SECTION 22 14 53
RAINWATER AND STORMWATER HARVESTING AND RECLAMATION SYSTEMS
Display hidden notes to specifier. (Don't know how? Click Here)
Copyright 2018 - 2018 ARCAT, Inc. - All rights reserved
** NOTE TO SPECIFIER ** Rainwater Management; Rainwater management. This section is based on the products of Rainwater Management, which is located at:
1260 West Riverside Dr.
Salem, VA 24153
Toll Free Tel: 866-653-8837
Tel: 540-375-6750
Fax: 540-375-6751
Email:request info ()
Web:
[Click Here] for additional information.
Rainwater Management Solutions, based in Salem, VA, is an industry-leading supplier, system integrator, and professional services firm, specializing in turnkey solutions for rainwater and stormwater management. Our knowledgeable staff has a combined experience of over 60 years in the rainwater harvesting business. RMS provides complete rainwater harvesting systems and solutions for residential, commercial, industrial, and agricultural projects. The firm provides professional design and consulting services to its clients, which include development, engineering, and architectural firms seeking specialized rainwater and stormwater management system design capabilities. Many of our clients are focused on earning LEED points. RMS provides both residential and commercial solutions and has worked on small to very large scale projects. RMS is the exclusive dealer of WISY filters within North America.
Water conservation and management is increasingly becoming a worldwide survival issue due to accelerating water shortages, property development and population growth, aging infrastructures, growing agricultural demands, a general warming trend, and the ever-increasing cost of and demand for natural water resources.
RMS brings a commonsense, cost-effective approach to addressing the escalating issue of water conservation and management through its innovative rainwater harvesting system designs and its experienced, knowledgeable staff. The expertise of the staff encompasses industries directly impacted by water management issues.
1 GENERAL
1.1 SECTION INCLUDES
** NOTE TO SPECIFIER ** Delete, add items below as required for the Project.
1.1.1 Rain harvesting delivery systems.
1.1.1.1 Above ground.
1.1.1.2 Below ground.
1.1.2 Pre-filtration systems.
1.1.2.1 Above ground.
1.1.2.2 Below ground.
1.1.3 Pre-filtration system components.
1.1.4 Post storage filtration and purifications systems.
1.1.5 Post storage filtration and purification components.
1.1.6 Delivery pumps and accessories.
1.1.7 Domestic back-up components.
1.1.8 Rain water controllers.
1.1.9 Storage tanks.
1.1.9.1 Polyethylene above ground,
1.1.9.2 Corrugated metal above ground,
1.1.9.3 Red cedar above ground
1.1.9.4 Below ground.
1.1.9.5 Polyethylene below ground.
1.1.9.6 Fiberglass below ground.
1.1.9.7 Modular below-ground.
1.2 RELATED SECTIONS
** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
1.2.1 Division 15 - Gray water plumbing piping systems.
1.2.2 Section 22 14 00 - Facility Storm Drainage.
1.3 REFERENCES
** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.
1.3.1 American National Standards Institute (ANSI):
1.3.1.1 ANSI 78: Stormwater Harvesting System Design for Direct End-Use Applications.
1.4 SYSTEM DESCRIPTION
1.4.1 Design Intent: Custom and "off-the-shelf" rainwater harvesting systems consisting of manufactured components integrated into an automated system. The system shall collect rainwater from a roof via drains, downspouts and conveyance piping; and convey rainwater through, self-cleaning, gravity fed pre-filters. Filtered rainwater is then stored in a storage tank. Water is drawn from the storage tank and pumped through a packaged pumping system to an irrigation or end use plumbing system. The pumping package is designed to provide water at the desired design point on an on-demand basis.
1.4.2 Design Requirements: Filter, store, and distribute harvested rainwater per ANSI 78.
1.4.3 Water Disinfection Methods: May include sediment filtration, ultraviolet treatment, chlorine injection, carbon filtration, or a combination thereof.
1.5 SUBMITTALS
1.5.1 Submit under provisions of Section 01 30 00 - Administrative Requirements.
1.5.2 Product Data: For system components; include dimensions, capacities, operating characteristics, utility connections, and accessories.
1.5.2.1 Preparation instructions and recommendations.
1.5.2.2 Storage and handling requirements and recommendations.
1.5.2.3 Installation methods.
1.5.3 Shop Drawings: Include system layout, components, accessories, details of construction, and relationship with adjacent construction.
