Information as per format given below is to be furnished by the tenderer in techno-commercial bid failing which offer will not be considered
Sl. No. / Tender specification /Compliance (Yes/No)
/Tenderer’s specification
/Remarks
UPS RATING :60KVA (3 x 20KVA)Type: Rack mounted UPS
UPS shall utilize rack mounted redundant scalable array architecture
UPS system shall power train shall be comprised of hot swappable/ user replaceable 20KVA power modules, which shall operate in parallel.
Each 20kVA power module contains a full rated input rectifier / boost converter, full rated output inverter, and battery charging circuit.
The system shall also comprise of a user-replaceable continuous duty hot swappable bypass static switch module, hot swappable / user replaceable battery modules, redundant control modules, redundant logic power supplies, and LCD interface display.
All of the above system components shall be housed in a standard 600mm wide, 1070mm deep, and 1991mm high equipment rack (tentative measurements).
The UPS shall be designed to permit ready access to modules and assemblies. The placement of parts, test points and terminals shall be such that they are accessible for circuit checking, adjustment and maintenance without removal of any adjustment module or assembly.
All power semiconductors in the module shall be protected by fast acting fuses so that failure of any one power semiconductor will not cause cascading failures.
Each fuse shall preferably be provided with a blown fuse indicator on the control panel. The UPS module shall not incur permanent damage to itself and the connected load under all predictable types of failure conditions within itself and the connected load.
UPS shall be designed to interface and operate with DG set to maintain UPS supply in case of utility supply failure without any distortion on DG supply or hunting or de-rating DG set.
Qty : 2 sets
(each set consist of UPS unit and battery bank )
Tenderers shall supply the department approved make items only. The approved makes for Modular UPS are: Emerson, Socomec, Riello AROS, APC (Schneider), Numeric.
Make of UPS
Series
Model no
Input Power at rated load, power factor, Output Power
Input rated voltage: 415V three phase 4wire AC system
Input voltage range: 340 – 477V at 100% load and 200-477V at 50% load
Rated frequency: 50HZ and frequency range: 40-70HZ (autosensing)
Input power factor: >0.99 lag at load greater than 25%
Input current distortion without filters: < 5% at 100% load
Soft start: Shall be linear from 0 – 100% input current and shall not exhibit not exhibit inrush. This shall take place over a 10 sec time period.
Maximum input current at rated load & power factor
Maximum input current with battery charging(line current)
AC-AC efficiency for nonlinear loads
Output nominal voltage: 415v three phase 4wire AC system
Output voltage regulation:
± 1% for 100% linear load
± 3% for 100% nonlinear load
Output frequency regulation:
50HZ when bypass input not present
Frequency synchronized to bypass when input frequency between 48.5 – 51.5HZ with regulation of ±1%
Voltage transient response: ±5% max for 100% load step
Voltage transient recovery : within less than 5msec.
Output voltage distortion factor:
2% with100% linear load,
<5% with 100% non-linear load
Output Power factor at full rated load : 0.9lag
Output wave form : sinusoidal
Overload capacity:
150% for 60 sec
Overload capacity
125% for 10min
Overload capacity:
150% for 5 sec
when mains failure and UPS is in battery mode
Maximum crest factor 3
Walk in time
Converter output (DC Voltage) and ripple on DC bus
Inverter Technology
Bypass Static Switch: rated for 60KVA
Bypass Static Switch: Rated voltage 415V
Bypass Static Switch: Voltage tolerance ±15%
Bypass Static Switch: Rated frequency 50Hz
Bypass Static Switch: Frequency tolerance ± 10%
Bypass Static Switch: Overload capacity
125% continuous
150% 1min
1000% 100 msec
Bypass Static Switch change over time:
From inverter to bypass
From bypass to inverter
in synchronization mode
in non-synchronization mode
Metering provided: Provide detailed write-up
Indications provided: Provide detailed write-up
Protection provided: Provide detailed write-up:
Thermostats shall be provided to monitor the temperature of UPS system and the batteries. The UPS system shall automatically transfer the load to the bypass source via static bypass switch without power interruption in case of over temperature alarm is detected. The threshold of the over temperature alarm shall be configurable and the alarm shall be configurable to disable/ enable.
Event logging at front Panel: Provide detailed write-up
Cooling method adopted / type of cooling
Total heat dissipation in BTU:
At 100% load
At 50% load
Environnemental protection 40°C, 95%RH
Audible Noise in dbA at 1 Mtr.
<63 with 50% load
<65 with 100%
Degree of Ingress protection
IP 20 or better
Powder Coating / Painting details
UPS Testing Standard
Conformity Standard
-Design
-Safety
-EMC
-CE Marking
-ISO Certificate
Batteries:
Type: VRLA of AGM or gel type modular in construction and shall be hot swappable user replaceable
Service life of battery: not less than 5years
Each battery module shall be monitored for voltage and temperature
Battery charging current max.
Rectifier / Charger Technology
IGBT based with temperature compensated charger circuitry
Battery Management system
Enclose detailed write up
No of battery racks/modules designed for 20 min backup.
Battery sizing calculations sheet
Furnish the details
Battery bank voltage as designed required
Battery capacity in AH for suitable discharge rate:
Discharge rate opted:
Each Battery voltage:
No of batteries:
Battery make:
The overall efficiency of the UPS system, output to input, shall not be less than 90% for UPS at 50% rated load
Efficiency AC/AC (overall)
a)At full load
b)At 75% load
c)At 50% load
d)At 25% load
Dimension of UPS with rack
Width (in mm.)
Depth (in mm.)
Height (in mm.)
Dimension of Battery Rack
Width (in mm.)
Depth (in mm.)
Height (in mm.)
Maximum heat loss
Whether air conditioning is required for battery and UPS? If so, recommended AC system
MTBF
MTTR
Special features of UPS
Enclose the details
Details of Maintenance bypass switch provided
Provide details on Remote monitoring
Provide the list of tests offered-
1)At factory:
2)At site:
Validity: Offer shall be valid for 120days from the date of opening of technical bid
Place of delivery and installation including packing, forwarding freight charges:
1)One set at ISTRAC, BIAK-1 station, Indonesia.
2)One set at ISTRAC, BIAK-2 station, Indonesia.
Warranty: The fully assembled UPS system with battery banks shall be warranted for a period of 60months (5 years) from the date of commissioning.
Name and address of the tenderer Signature of the tenderer