SECTION 15861 - AIR FILTERS
PART 1 - GENERAL
1.1 SUMMARY
- This Section includes factory-fabricated air-filter devices and media used to remove particulate matter from air for HVAC applications.
1.2 SUBMITTALS
- Product Data: Include dimensions; shipping, installed, and operating weights; required clearances and access; rated flow capacity, including initial and final pressure drop at rated airflow; efficiency and test method; fire classification; furnished specialties; and accessories for each model indicated.
- Shop Drawings: Include plans, elevations, sections, and details to illustrate component assemblies and attachments.
- Show filter rack assembly, dimensions, materials, and methods of assembly of components.
- Include setting drawings, templates, and requirements for installing anchor bolts and anchorages.
- Maintenance Data: For each type of filter and rack to include in maintenance manuals.
1.3 QUALITY ASSURANCE
- Product Options: Drawings indicate size, profiles, and dimensional requirements of air filters and are based on the specific system indicated.
- Comply with NFPA90A and NFPA90B.
- ASHRAE Compliance: Comply with provisions of ASHRAE52.1 for method of testing and rating air-filter units.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
- Manufacturers: Unless otherwise directed by the Owner, provide products by one of the following:
- Air Filters:
- AAF International.
- Airguard Industries, Inc.
- Cambridge.
- Continental Air Filter Div.; NiCon Filter Corp.
- Farr Co.
- Flanders Filters, Inc.
- International Air Filter, Inc.
- Koch Filter Corp.
- Filter Gages:
- Airguard Industries, Inc.
- Dwyer Instruments Inc.
2.2 PRE-FILTERS
- Description: Fiberglass filters with filtering media of nominal 2 inch thickness industrial type glass fiber with an initial resistance of no more than 0.25" WG, rated at a face velocity of 500 FPM. Test filters per ASHRAE Standard 52-76. Average efficiency shall be 25 to 30 percent.
- Framing System: Furnish filtering media manufacturer-furnished galvanized steel, 18 gage holding frames with UL Class 1 rating.
2.3 FILTER GAGES
- Manometer-Type Filter Gage: Molded plastic with epoxy-coated aluminum scale, logarithmic-curve tube gage with integral leveling gage, graduated to read from 0- to 3.0-inch wg and accurate within 3 percent of full scale range.
- Photohelic-Type Filter Gage: Graduated to read from 0- to 3.0-inch wg and accurate within 3 percent of full scale range.
- Accessories: Static-pressure tips, tubing, gage connections, and mounting bracket.
PART 3 - EXECUTION
3.1 INSTALLATION
- Install filter frames according to manufacturer's written instructions.
- Position each filter unit with clearance for normal service and maintenance. Anchor filter holding frames to substrate.
- Install filters in position to prevent passage of unfiltered air.
- Install filter gage static-pressure tips upstream and downstream from filters to measure pressure drop through filter. Mount filter gages on outside of filter housing or filter plenum in an accessible position.
- Coordinate filter installations with duct and air-handling unit installations.
3.2 CLEANING
- After completing system installation and testing, adjusting, and balancing air-handling and air-distribution systems and clean filter housings. Furnish and install a new set of replacement filters.
END OF SECTION
AIR FILTERS 15861 - 2 of 2