1.5.4 Manufacturer's Certificates: Certify products to meet or exceed specified requirements.
1.5.5 Closeout Submittals: Operation and maintenance data.
1.5.5.1 Provide instructions on operation, calibration, troubleshooting, and servicing equipment.
1.5.5.2 Include layout drawings, parts lists, and component manufacturer's product data.
1.6 QUALITY ASSURANCE
1.6.1 System Integrator: Rainwater Management Solutions Incorporated.
1.6.2 Manufacturer Qualifications:
1.6.2.1 Minimum 10 years experience in work of this Section.
1.6.2.2 Successful completion of minimum of 10 previous projects of similar scope and complexity.
1.6.3 Installer Qualifications:
1.6.3.1 Minimum 3 years experience in work of this Section.
1.6.3.2 Successful completion of minimum of 3 previous projects of similar scope and complexity.
1.6.3.3 Maintain factory trained technicians on staff to provide field service and warranty work.
1.7 DELIVERY, STORAGE, AND HANDLING
1.7.1 Do not deliver system components until time needed for installation, and after proper protection can be provided.
1.7.2 Protect components from damage and corrosion.
1.7.3 Leave protective coverings in place until just prior to installation.
1.8 PROJECT CONDITIONS
1.8.1 Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.
1.9 WARRANTY
1.9.1 Warranty: Submit manufacturer's standard limited warranty.
2 PRODUCTS
2.1 MANUFACTURERS
2.1.1 Acceptable Manufacturer: Rainwater Management, which is located at: 1260 West Riverside Dr.; Salem, VA 24153; Toll Free Tel: 866-653-8837; Tel: 540-375-6750; Fax: 540-375-6751; Email:request info (); Web:
** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 01 section on product options and substitutions.
2.1.2 Substitutions: Not permitted.
2.1.3 Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.
** NOTE TO SPECIFIER ** Rainwater pre-filtration, storage, and pump systems. Delete Article if specifying systems or system components separately.
2.2 RAINWATER HARVESTING AND DELIVERY SYSTEMS
2.2.1 Performance Requirements: Size systems to accommodate the rain harvesting capacity required for the given structure and structure location and meeting the design requirements.
** NOTE TO SPECIFIER ** Delete paragraph not required. Either above or below ground systems.
2.2.2 Above Ground Systems:
** NOTE TO SPECIFIER ** Delete tank and pump systems not required.
2.2.2.1 Tank with Submersible Pump:
2.2.2.1.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.1.2 Vortex filter - WISY.
2.2.2.1.3 First flush and excess water outlet.
2.2.2.1.4 Low water cut off float switch for pump protection (N/O).
2.2.2.1.5 Stainless steel smoothing inlet.
2.2.2.1.6 Floating stainless steel suction filter.
2.2.2.1.7 Submersible feed pump with check valve.
2.2.2.1.8 Overflow.
2.2.2.1.9 Pressure tank with tank tee.
2.2.2.1.10 Check valve.
2.2.2.2 Tank with Suction / Booster Pump:
2.2.2.2.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.2.2 Vortex filter - WISY.
2.2.2.2.3 First flush and excess water outlet.
2.2.2.2.4 Low water cut off float switch for pump protection (N/O).
2.2.2.2.5 Stainless steel smoothing inlet.
2.2.2.2.6 Floating stainless steel suction filter.
2.2.2.2.7 Check valve.
2.2.2.2.8 Overflow.
2.2.2.2.9 Booster jet pump.
2.2.2.2.10 Pressure tank with tank tee.
2.2.2.3 Tank with Submersible Pump and Purification Kit:
2.2.2.3.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.3.2 Vortex filter - WISY.
2.2.2.3.3 First flush and excess water outlet.
2.2.2.3.4 Low water cut off float switch for pump protection (N/O).
2.2.2.3.5 Stainless steel smoothing inlet.
2.2.2.3.6 Floating stainless steel suction filter.
2.2.2.3.7 Submersible feed pump with check valve.
2.2.2.3.8 Overflow.
2.2.2.3.9 Sediment filter.
2.2.2.3.10 Carbon filter.
2.2.2.3.11 UV light.
2.2.2.3.12 Pressure tank with tank tee.
2.2.2.3.13 Check valve.
2.2.2.4 Tank with Suction, Booster Pump and Purification Kit:
2.2.2.4.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.4.2 Vortex filter - WISY.
