United Enertech 2” Deep Drainable Blade Louver
3005 South Hickory Street
Chattanooga, Tennessee 37407
Phone(423) 698-7715
Fax (423) 698-6629
Product Guide Specification
Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) MasterFormat, Three-Part SectionFormat, and PageFormat, contained in the CSI Manual of Practice. Five-digit section numbers are from MasterFormat, 1995 edition.
The section must be carefully reviewed and edited by the Architect to meet the requirements of the project and local building code. Coordinate with other specification sections and the drawings.
Delete all “Specifier Notes” when editing this section.
Section 10210
EXTRUDED ALUMINUM STATIONARY LOUVERS
Specifier Notes: This section covers United Enertech extruded aluminum stationary louvers with drainable blades, Model FL-D-2. Consult United Enertech for assistance in editing this section for specific applications.
PART 1GENERAL
1.1SECTION INCLUDES
- Extruded aluminum stationary louvers with drainable blades.
1.2RELATED SECTIONS
Specifier Notes: Edit the following list as required for the project. List other sections with work directly related to the louvers.
- Section 03300 – Cast-In-Place Concrete.
- Section 04200 – Masonry Units.
- Section 05100 – Structural Metal Framing
- Section 06100 – Rough Carpentry.
- Section 07410 – Metal Wall Panels.
- Section 07600 – Flashing and Sheet Metal
- Section 07920 – Joint Sealants.
FL-D-2 10210-1
- Section 09910 – Paints.
- Section 15850 – Air Outlets and Inlets
1.3REFERENCES
- AAMA 2605-98 – High Performance Organic Coatings on Architectural Extrusions and Panels.
- AMCA 500-L – Test Methods for Louvers.
- SUBMITTALS
- Comply with requirements of Section 01330 - Submittal Procedures.
- Product Data: Submit manufacturer’s product data including performance data.
- Shop Drawings: Submit shop drawings indicating materials, construction, dimensions< accessories, and installation details.
- Samples: Submit sample of louver to show frame, blades, bird screen, vertical supports, accessories, finish, and color.
1.5Quality Assurance
- Louvers licensed to bear AMCA Certified Ratings Seal. Ratings based on tests and procedures performed in accordance with AMCA 511 and comply with AMCA Certified Ratings Program. AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
1.6DELIVERY, STORAGE, AND HANDLING
- Delivery: Deliver materials to site in manufacturer’s original, unopened containers and packaging, with labels clearly indicating manufacturer and material.
- Storage: Store materials in a dry area indoors, protected room damage and in accordance with manufacturer’s instructions.
- Handling: Protect materials and finishes during handling and installation to prevent damage.
PART 2PRODUCTS
2.1MANUFACTURER
A.United Enertech, 3005 South Hickory Street, Chattanooga, Tennessee 37407. Phone (423) 698-7715. Fax (423) 698-6629.
2.2EXTRUDED ALUMINUM STATIONARY LOUVERS
A.Fabrication:
1.Model: FL-D-2
2.Performance Ratings:AMCA licensed.
3.Frame:
a.Material: Extruded aluminum, Alloy 6063-T5.
b.Wall Thickness: 0.060 inch (1.6mm), nominal.
c.Depth: 2 inches (51mm).
d.Construction: [Standard] [Flange].
FL-D-2 10210-2
4.Blades:
a.Style: Drainable.
b.Material: Extruded aluminum, Alloy 6063-T5.
c.Wall Thickness: 0.060 inch (1.5mm), nominal.
d.Angle: 37 degrees
e.Centers: 1.5 inches (38.1 mm), nominal
5.Bird Screen:
a.Material: Aluminum, [3/4 inch x 0.051 inch (19 mm x 1.3 mm), expanded, flattened]
b.Frame: Removable, rewireable.
6.Gutters: Drain gutter in each blade.
7.Downspouts: Downspouts in jambs to drain water from louver for minimum water cascade from blade to blade.
8.Vertical Supports: Hidden vertical supports to allow continuous line appearance up to 120” (3,048 mm)
9.Assembly: Factory assemble louver components.
- Performance Data:
- Based on testing 48 inch x 48 inch (1,219 mm x 1,219 mm) size unit in accordance with AMCA
500-L
- Free Area: 54 percent, nominal.
- Free Area Size: 8.66 square feet (.8 m2).
- Maximum Recommended Air Flow Thru Free Area: 805 feet per minute (242 m/min).
- Air Flow: 6,971 cubic feet per minute (197 m3/min).
- Maximum Pressure Drop: 0.08 inches w.g. (0.02 kPa).
- Water Penetration: Maximum of 0.01 ounces per square foot (3.1 g/m2) of free area at an air flow of 805 feet per minute (242 m/min.) free area velocity when tested for 15 minutes.
Specifier Notes: Specify required design loading.
