I

Seite 3/3 I

Tender text "Overvoltage protection for Data systems”

RS485 signals

Overvoltage protection in wall mounted housing K21 for Data systems with RS485 Interface. Integrated 4-wire protective circuit for the data interface with high-speed suppression diodes and the possibility for high impedance earthing via a gas discharge tube.

Technical data:

2 x RS485 signals up to max.12V

Baudrate: < 6 MBd

Ordering data:

Make: Weidmüller

Surface-mounted housing with

interface protection : K21 (length: 125mm, width: 80 mm, height : 57mm)

With 5 PG screw fittings

Order No. 8008501001

Type : RS485 protection

RS485 signals

Overvoltage protection in plug-in housing LPU for data terminal equipment with RS 485 interface . Integrated 2-wire protective circuit for the data interface with high-speed suppression diodes and the possibility for high impedance earthing via a gas discharge tube .

Technical data:

RS485 signals up to max.12V

Baudrate: < 9600 Bd

Ordering data:

Make: Weidmüller

Order No. 9454930000

Type : RS485 protection

Accessories : housing SEG-U 8007871001

EIB signals

Overvoltage protection in slim terminal housing (6mm) with PE contact and spring clamp connection in sizes 0.5 to 1.5mm². The PE connection is made by snapping onto an earthed 35mm mounting rail .

The EIB bus is protected using gas discharge tubes connected between the lines and to earth.

Technical data:

Max. rated voltage: 90Vdc

Resistance per path: 0.2 ohms

Discharge current, Imax (8/20µs) : 10 kA

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 700V

Ordering data:

Make: Weidmüller

Order No. 8449130000

Type : MCZovp gas discharge tube

LON signals

Overvoltage protection in slim terminal housing (6mm) with PE contact and spring clamp connection in sizes 0.5 to 1.5mm². The PE connection is made by snapping onto an earthed 35mm mounting rail . The LON signal (FTT or TP78) is protected using high-speed suppression diodes connected between the lines and to earth.

Technical data:

Max. rated voltage: +-12V

Resistance per path: 0.5 ohms

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 30V

Damping, typical: < 5db

Ordering data:

Make: Weidmüller

Order No. 8473470000

Type : MCZovp LON

Accessories for LON

Termination for LON in terminal block DK4 (width 12mm) .

The LON network can be terminated with jumpers; LP BUS, LP FREE or TP / XF can be connected.

Technical data:

Max. rated voltage: 48V

Resistance per path: 0.5 ohms

Ordering data:

Make: Weidmüller

Order No. 8496110000

Type : Dialoc Term

RS232

Overvoltage protection in installation housing (22.5mm) and screw terminal in sizes 0.5 to 1.5mm². The RS232 signal (RxD, TxD, GnD) is protected using gas discharge tubes and high-speed suppression diodes connected between the lines and to earth.

Technical data:

Max. rated voltage : 12-14.5V

Resistance per path: 1.3 ohms

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 20V

Baudrate 9600 bd

Ordering data:

Make: Weidmüller

Order No. 1170460000

RS232

Overvoltage protection in the adapter plug (25-pole D-sub). The RS232 signals and the handshake lines are protected using gas discharge tubes connected to PE and high-speed suppression diodes connected between the lines.

Technical data:

Max. rated voltage : 12-14.5V

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 20V

Baudrate 19200 bd

Ordering data:

Make: Weidmüller ZS RS 232/B-S

Order No. 8570500000

Make: Weidmüller ZS RS 232/S-B

Order No. 8570510000