2.2.2.4.3 First flush and excess water outlet.
2.2.2.4.4 Low water cut off float switch for pump protection (N/O).
2.2.2.4.5 Stainless steel smoothing inlet.
2.2.2.4.6 Floating stainless steel suction filter.
2.2.2.4.7 Submersible feed pump with check valve.
2.2.2.4.8 Overflow.
2.2.2.4.9 Suction, booster pump.
2.2.2.4.10 Pressure tank with tank tee.
2.2.2.4.11 Water purification system.
2.2.2.5 Tank with Submersible Pump and Pressure Difference Backup:
2.2.2.5.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.5.2 Vortex filter - WISY.
2.2.2.5.3 First flush and excess water outlet.
2.2.2.5.4 Low water cut off float switch for pump protection (N/O).
2.2.2.5.5 Stainless steel smoothing inlet.
2.2.2.5.6 Floating stainless steel suction filter.
2.2.2.5.7 Submersible feed pump with check valve.
2.2.2.5.8 Overflow.
2.2.2.5.9 Pressure tank with tank tee.
2.2.2.5.10 Check valve.
2.2.2.5.11 Pressure gauge.
2.2.2.5.12 Pressure regulator valve.
2.2.2.5.13 RPZ - Backflow prevention device.
2.2.2.5.14 Domestic water supply.
2.2.2.6 Tank with Suction, Booster Pump and Pressure Difference Backup:
2.2.2.6.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.6.2 Vortex filter - WISY.
2.2.2.6.3 First flush and excess water outlet.
2.2.2.6.4 Low water cut off float switch for pump protection (N/O).
2.2.2.6.5 Stainless steel smoothing inlet.
2.2.2.6.6 Floating stainless steel suction filter.
2.2.2.6.7 Check valve.
2.2.2.6.8 Overflow.
2.2.2.6.9 Suction, booster pump.
2.2.2.6.10 Pressure tank with tank tee.
2.2.2.6.11 Pressure gauge.
2.2.2.6.12 Pressure regulator valve.
2.2.2.6.13 RPZ - Backflow prevention device.
2.2.2.6.14 Domestic water supply.
2.2.2.7 Tank with Submersible Pump, Purification Kit and Pressure Difference Backup:
2.2.2.7.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.7.2 Vortex filter - WISY.
2.2.2.7.3 First flush and excess water outlet.
2.2.2.7.4 Low water cut off float switch for pump protection (N/O).
2.2.2.7.5 Stainless steel smoothing inlet.
2.2.2.7.6 Floating stainless steel suction filter.
2.2.2.7.7 Submersible feed pump with check valve.
2.2.2.7.8 Overflow.
2.2.2.7.9 Check valve.
2.2.2.7.10 Sediment filter.
2.2.2.7.11 Carbon filter.
2.2.2.7.12 UV light.
2.2.2.7.13 Pressure tank with tank tee.
2.2.2.7.14 Pressure gauge.
2.2.2.7.15 Pressure regulator valve.
2.2.2.7.16 RPZ - Backflow prevention device.
2.2.2.7.17 Domestic water supply.
2.2.2.8 Tank with Suction, Booster Pump, Purification Kit and Pressure Difference Backup:
2.2.2.8.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.2.8.2 Vortex filter - WISY.
2.2.2.8.3 First flush and excess water outlet.
2.2.2.8.4 Low water cut off float switch for pump protection (N/O).
2.2.2.8.5 Stainless steel smoothing inlet.
2.2.2.8.6 Floating stainless steel suction filter.
2.2.2.8.7 Check valve.
2.2.2.8.8 Overflow.
2.2.2.8.9 Suction, booster Pump.
2.2.2.8.10 Sediment filter.
2.2.2.8.11 Carbon filter.
2.2.2.8.12 UV light.
2.2.2.8.13 Pressure tank with tank tee.
2.2.2.8.14 Pressure gauge.
2.2.2.8.15 Pressure regulator valve.
2.2.2.8.16 RPZ - Backflow prevention device.
2.2.2.8.17 Domestic water supply.
2.2.3 Below Ground Systems:
** NOTE TO SPECIFIER ** Delete tank and pump systems not required.
2.2.3.1 Tank with Submersible Pump:
2.2.3.1.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.3.1.2 Vortex filter - WISY.
