SECTION 08 33 00

ROLLING COUNTER FIRE DOORS WITH FRAME, M100 FIREGARD™ TUBE MOTOR OPERATION /

SMOKESHIELD® ROLLING COUNTER FIRE DOORS WITH FRAME, M100 FIREGARD™ TUBE MOTOR OPERATION

GENERAL NOTES TO SPECIFIER:

THIS SPECIFICATION SECTION HAS BEEN PREPARED TO ASSIST DESIGN PROFESSIONALS IN THE PREPARATION OF PROJECT OR OFFICE MASTER SPECIFICATIONS. IT FOLLOWS GUIDELINES ESTABLISHED BY THE CONSTRUCTION SPECIFICATIONS INSTITUTE, AND THEREFORE MAY BE USED WITH MOST MASTER SPECIFICATION SYSTEMS WITH MINOR EDITING.

EDIT CAREFULLY TO SUIT PROJECT REQUIREMENTS. MODIFY AS NECESSARY AND DELETE ITEMS THAT ARE NOT APPLICABLE. VERIFY THAT REFERENCED SECTION NUMBERS AND TITLES ARE CORRECT. (NUMBERS AND TITLES REFERENCED ARE BASED ON MASTERFORMATÔ, 2004 EDITION).

THIS SECTION ASSUMES THE PROJECT MANUAL WILL CONTAIN COMPLETE DIVISION 1 DOCUMENTS INCLUDING SECTIONS 01 33 00 SUBMITTAL PROCEDURES, 01 62 00 PRODUCT OPTIONS, 01 25 13 PRODUCT SUBSTITUTION PROCEDURES, 01 66 00 PRODUCT STORAGE AND HANDLING REQUIREMENTS, 01 77 00 CLOSEOUT PROCEDURES, AND 01 78 00 CLOSEOUT SUBMITTALS. IF THE PROJECT MANUAL DOES NOT CONTAIN THESE SECTIONS, ADDITIONAL INFORMATION SHOULD BE INCLUDED UNDER THE APPROPRIATE ARTICLES.

THIS IS AN OPEN PROPRIETARY SPECIFICATION ALLOWING USERS THE OPTION OF APPROVING OTHER MANUFACTURERS WHICH COMPLY WITH THE CRITERIA SPECIFIED HEREIN.

NOTES TO THE SPECIFIER ARE CONTAINED IN BOXES AND SHOULD BE DELETED FROM FINAL COPY.

OPTIONAL ITEMS REQUIRING SELECTION BY THE SPECIFIER ARE ENCLOSED WITHIN BRACKETS, E.G.: [35] [40] [45]. IN CASES WHERE ONE OF THE OPTIONAL ITEMS IS A STANDARD FEATURE OF THE DOOR MODEL, IT IS LISTED IN THE FIRST POSITION. MAKE APPROPRIATE SELECTION AND DELETE OTHERS.

ITEMS REQUIRING ADDITIONAL INFORMATION ARE UNDERLINED, E.G.: ______.

OPTIONAL PARAGRAPHS ARE SEPARATED BY A REDLINED "OR," E.G.:

OR

PART 1 GENERAL

1.1 SUMMARY

A. Section Includes:

1. Electric tube motor operated automatic closing rolling [counter fire doors] [counter fire doors with SmokeShieldÒ leakage rated assembly label] with integral frame [and countertop].

B. Related Sections:

1. 05 50 00 Metal Fabrications. Door opening jamb and head members.

2. 06 10 00 Rough Carpentry. Door opening jamb and head members.

3. 08 31 00 Access Doors and Panels. Access doors.

4. 08 70 00 Hardware. Padlocks. Masterkeyed cylinder.

5. 09 91 00 Painting. Field painting.

6. Division 26. Electrical wiring and conduit for connection to alarm system.

C. Products That May Be Supplied, But Are Not Installed Under This Section:

1. Control station.

2. Key test station.

3. Smoke/heat detectors.

4. Annunciator.

5. Smart Control panel for tube motor.

INCLUDE APPROPRIATE LANGUAGE BELOW, INCLUDING A REFERENCE TO SECTION 01 23 00 ALTERNATES, IF ROLLING COUNTER FIRE DOORS WITH INTEGRAL FRAMES ARE INCLUDED IN ANY ALTERNATES, ADD SECTION 01 23 00 TO 1.1 B. DELETE IF NO ALTERNATES.

D. Alternates:

1. The Cookson Company, Inc.

2. Amarr

3. Clopay

1.2 SYSTEM DESCRIPTION

A. Performance Requirements:

IF LABELED SMOKE PROTECTION IS NOT DESIRED OR REQUIRED, THEN DELETE LINE ITEM “2” BELOW.

