 x 648 x 716 / 440 /
Typical EBM Installation with Hardwired UPS (700315047): .
Plug ‘n Play UPS (700315054) with Hardwired PPDM (700315112) configuration: .
Optional PPDM (700358609): .