SECTION 15720
AIR HANDLING UNITS
Logo
Display hidden notes to specifier by using “Tools”/”Options”/“View”/”Hidden Text”.
** NOTE TO SPECIFIER ** REZNOR; industrial and commercial heating products.
.
This section is based on the products of REZNOR, which is located at:
8155 T&B Blvd.
Mailcode #4C-25
Memphis, TN 38125
Toll Free Tel: (800) 695-1901
Fax: (901) 252-1305
Email:
Web:
{click Here} for additional information.
With over 120 years of experience in gas heating, Reznor manufactures a wide range of industrial and commercial heating products. Founded in 1888 in Pennsylvania, Reznor is a global leader, attained by being at the forefront of HVAC technology, thanks to its innovative solutions for heating, ventilation, cooling and air conditioning incorporated in its extended range of gas fired air heaters, air handling units, condensing units and rooftop units. Today Reznor is a $100 million+ division of Thomas & Betts Corp. and has manufacturing and sales facilities across the world.
PART 1 GENERAL
1.1SECTION INCLUDES
** NOTE TO SPECIFIER ** Delete items below not required for project.
- Heating/cooling makeup air systems.
- Air rotation equipment.
1.2RELATED SECTIONS
** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
- Section 15050 – Basic Mechanical Materials and Methods: Rough-in and service requirements for materials and installation.
- Section 16050 – Basic Electrical Materials and Methods: Rough-in and service requirements for materials and installation.
1.3SUBMITTALS
- Submit under provisions of Section 01300.
- Product Data: Manufacturer's data sheets on each product to be used, including:
- Preparation instructions and recommendations.
- Storage and handling requirements and recommendations.
- Installation methods.
- Shop Drawings: Submit manufacturer/installer's shop drawings, including plans, elevations, sections, and details, indicating location of equipment, operating characteristics, loads, dimensions, tolerances, materials, components, fabrication, fasteners, hardware, finish, options, and accessories.
1.4QUALITY ASSURANCE
- Manufacturer Qualifications: Single source for design, engineering, production, warranty and warranty service.
- Manufacturer shall have at least 20 years experience in manufacturing makeup air equipment.
- Installer Qualifications: Licensed and experienced with mechanical equipment installation, testing and start-up. Familiar with code and AHJ requirements and restrictions.
1.5DELIVERY, STORAGE, AND HANDLING
- Store products in manufacturer's unopened packaging until ready for installation.
1.6PROJECT CONDITIONS
- Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.
PART 2 PRODUCTS
2.1MANUFACTURERS
- Acceptable Manufacturer: REZNOR; 8155 T&B Blvd., Memphis, TN 38125. ASD. Toll Free Tel: (800) 695-1901. Fax: (901) 252-1305. Email: _____. Web:
** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
- Substitutions: Not permitted.
- Requests for substitutions will be considered in accordance with provisions of Section 01600.
** NOTE TO SPECIFIER ** Delete if not required.
2.2HEATING/COOLING MAKEUP AIR
** NOTE TO SPECIFIER ** The MAPS III Series packaged rooftop units are designed to cool and heat high volumes of outside air year round for makeup air and ventilation applications. In addition, MAPSIII can provide significant capacities of space conditioning. All MAPSIII products feature the Reznor IQ digital controller to fully integrate all operation and external sensing into a stand-alone package or through native BacNet, into a building management system.
Models RCB/RDB/RDCB/RDDB/RECB/REDB only. Delete if not required.
- Packaged Rooftop Unit:
** NOTE TO SPECIFIER ** Delete unit not required.
- Unit: High Capacity DX Cooling Makeup Air Units in R410-A Refrigerant:
- Model RCB as manufactured by REZNOR.
** NOTE TO SPECIFIER ** Delete size not required.
- Size: 060. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 078. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 090. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 118. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 136. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 160. Minimum CFM – 2200. Maximum CFM – 4840.
- Size: 186. Minimum CFM – 2200. Maximum CFM – 4840.