2.2.3.1.3 First flush and excess water outlet.
2.2.3.1.4 Stainless steel smoothing inlet.
2.2.3.1.5 Floating stainless steel suction filter.
2.2.3.1.6 Submersible feed pump with check valve.
2.2.3.1.7 Low water cut off float switch for pump protection (N/O).
2.2.3.1.8 Multifunctional overflow device - WISY.
2.2.3.1.9 Overflow.
2.2.3.1.10 Pressure tank with tank tee.
2.2.3.1.11 Check valve.
2.2.3.1.12 Domestic water supply.
2.2.3.2 Tank with Booster, Suction Pump:
2.2.3.2.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.3.2.2 Vortex filter - WISY.
2.2.3.2.3 First flush and excess water outlet.
2.2.3.2.4 Stainless steel smoothing inlet.
2.2.3.2.5 Low water float switch for pump protection (N/O).
2.2.3.2.6 Floating stainless steel suction filter.
2.2.3.2.7 Multifunctional overflow device - WISY.
2.2.3.2.8 Overflow.
2.2.3.2.9 Booster, jet pump.
2.2.3.2.10 Check valve.
2.2.3.2.11 Pressure tank with tank tee.
2.2.3.2.12 Domestic water supply.
2.2.3.3 Tank with Submersible Pump and Purification Kit.
2.2.3.3.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.3.3.2 Vortex filter - WISY.
2.2.3.3.3 First flush and excess water outlet.
2.2.3.3.4 Stainless steel smoothing inlet.
2.2.3.3.5 Floating stainless steel suction filter.
2.2.3.3.6 Submersible feed pump with check valve.
2.2.3.3.7 Low water cut off float switch for pump protection (N/O).
2.2.3.3.8 Multifunctional overflow device - WISY.
2.2.3.3.9 Overflow.
2.2.3.3.10 Sediment filter.
2.2.3.3.11 Carbon filter.
2.2.3.3.12 UV light.
2.2.3.3.13 Pressure tank with tank tee.
2.2.3.3.14 Check valve.
2.2.3.3.15 Domestic water supply.
2.2.3.4 Tank with Booster, Suction Pump and Purification Kit:
2.2.3.4.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.3.4.2 Vortex filter - WISY.
2.2.3.4.3 First flush and excess water outlet.
2.2.3.4.4 Stainless steel smoothing inlet.
2.2.3.4.5 Floating stainless steel suction filter.
2.2.3.4.6 Submersible feed pump with check valve.
2.2.3.4.7 Low water cut off float switch for pump protection (N/O).
2.2.3.4.8 Multifunctional overflow device - WISY.
2.2.3.4.9 Overflow.
2.2.3.4.10 Sediment filter.
2.2.3.4.11 Carbon filter.
2.2.3.4.12 UV light.
2.2.3.4.13 Pressure tank with tank tee.
2.2.3.4.14 Check valve.
2.2.3.4.15 Domestic water supply.
2.2.3.5 Below Ground Tank with Submersible Pump and Normally Closed Solenoid Valve for Municipal Backup:
2.2.3.5.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.3.5.2 Vortex filter - WISY.
2.2.3.5.3 First flush and excess water outlet.
2.2.3.5.4 Stainless steel smoothing inlet.
2.2.3.5.5 Floating stainless steel suction filter.
2.2.3.5.6 Submersible feed pump with check valve.
2.2.3.5.7 Low water cut off float switch for pump protection (N/O).
2.2.3.5.8 Overflow, multi-siphon, flap valve.
2.2.3.5.9 Domestic water supply.
2.2.3.5.10 RPZ backflow prevention device.
2.2.3.5.11 Normally closed float switch.
2.2.3.5.12 Normally closed solenoid valve.
2.2.3.5.13 Pressure tank with tank tee.
2.2.3.5.14 Spring check valve.
2.2.3.6 Tank with Submersible Pump and Pressure Difference Municipal Backup with Check Valve:
2.2.3.6.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.3.6.2 Vortex filter - WISY.
