Specialty Exterior Lighting ME- Building Group

SECTION 265616 – SPECIALTY EXTERIOR LIGHTING

PART 1 - GENERAL

1.1  RELATED DOCUMENTS

  1. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2  SUMMARY

  1. This Section includes the following:
  2. Exterior specialty luminaires with lamps and ballasts.

1.3  PERFORMANCE REQUIREMENTS

  1. Structural Performance: Provide bollard assemblies, including anchorages and foundations.

1.4  SUBMITTALS

  1. Product Data: Include data on features, accessories, finishes, and the following:
  2. Physical description of luminary, including materials, and dimensions.
  3. Details of installation.
  4. Ballasts, including energy-efficiency data.
  5. Lamps, including life, output, and energy-efficiency data.
  6. Bases and anchoring, including anchor-bolt templates.
  7. Shop Drawings: Include elevations and details showing general arrangement, anchoring and supporting systems.
  8. Include details of foundation system.

1.5  QUALITY ASSURANCE

  1. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA70, Article100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
  2. Comply with NFPA70.

PART 2 - PRODUCTS

2.1  MANUFACTURERS

  1. Basis of Design Product: Each luminary is based on the product named. Provide the named product or propose a substitution for approval.

2.2  LUMINAIRES, GENERAL REQUIREMENTS

  1. Comply with UL1598 and be listed and labeled for installation in wet locations.
  2. Corrosion-resistant aluminum, free of burrs and sharp corners and edges.
  3. Exposed Hardware Material: Stainless steel.

2.3  BALLASTS FOR HID LAMPS

  1. Comply with ANSIC82.4 and UL1029 and capable of open-circuit operation without reduction of average lamp life. Include the following features, unless otherwise indicated:
  2. Ballast Circuit: Constant-wattage autotransformer or regulating high-power-factor type.
  3. Minimum Starting Temperature: Minus 22 degF.
  4. Normal Ambient Operating Temperature: 104 degF.
  5. Ballast Fuses: One in each ungrounded power supply conductor.

2.4  SPECIALTY EXTERIOR LIGHTING DEVICES

  1. In-ground uplight:
  2. Basis-of-Design: Hydrel M9720-ASP-P38100MSP-120-SP-34SNPT-IHL38-STR
  3. Voltage: 208,277 and120-V ac.
  4. Nominal Dimensions: round, 12-inch diameter.
  5. Lamps: 100W Metal Halide, PAR38, spot distribution.
  6. Lens: Double lens to reduce surface temperature.
  7. Internal Glare Control: Internal Honeycomb Louver
  8. Focusing and Aiming Provisions: 15-degree tilt mechanism.
  9. Trim Ring: Stainless steel.
  10. Bollard:
  11. Basis-of-Design: Landscapeforms “Annapolis”
  12. Voltage: 208,277 and120-V ac.
  13. Nominal Dimensions: Round, 12-inch diameter.
  14. Lighting: Option as standard with the manufacturer.
  15. Construction: Structural steel tube body, aluminum top and base ring.

1)  Finish: Powdercoat in color selected by the Owner.

2.5  MISCELLANEOUS MATERIALS

  1. Concrete: Provide concrete composed of portland cement, coarse and fine aggregate, and water mixed in proportions to attain a 28-day compressive strength of not less than 3000 psi, complying with ASTMC94/C94M.
  2. Nonshrink, Nonmetallic Grout: Factory-packaged, nonstaining, noncorrosive, nongaseous grout complying with ASTMC1107.
  3. Sand: ASTMC33, fine aggregate.
  4. Elastomeric Joint Sealant: Multicomponent urethane joint sealant complying with requirements in Division7 Section "Joint Sealants" for UseNT (nontraffic) and for UseM, G, A, and, as applicable to joint substrates indicated, O joint substrates.

PART 3 - EXECUTION

3.1  FIELD QUALITY CONTROL

  1. Inspect each installed fixture for damage. Replace damaged fixtures and components.
  2. Foundation Installation: Provide foundations to secure bollards.
  3. Illumination Observations: Verify normal operation of lighting units after installing luminaires and energizing circuits with normal power source.

END OF SECTION

Page 2 of 3

Revision Date: 01/21/14 Project & Bid Package

File name: 265616 SPECIALTY EXTERIOR LIGHTING