- Size: 190. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 200. Minimum CFM – 2200. Maximum CFM – 4840.
- Size: 216. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 298. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 360. Minimum CFM – 6000. Maximum CFM – 12500.
- Size: 410. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 480. Minimum CFM – 6000. Maximum CFM – 13000.
- Size: 600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size: 720. Minimum CFM – 6000. Maximum CFM – 13000.
- Unit: High Outside Air DX Cooling with dedicated Re-Heat Pump Makeup Air Units in R410-A Refrigerant:
- Model RDB as manufactured by REZNOR.
** NOTE TO SPECIFIER ** Delete size not required.
- Size: 084. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 102. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 114. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 142. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 162. Minimum CFM – 1350. Maximum CFM – 3000.
- Size: 184. Minimum CFM – 2000. Maximum CFM – 5000.
- Size: 210. Minimum CFM – 2000. Maximum CFM – 5000.
- Size: 222. Minimum CFM – 2000. Maximum CFM – 5000.
- Size: 224. Minimum CFM – 2000. Maximum CFM – 5000.
- Size: 236. Minimum CFM – 2000. Maximum CFM – 5000.
- Size: 248. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 262. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 272. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 288. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 354. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 370. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 418. Minimum CFM – 6000. Maximum CFM – 13000.
- Size: 444. Minimum CFM – 6000. Maximum CFM – 13000.
- Size: 468. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 482. Minimum CFM – 3600. Maximum CFM – 9000.
- Size: 602. Minimum CFM – 6000. Maximum CFM – 13000.
- Size: 722. Minimum CFM – 6000. Maximum CFM – 13000.
- Size: 842. Minimum CFM – 6000. Maximum CFM – 13000.
- Unit: High Capacity DX Cooling/Gas Heating Makeup Air Units in R410-A Refrigerant:
- Model RDCB as manufactured by REZNOR.
- Units are 82% efficient output MBH.
** NOTE TO SPECIFIER ** Delete size not required.
- Size-Input MBH: 060-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 078-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 090-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 118-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 136-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 060-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 078-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 090-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 118-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 136-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 060-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 078-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 090-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 118-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 136-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 078-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 090-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 118-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 136-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 160-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 186-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 200-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 078-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 090-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 118-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 136-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 160-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 186-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 200-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 190-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 216-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 298-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 410-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 190-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 216-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 298-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 360-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 410-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 480-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 190-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 216-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 298-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 360-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 410-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 480-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 190-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 216-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 298-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 360-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 410-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 480-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 360-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 480-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 360-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 480-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 360-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 480-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 360-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 480-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 360-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 480-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 600-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 720-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Unit: High Capacity DX Cooling with dedicated Re-Heat Pump/Gas Heating Makeup Air Units in R410-A Refrigerant:
- Model RDDB as manufactured by REZNOR.
- Units are 82% efficient output MBH.
** NOTE TO SPECIFIER ** Delete size not required.
- Size-Input MBH: 084-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 102-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 114-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 142-100. Minimum CFM – 1350. Maximum CFM – 1650.
- Size-Input MBH: 084-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 102-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 114-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 142-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 162-150. Minimum CFM – 1350. Maximum CFM – 2500.
- Size-Input MBH: 084-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 102-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 114-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 142-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 162-200. Minimum CFM – 1480. Maximum CFM – 3300.
- Size-Input MBH: 102-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 114-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 142-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 162-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 184-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 210-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 222-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 224-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 236-250. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 102-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 114-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 142-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 162-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 184-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 210-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 222-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 224-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 236-300. Minimum CFM – 2220. Maximum CFM – 4940.
- Size-Input MBH: 248-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 262-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 272-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 288-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 354-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 370-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 468-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 482-400. Minimum CFM – 3000. Maximum CFM – 9000.
- Size-Input MBH: 248-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 262-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 272-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 288-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 354-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 370-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 418-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 468-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 482-500. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 602-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-500. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 248-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 262-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 272-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 288-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 354-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 370-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 418-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 468-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 482-600. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 602-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 248-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 262-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 272-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 288-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 354-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 370-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 418-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 468-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 482-700. Minimum CFM – 3500. Maximum CFM – 9000.