1. All rolling counter fire doors shall be constructed in accordance with testing agency requirements and shall bear a [1-1/2 hour] [3/4 hour] rating label.

2. Provide doors with testing agency label for “Leakage Rated Assembly” or “S” label.

a.  Comply with NFPA 105 air leakage requirements.

b.  Pass UL test procedure 1784.

1.3 SUBMITTALS

A. Reference Section 01 33 00 Submittal Procedures; submit the following items:

1. Product Data.

2. Shop Drawings: Include special conditions not detailed in Product Data. Show interface with adjacent work.

3. Quality Assurance/Control Submittals:

a. Provide proof of manufacturer ISO 9001:2008 registration.

b. Provide proof of manufacturer and installer qualifications - see 1.4 below.

c. Provide manufacturer's installation instructions.

4. Closeout Submittals:

a. Operation and Maintenance Manual.

b. Certificate stating that installed materials comply with this specification.

1.4 QUALITY ASSURANCE

A. Qualifications:

1. Manufacturer Qualifications: ISO 9001:2008 registered and a minimum five years experience in producing rolling counter fire doors with integral frames of the type specified.

2. Installer Qualifications: Manufacturer's approval.

1.5 DELIVERY STORAGE AND HANDLING

A. Reference Section 01 66 00 Product Storage and Handling Requirements.

B. Follow manufacturer's instructions.

1.6 WARRANTY

A. Standard Warranty: Two years from date of shipment against defects in material and workmanship.

B. Maintenance: Submit for owner’s consideration and acceptance of a maintenance service agreement for installed products.

PART 2 PRODUCTS

2.1 MANUFACTURER

A. Manufacturer: Cornell Iron Works Enterprise, Crestwood Industrial Park, Mountaintop, PA 18707. Telephone: (800) 233-8366, Fax: (800) 526-0841. Underwriters Laboratories, Inc. (UL), ISO 9001:2008 Registered.

INSERT NAME, ADDRESS, AND PHONE NUMBERS OF LOCAL DISTRIBUTOR BELOW.

1. Distributor:

B. Model: [ERC20] [ERC21]

C. Substitutions: Reference Section 01 25 13 Product Substitution Procedures.

2.2 MATERIALS

A. Curtain:

1. Slats: No. 10 (1-1/4” high by 3/8” deep) interconnected flat-faced slats constructed of 22 gauge, ASTM A 653, Commercial Quality, galvanized steel with tubular steel bottom bar measuring 2” high by 1-1/4” deep.

OR

1. Slats: No. 10 (1-1/4” high by 3/8” deep), interlocked flat-faced slats constructed of 22 gauge AISI type 304 series stainless steel with tubular stainless steel bottom bar measuring 2” high by 1-1/4” deep.

2. Fabricate continuous interlocking slat sections with high strength galvanized steel endlocks riveted to slat ends per UL requirements.

3. Slat Finish:

a. GalvaNexÔ Coating System to include an ASTM A 653 galvanized base coating treated with dual process rinsing agents in preparation of a chemical bonding, [light gray] [tan] [white] baked-on polyester base coat and a [light gray] [tan] [white] baked-on polyester finish coat. The scientific organic material composition and chemical bonding process of GalvaNexÔ produces a superior finish against corrosion and abrasion. GalvaNexÔ components include a limited two year finish warranty.

OR

a.  GalvaNexÔ Coating System and phosphate treatment followed by baked-on polyester powder coat, [color as selected by Architect from manufacturer's standard color range, minimum 32 colors] [custom color as selected by Architect]; minimum 2.5 mils (0.065 mm) cured film thickness; ASTM D-3363 pencil hardness: H or better.

OR

a. Stainless Steel: No. 4 finish.

4. Bottom Bar Finish:

a. Steel: Phosphate treatment followed by baked-on [dark bronze] [gray] [tan] [white] polyester powder coat; minimum 2 mils cured film thickness; ASTM D-3363 pencil hardness: H or better.

OR

a. Steel: ASTM A 123, Grade 85 zinc coating, hot-dip galvanized.

OR

a. Steel: Phosphate treatment followed by baked-on polyester powder coat, [color as selected by Architect from manufacturer's standard color range, minimum 32 colors] [custom color as selected by Architect]; minimum 2.5 mils (0.065 mm) cured film thickness; ASTM D-3363 pencil hardness: H or better.

OR

a. Stainless Steel: No. 4 finish.

B. Head and Jamb Frame:

1. Stainless Steel: 16 gauge stainless steel formed shapes.

2. Finish: Stainless steel: No. 4 finish.

DELETE BELOW IF STAINLESS STEEL COUNTERTOP IS NOT TO BE PROVIDED WITH ROLLING COUNTER FIRE DOOR WITH INTEGRAL FRAME.