- Design Load: Incorporate structural supports required to withstand wind load of [20] [ ______] pounds per square foot ( [0.96] [______] kPa).
2.3ACCESSORIES
Specifier Notes: Consult United Enertech for assistance in specifying accessories for specific applications.
- Blank-Off Panels: [0.040 inch (1mm) aluminum sheet] [1 inch (25 mm), aluminum skin, insulated core], factory installed with removable screws and neoprene gaskets.
- Hinged Frame: Continuous piano hinge attached to tube subframe.
- [Front] [Rear] Security Bars: [Aluminum, 1/2 inch x 1/2 inch (13mm x 13mm), welded to louver].
- Filter Racks: Formed channel racks to accept standard [1 inch (25mm)] [2 inch (51mm)] thick filters.
Specifier Notes: Consult United Enertech for assistance in selecting from standard and nonstandard bird and insect screens for specific applications.
- Bird Screens:
FL-D-2 10210-3
- Insect Screen:
- Extended Sills: Extruded aluminum, Alloy 6063-T5. Minimum nominal wall thickness .081 inch (2 mm).
- Visible Mullions: Manufacturer’s standard horizontal or vertical visible mullions for architectural accent as indicated on drawings.
2.4FACTORY FINISH
Specifier Notes: Specify one of the following factory finishes and delete the others. Mill finish is standard. Consult United Enertech for assistance in choosing factory finish for specific applications.
- Standard mill finish.
- 2 or 3 Coat Fluoropolymer Coating:
- Conform to AAMA 2605-05.
- Apply coating following cleaning and pretreatment.
- Cleaning: AA-C12C42R1X.
- Dry louvers before final finish application.
- Total Dry Film Thickness: Approximately 1.2 mils (0.03 mm), when baked at 450 degrees F (232 degrees C) for 10 minutes.
- Warranty: Limited 20 year warranty on standard colors.
- Super Durable Baked Powder 2 Coat Coating:
- Conform to AAMA 2604-02.
- Apply coating following cleaning and pretreatment.
- Cleaning: AA-C12C42R1X.
- Dry louvers before final finish application.
- Total Dry Film Thickness: Approximately 1.2 mils (0.03 mm), when baked at 450 degrees F (232 degrees C) for 10 minutes.
- Warranty: Limited 7 year warranty on standard colors.
- Color Anodize Finish:
- Comply with Aluminum Association AA-C22A44.
- Apply finish following chemical etching and pretreatment.
- Electrolytically deposited color anodized finish.
- Minimum Thickness: 0.7 mils (0.018 mm).
Specifier Notes: Choose one of the following two clear anodize finishes and delete the other. Clear anodize is available in 2 surface depths. Clear anodize finish 204-R1 is recommended for normal weather exposure. Clear anodize finish 215-R1 is recommended for severely corrosive or abrasive atmosphere exposure. Consult United Enertech for assistance in specifying clear anodize for specific applications.
G.Clear Anodize Finish:
- Comply with Aluminum Association AA-C22A31. Clear anodize finish 204-R1.
- Apply finish following chemical etching and pretreatment.
- Minimum Thickness: 0.4 mils (0.01 mm), 30 minute anodizing process.
H.Clear Anodize Finish:
- Comply with Aluminum Association AA-C22A41. Clear anodize finish 215-R1.
- Apply finish following chemical etching and pretreatment.
- Minimum Thickness: 0.7mils (0.018 mm), 60 minute anodizing process.
FL-D-2 10210-4
- Prime Coat:
- Apply baked prime coat following chemical cleaning and pretreatment.
- Primer preparation for field painting.
Specifier Notes: Consult United Enertech color selection chart for standard color samples. United Enertech can match most custom colors in Kynar based paint.
- Color for Fluoropolymer Coating: Color as selected by Architect from manufacturer’s standard colors.
- Color for Anodize Finish: [Clear Anodize] [Dark Bronze] [Medium Bronze].
PART 3EXECUTION
3.1EXAMINATION
- Inspect areas to receive louvers. Notify the Architect of conditions that would adversely affect the installation or subsequent utilization of the louvers. Do not proceed with installation until unsatisfactory conditions are corrected.
3.2INSTALLATION
A.Install louvers at locations indicated n the drawings and in accordance with manufacturer’s instructions.
- Install louvers plumb, level, in plane of wall, and in alignment with adjacent work.
- Install joint sealants as specified in Section 07920.
Specifier Notes: Specify field topcoat if prime coat is specified in PART 2 – PRODUCTS.
- Apply field topcoat within 6 months of application of shop prime coat. Apply field topcoat as specified in Section 09910.
3.3CLEANING
- Clean louver surfaces in accordance with manufacturer’s instructions.
- Repair minor damaged surfaces as directed by Architect.
END OF SECTION
FL-D-2 10210-5