- Size-Input MBH: 602-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-700. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 418-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 602-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-800. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 418-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 602-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-1000. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 418-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 602-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-1200. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 418-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 602-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-1400. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 418-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 444-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 602-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 722-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Size-Input MBH: 842-1600. Minimum CFM – 6000. Maximum CFM – 13000.
- Unit: Packaged Rooftop, Electric Heat, DX Cooling Makeup Air System for Commercial / Industrial Use, R410-A Refrigerant:
- Model RECB as manufactured by REZNOR.
- Units are 100% efficient output MBH.
** NOTE TO SPECIFIER ** Delete size not required.
- Size (Input MBH): 060-10S (34). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 060-15 (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 060-15S (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-15 (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-15S (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-15 (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-15S (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-15 (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-15S (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-15 (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-15S (51). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-15 (51). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-15 (51). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 060-20 (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 060-20S (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-20 (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-20S (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-20 (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-20S (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-20 (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-20S (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-20 (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-20S (68). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-20 (68). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-20 (68). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 200-20 (68). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 060-24S (82). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-24S (82). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-24S (82). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-24S (82). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-24S (82). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 060-25 (85). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-25 (85). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-25 (85). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-25 (85). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-25 (85). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-25 (85). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-25 (85). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 200-25 (85). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 060-30 (102). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-30 (102). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-30 (102). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-30 (102). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-30 (102). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-30 (102). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-30 (102). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 200-30 (102). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 060-35 (120). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-35 (120). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-35 (120). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-35 (120). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-35 (120). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-35 (120). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-35 (120). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 200-35 (120). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 060-39 (133). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 078-39 (133). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-39 (133). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-39 (133). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-39 (133). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-39 (133). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-39 (133). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 190-39 (133). Minimum CFM – 3600. Maximum CFM – 7500.
- Size (Input MBH): 200-39 (133). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 216-39 (133). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 298-39 (133). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 410-39 (133). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 078-50 (171). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-50 (171). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-50 (171). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-50 (171). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-50 (171). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-50 (171). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 190-50 (171). Minimum CFM – 3600. Maximum CFM – 7500.
- Size (Input MBH): 200-50 (171). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 216-50 (171). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 298-50 (171). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 410-50 (171). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 078-60 (205). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-60 (205). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-60 (205). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-60 (205). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-60 (205). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-60 (205). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 190-60 (205). Minimum CFM – 3600. Maximum CFM – 7500.
- Size (Input MBH): 200-60 (205). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 216-60 (205). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 298-60 (205). Minimum CFM – 3600 9000.
- Size (Input MBH): 410-60 (205). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 078-75 (256). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 090-75 (256). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-75 (256). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-75 (256). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-75 (256). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-75 (256). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 200-75 (256). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 190-75 (259). Minimum CFM – 3600. Maximum CFM – 7500.
- Size (Input MBH): 216-75 (259). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 298-75 (259). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 410-75 (259). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 190-88 (300). Minimum CFM – 3600. Maximum CFM – 7500.
- Size (Input MBH): 216-88 (300). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 298-88 (300). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 410-88 (300). Minimum CFM – 3600. Maximum CFM – 9000.
- Size (Input MBH): 090-88 (301). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 118-88 (301). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 136-88 (301). Minimum CFM – 1350. Maximum CFM – 3000.
- Size (Input MBH): 160-88 (301). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 186-88 (301). Minimum CFM – 2000. Maximum CFM – 5000.
- Size (Input MBH): 200-88 (301). Minimum CFM – 2000. Maximum CFM – 5000.
- Unit: Packaged rooftop makeup air unit, DX Cooling/ Dehumidification, Electric Heat, R-410A Refrigerant:
- Units are 100% efficient output MBH.
** NOTE TO SPECIFIER ** Delete size not required.