C. Countertop: 14 gauge stainless steel formed shape; No. 4 finish.

D. Counterbalance Shaft Assembly:

1. Barrel: Steel pipe capable of supporting curtain load with maximum deflection of 0.03 inches per foot (2.5 mm per meter) of width.

2. Spring Balance: Oil-tempered, heat-treated steel helical torsion spring assembly designed for proper balance of door. Provide wheel for applying and adjusting spring torque.

E. Brackets: Fabricate from reinforced 11 gauge steel plate with bearings at rotating support points to support counterbalance shaft assembly and form end closures for hood.

1. Finish:

a. Steel: Phosphate treatment followed by baked-on [dark bronze] [gray] [tan] [white] polyester powder coat; minimum 2 mils cured film thickness; ASTM D-3363 pencil hardness: H or better.

OR

a. Steel: ASTM A 123, Grade 85 zinc coating, hot-dip galvanized.

OR

a. Stainless Steel: No. 4 finish

F. Hood and operator and governing mechanism covers: [24 gauge galvanized steel] [24 gauge stainless steel] with reinforced top and bottom edges.

1. Finish:

a. GalvaNexÔ Coating System to include an ASTM A 653 galvanized base coating treated with dual process rinsing agents in preparation of a chemical bonding, [light gray] [tan] [white] baked-on polyester base coat and a [light gray] [tan] [white] baked-on polyester finish coat. The scientific organic material composition and chemical bonding process of GalvaNexÔ produces a superior finish against corrosion and abrasion. GalvaNexÔ components include a limited two year finish warranty.

OR

a.  GalvaNexÔ Coating System and phosphate treatment followed by baked-on polyester powder coat, [color as selected by Architect from manufacturer's standard color range] [custom color as selected by Architect]; minimum 2 mils cured film thickness; ASTM D-3363 pencil hardness: H or better.

OR

a. Stainless Steel: No. 4 finish.

INCLUDE THE FOLLOWING SMOKE SEALS WHEN LABELED SMOKE PROTECTION IS REQUIRED - MODEL ERC21 UNITS. CHECK CODE FOR SMOKE DETECTOR AND ALARM SYSTEM TIE-IN REQUIREMENTS. DELETE ITEM “F” IF NOT REQUIRED.

G. Smoke Seals:

1. Bottom Bar: [UL Tested fire astragal seal.] [Combination smoke seal/sensing edge.]

2. Guides and Head: Replaceable, UL Listed, nylon pile smoke seals sealing against fascia side of curtain.

2.3 ACCESSORIES

MOTOR OPERATION LOCKS THE DOOR SHAFT IN PLACE, THUS NO ADDITIONAL LOCKING IS PROVIDED AS STANDARD. ADDITIONAL/OPTIONAL LOCKING METHODS ARE LISTED BELOW. DELETE LOCKING WHEN ADDITIONAL LOCKING IS NOT REQUIRED.

A. Locking

1. Padlockable thumbturn locks on coil side of bottom bar extending lock bar into slots in guides. Provide guide mounted interlock switches to prevent motor operation when locks are engaged.

OR

1. Masterkeyable cylinder operable from [coil] [fascia] [both] side[s] of bottom bar. Provide guide mounted interlock switches to prevent motor operation when locks are engaged.

PLASTIC LAMINATE COUNTERTOPS ARE AVAILABLE IN LIEU OF INTEGRAL STAINLESS STEEL COUNTERTOP. INCLUDE IF DESIRED AND DELETE 2.2-C. 12” (305 mm) MINIMUM COUNTERTOP DEPTH; 36” (914 mm) MAXIMUM COUNTERTOP DEPTH.

B. Countertop: 1 ½ Hour Labeled, 1-5/8” (41 mm) thick, plastic laminate covered, size and configuration made for opening size and wall construction. Color as selected by Architect from standard range of Wilson Art or Formica plastic laminates.

C. Photoelectric Smoke/Heat Detector: UL listed.

2.4 OPERATION

A. M100 Series Tube Motor Operated: Supply Electric Tube Motor Operator - rated for a maximum of 10 cycles per day, cULus recognized, rated (50nm) or (100nm) as recommended by door manufacturer for size and type of door, 115 Volts, 1 Phase, 60 Hertz. Provide complete with electric tube motor, maintenance free electric brake, emergency manual crank hoist and control station(s). Motor shall be protected against overload with an auto-reset thermal sensing device. Operator shall be equipped with an emergency manual crank hoist assembly that safely cuts operator power when engaged. A disconnect chain shall not be required to engage or release the manual crank hoist. Operator shall be capable of 10-14 RPM. Fully adjustable, mechanical internal worm limit switch mechanism shall synchronize the operator with the door.

a.  Automatic closure shall be activated by [a local smoke/fire detector] [a central smoke/fire alarm system].

b.  Doors shall maintain an average closing speed of not more than 12” per second during automatic closing. When automatic closure is activated, electric sensing edge and push button are inoperable.

c.  Doors shall be fail-safe and close upon power failure.

d.  Resetting of spring tension or mechanical dropouts shall not be required. Upon restoration of power and/or clearing of the alarm signal, doors shall immediately reset by opening with the push button.

e.  The electrical contractor shall mount the control station(s) and supply the appropriate disconnect switch, all conduit and wiring per the overhead door wiring instructions.