2.2.3.6.3 First flush and excess water outlet.
2.2.3.6.4 Stainless steel smoothing inlet.
2.2.3.6.5 Floating stainless steel suction filter.
2.2.3.6.6 Submersible feed pump with check valve.
2.2.3.6.7 Low water cut off float switch for pump protection (N/O).
2.2.3.6.8 Multifunctional overflow device - WISY.
2.2.3.6.9 Overflow.
2.2.3.6.10 Pressure tank with tank tee.
2.2.3.6.11 Check valve.
2.2.3.6.12 Pressure gauge.
2.2.3.6.13 Pressure regulator valve.
2.2.3.6.14 RPZ backflow prevention device.
2.2.3.6.15 Domestic water supply.
2.2.3.7 Tandem Tanks with Submersible Pump and Purification:
2.2.3.7.1 Rainwater Collection Point: Roof drains, gutters, etc.
2.2.3.7.2 Vortex filter - WISY.
2.2.3.7.3 First flush and excess water outlet.
2.2.3.7.4 Stainless steel smoothing inlet.
2.2.3.7.5 Tank equalization line.
2.2.3.7.6 Floating stainless steel suction filter.
2.2.3.7.7 Submersible feed pump with check valve.
2.2.3.7.8 Low water cut off float switch for pump protection (N/O).
2.2.3.7.9 Overflow flows from tank 1 to tank 2, and flows from tank 2 to grade or storm water system.
** NOTE TO SPECIFIER ** Use this article to define a pre-filtration system for rain harvesting. Delete article if not required.