MOST COMMON CONTROL STATIONS ARE LISTED BELOW; CONSULT CORNELL ARCHITECTURAL DESIGN SERVICES (800) 233-8366 EXT. 4551 FOR OTHER OPTIONS. DELETE IF MANUALLY OPERATED.

1.  Control Station: Flush mounted, Rocker Switch; NEMA 1

OR

1.  Control Station: Flush mounted, Designer Switch; NEMA 1

OR

1.  Control Station: Flush mounted, Toggle Switch; NEMA 1

OR

1. Control Station: Flush mounted, "Open/Close/Stop" push buttons; NEMA 1B.

OR

1. Control Station: Surface mounted, "Open/Close/Stop" push buttons; NEMA 1.

OR

1.  Control Station: Flush mounted, "Open/Close" key switch with "Stop" push button; NEMA 1B.

OPTIONAL WALL MOUNTED KEY CONTROL STATIONS ARE AVAILABLE TO TEST THE DOOR’S AUTOMATIC CLOSING SYSTEM. DELETE IF NOT DESIRED.

2. Key Test Station: Flush mounted, NEMA 1.

OR

2. Key Test Station: Surface mounted, NEMA 4.

CONSTANT PRESSURE CLOSE OPERATION IS STANDARD AND RECOMMENDED FOR M100 TUBE MOTOR OPERATED COUNTER FIRE DOOR UNITS. Select the operator function below when constant pressure close operation is acceptable. The motor control station(s) must be mounted within visible sight of the entire door opening and pressure must be maintained on “close” for the duration of each close cycle. AN ELECTRIC SENSING EDGE IS REQUIRED TO ENABLE MOMENTARY CONTACT CLOSE OPERATION. PROVIDE DESIRED FUNCTIONALITY FROM “B” BELOW.

B. Provide operator to function with constant pressure close operation.

OR

FOR MOMENTARY CONTACT CLOSE OPERATION PER UL325-2010, MOTOR OPERATED DOORS MUST BE PROVIDED WITH A CONNECTED AND PROPERLY FUNCTIONING PRIMARY ENTRAPMENT PROTECTION DEVICE OR THE SYSTEM WILL REVERT TO CONSTANT PRESSURE CLOSE OPERATION.

■ SELECT A PRIMARY ENTRAPMENT PROTECTION DEVICE FROM 2.4-B-1 BELOW TO ENABLE MOMENTARY CONTACT CLOSE OPERATION, INCLUDING THE CONNECTION OF RADIO CONTROLS, INDUCTION LOOPS, TIMER TO CLOSE, ETC.

A CONTINUOUSLY MONITORED WIRELESS SENSING EDGE OR STAND ALONE 2-WIRE E.L.R. ELECTRIC SENSING EDGE IS RECOMMENDED TO MEET THE UL325-2010 REQUIREMENT FOR ENTRAPMENT PROTECTION WHILE ALSO PROVIDING PROPERTY PROTECTION. A SENSING EDGE WILL DETECT OBJECTS PROJECTING THROUGH THE OPENING ABOVE 6” FROM THE COUNTER / FLOOR THAT PHOTO EYES MAY NOT DETECT.

B. Entrapment Protection: Provide the following primary entrapment device to enable momentary contact close operation.

1. Provide a continuously monitored, wireless sensing/weather edge seal extending full width of door bottom bar. Contact before door fully closes shall cause door to immediately stop downward travel and reverse direction to the fully opened position.

OR

1. Provide a 2-wire electric sensing/weather edge seal extending full width of door bottom bar. Contact before door fully closes shall cause door to immediately stop downward travel and reverse direction to the fully opened position. Provide a [retracting safety cord and reel] [self-coiling cable] connection to control circuit.

OR

1. Provide NEMA 4X photo eye sensors consisting of a transmitter and receiver that are to be mounted within 6” (152.4 mm) of the bottom of the door, projecting an IR beam across the entire width of the door. Interruption of beam before door fully closes shall cause door to immediately stop downward travel and reverse direction to the fully opened position. Electrical contractor to provide low voltage wiring from the transmitter and receiver to the door operator.