2.3 PRE-FILTRATION SYSTEMS
** NOTE TO SPECIFIER ** Delete paragraph not required. Either above or below ground system.
2.3.1 Above Ground: Above ground tanks not included.
** NOTE TO SPECIFIER ** Delete pre-filtration systems not required.
2.3.1.1 Roof Collection Package: For 1,100 sq ft (102.2 sq m).
2.3.1.1.1 Garden Downspout Filter - WISY.
2.3.1.1.2 Downspout converter kit.
2.3.1.1.3 Hose and tension ring.
2.3.1.1.4 Mounting clip and screw.
2.3.1.1.5 Pump: Grundfos SBA 3-45 Submersible Package.
2.3.1.1.6 Bulkhead and schedule 40 PVC fittings.
2.3.1.2 Roof Collection Package: For 2,100 sq ft (195.1 sq m).
2.3.1.2.1 WFF 100 Vortex Fine Filter - WISY.
2.3.1.2.2 Extension tube.
2.3.1.2.3 Wall mount bracket.
2.3.1.2.4 Smoothing inlet.
2.3.1.2.5 Grundfos SBA 3-45 submersible pump package.
2.3.1.2.6 Bulkhead and schedule 40 PVC fittings.
2.3.1.3 Roof Collection Package: 5,500 sq ft (511 sq m).
2.3.1.3.1 WFF 150 Vortex Fine Filter - WISY.
2.3.1.3.2 Extension tube.
2.3.1.3.3 Wall mount bracket.
2.3.1.3.4 Smoothing inlet.
2.3.1.3.5 Grundfos SBA 3-45 submersible pump package.
2.3.1.3.6 Bulkhead and schedule 40 PVC fittings.
2.3.1.4 RMS 500-Gallon (1893 L) Package: ABG-5.
2.3.1.4.1 Roof Collection Area: 1,600 sq ft (148.6 sq m).
2.3.1.4.2 Recommended Usage: 20 gallons (75.7 L) per day.
2.3.1.4.3 Delivered pre-plumbed, ready to install for above ground rainwater harvesting.
2.3.1.4.3.1 Tank: 500 Gallon (1893 L) Rotoplas Tank.
2.3.1.4.3.1.1 Diameter x Height: 48 x 73 in (1219 x 1854 mm).
2.3.1.4.3.2 Poly Downspout Filter with adapter kit, hose and tension ring.
2.3.1.4.3.3 PVC U-shaped Calming Inlet (pre-plumbed in tank by RMS).
2.3.1.4.3.4 PBC P-Trap (pre-plumbed in tank by RMS).
2.3.1.4.3.5 Floating Filter: 1-1/4 in (31.5 mm) with 7 ft (2134 mm) of food-grade suction hose.
2.3.1.4.3.6 Pump: 1 HP (0.75 kW) (0.75 kW) Grundfos MQ; 115V/1/60Hz, with protection cover.
2.3.1.4.3.7 Check Valve: 1 in (25 mm); quantity of two.
2.3.1.4.3.8 Tank gaskets, bulkheads, and fittings.
** NOTE TO SPECIFIER ** Delete options not required.
2.3.1.4.4 Optional Additions:
2.3.1.4.4.1 Blind Insert for winterization - WISY.
2.3.1.4.4.2 Liquidator to gauge the water in the tank.
2.3.1.5 RMS 1000-Gallon (3785 L) Package: ABG-10.
2.3.1.5.1 Roof Collection Areas: 2,100 sq ft (195.1 sq m).
2.3.1.5.2 Recommended Usage: 75 gal (284.9 L) per day.
2.3.1.5.3 Delivered pre-plumbed and ready to install for above ground rainwater harvesting.
2.3.1.5.3.1 Tank: 1,000-Gallon (3785 L) Rotoplas Tank.
2.3.1.5.3.1.1 Diameter x Height: 60 x 89 in (1524 x 2261 mm).
2.3.1.5.3.2 Vortex Filter - WISY: WFF100 with wall-mount bracket and flexible rubber couplings.
2.3.1.5.3.3 Smoothing Inlet: 4 in (102 mm).
2.3.1.5.3.4 Overflow Device: 4 in (102 mm).
2.3.1.5.3.5 Floating Filter: 1-1/4 in (31.5 mm) with 7 ft (2134 mm) of food-grade suction hose.
2.3.1.5.3.6 Pump: 1 HP (0.75 kW) Grundfos MQ; 115 V, 1 Ph, 60 Hz, with protection cover.
2.3.1.5.3.7 Check Valve: 1 in (25 mm); quantity of two.
2.3.1.5.3.8 Tank gaskets, bulkheads, and fittings.
** NOTE TO SPECIFIER ** Delete options not required.
2.3.1.5.4 Optional Additions:
2.3.1.5.4.1 Blind insert for winterization - WISY.
2.3.1.5.4.2 Extension tube for WFF100 / WFF150 (helpful if installed indoors).
2.3.1.5.4.3 Sieve basket.
2.3.1.5.4.4 Liquidator to gauge the water in the tank.
2.3.1.5.4.4.1 RMS 1600-Gallon (6057 L) Package: ABG-16.
2.3.1.5.4.4.1.1 Roof Collection Area: 5,500 sq ft (511 sq m).
2.3.1.5.4.4.1.2 Recommended Usage: 100 gal (378.5 L) per day.
2.3.1.5.4.4.1.3 Delivered pre-plumbed and ready to install for above ground rainwater harvesting.
2.3.1.5.4.4.1.3.1 Tank: 1,600-Gallon (6057 L) Rotoplas Tank.
2.3.1.5.4.4.2 Diameter x Height: 86 x 72 in (325 x 273 mm).
2.3.1.5.4.4.2.1.1 WISY Vortex Filter: WFF150 with mounting bracket and flexible rubber couplings.
2.3.1.5.4.4.2.1.2 Smoothing Inlet: 4 in (102 mm).
2.3.1.5.4.4.2.1.3 Overflow Device: 4 in (102 mm).
2.3.1.5.4.4.2.1.4 Floating Filter: 1-1/4 in (31.5 mm) with 7 ft (2134 mm) of food-grade suction hose.
2.3.1.5.4.4.2.1.5 Pump: 1 HP (0.75 kW) Grundfos MQ; 115 V, 1 Ph, 60 Hz, with protection cover.
2.3.1.5.4.4.2.1.6 Check Valve: 1 in (25 mm); quantity of two.
2.3.1.5.4.4.2.1.7 Tank gaskets, bulkheads, and fittings.
** NOTE TO SPECIFIER ** Delete options not required.
2.3.1.5.5 Optional Additions:
2.3.1.5.5.1.1.1.1 WISY Blind Insert for winterization.
2.3.1.5.5.1.1.1.2 Extension tube for WFF100/WFF150 (helpful if installed indoors).
2.3.1.5.5.1.1.1.3 Sieve basket.
2.3.1.5.5.1.1.1.4 Liquidator to gauge the water in the tank.
2.3.1.6 RMS 2500-Gallon (9463.5 L) Package: ABG-25.
2.3.1.6.1 Roof Collection Area: 5,500 sq ft (511 sq m).
2.3.1.6.2 Recommended Usage: 100 gal (378.5 L) per day.
2.3.1.6.3 Delivered pre-plumbed and ready to install for your rainwater above ground harvesting.
2.3.1.6.3.1 Tank: 2,500-Gallon (9463.5 L) Rotoplas Tank.
2.3.1.6.3.1.1 Diameter x Height: 90 x 96 in (2286 x 2438 mm).