HALOGUARDTM III
MULTI-POINT, MULTI-GAS MONITOR
INSTRUCTION MANUAL
11285 Elkins Road Bldg. H-1
Roswell, GA 30076
TEL: 770-667-3865
FAX: 770-667-3857
IMPORTANT
READ ENTIRE BOOKLET BEFORE
INSTALLING OR OPERATING
HALOGUARDTM III MONITOR
TABLE OF CONTENTS
Page
1.Unpacking Instructions------3
2.Before Installation------3
3.Function of LED’s, Pushbuttons, & LCD Information------4
4.Installation------6
5.Set-up & System Configuration------8
6.Calibration, Testing, & Trouble Shooting------10
7.Maintenance & Specifications------11
FIGURES
Page
1.Typical Area Monitoring Installation ------3
2.Mounting Dimensions------4
3.LCD Display Information------4
4.Haloguard III------5
5.Analog Jumper Settings------6
6.Circuit Board------7
7.Setup & Configuration Jumper Settings------8
8.Remote Expansion Module Terminations------9
9.Remote Expansion Module Circuit Board------9
10.Replacement Parts------11
11.Accessories------11
12.Initial Factory Settings------11
13.Refrigerant Exposure limits------11
UNPACKING INSTRUCTIONS
HaloguardTM monitors are carefully packed, inspected and delivered to the carrier in good condition. If damage occurs in transit it is the responsibility of the carrier. Carefully inspect the unit upon receipt. Any damage should be reported to the carrier and an inspection requested. After inspection by the carrier and your receipt of his acknowledgment as to the damage, contact us for return authorization (RMA). We cannot file claims for damaged goods on your behalf, but we will assist you in any way we can. In order to expedite our work, please provide serial number and model number when you call.
WE CANNOT ACCEPT RETURNS WITHOUT PRIOR APPROVAL.
BEFORE INSTALLATION
1.Remove Haloguard III from carton. Check contents against packing list. If shipment is incomplete, contact us immediately.
2.Select a site for the installation:
a.Power requirements: Provide a clean source of power 115-230 VAC, 50/60 Hz, single phase 15A minimum.
b.Sample tube pick-up should be located near potential leaks in a quiet area or downstream from leak source in area with air movement.
c.Sample tube pick-up should be located 18” - 24” above the floor. If using optional scanner, locate sample tubes at points near all chiller locations. Make sure each sample tube is equipped with an end of line filter.
d.Make sure the area selected is not subject to flooding, potential impact or severe ambient temperature and humidity changes (i.e. boiler blow-down or near roll-up doors).
- Wide band infrared detector is non-selective and may respond to the presence of other gases (i.e. paint thinner, cleaning fluids and other refrigerants) if interfering gas reaches a high concentration. For accurate refrigerant leak detection select a location free from above vapors or temporarily disable sensor when they are present. Contact us for specific gas interference.
3. The Haloguard III should be installed indoors, about five feet above the floor and at a location easily visible to operators, in an area with minimal vibration, and with temperature and humidity changes like sample pick-up location. DO NOT MOUNT DIRECTLY TO CHILLER
Fig. 1-Typical Area Monitoring Installation
IMPORTANT
CONSULT LOCAL AND NATIONAL ELECTRICAL CODES FOR ANY SPECIAL REQUIREMENTS OR RESTRICTIONS BEFORE INSTALLING HALOGUARD.
FUNCTION OF LED’S, PUSHBUTTONS, and LCD DISPLAY INFORMATION
1.READY LED- Steady LED means Haloguard III is measuring ppm; blinking indicates otherwise
2.POWER LED- LED indicates Haloguard III is receiving power.
3.FAULT LED – LED indicates malfunction.LCD displays specific type of failure (See Figure 3)
- ALARM 1, ALARM 2, ALARM 3 LED’s-Adjustable Alarm levels & relays - Factory set for
particular refrigerant (See Figure 12 ). User adjustable as follows:
RANGE / 1 PPM INCREMENTS / 10 PPM INCREMENTS0 - 1000 ppm / 50 - 100 / 100 - 1000
- MANUAL SCAN push-button
6.RESET/SILENCE push-button - Silences alarms, disables relays, and resets instrument for 20 minutes. LCD displays RESET/SILENCE with 20 minute countdown. Alarms are automatically reactivated if alarm condition is not corrected. Reset is automatically initiated on start-up and after power failure.
7.Optional Display Features: TWA Integration – Haloguard III calculates an 8 hr. Time Weighted Average (TLV-TWA), displays this value on LCD, activates Alarm 1 LED and relay if factory set PPM value is exceeded. Used for gases with TLV-TWA less than 1000ppm. TLV-TWA Alarm is factory set and not user adjustable.
INSTALLATION
1.Check power supply and determine best location. (See Section “Before Installation”)
2.Disconnect power before beginning.
Refer to figures 2, 3, 4, 5 and 6 before proceeding.
3.Installation
a. Mounting Haloguard III
1.Securely mount the unit to a wall or support using the (4) mounting holes.
2.Remove cover.
3.Install sample tube to 18-24” above floor, install end of line filter. Sample inlet may be extended up to 300FT with 0.125” OD x 0.093” ID nylon, copper or stainless steel tubing. When extending sample tubing:
a.Keep sample lines as short as possible and free of kinks.
b. Exhaust to atmosphere. DO NOT install any device which might restrict the flow.
- Route sample inlet tubing through entry indicated ( Figure 4 ) and insert into one-touch fitting provided. To remove tubing pull plastic ring on end of one-touch fitting to release.
b.Wiring Connections:
- Relay Terminals – Route wire through entry indicated. (Figure 4 ). Remove safety cover. Connect alarm relays NO or NC (Figure 6) as required.
- Power Supply Wiring-Route wire through entry indicated. (Figure 4 ). Remove safety cover. All connections are made to the terminal block labeled IN 120/250VAC (Figure 6). Connect HOT AC wire to Terminal L. Connect NEUTRAL wire to terminal N. Connect a GROUND wire to terminal G. Auxiliary 120/250VAC output is provided to activate remote audible and strobe light alarms. This output is not fused. Limit load to 0.5A.max total. Replace cover.
**WARNING**analog output is a driven signal, do not connect any wire with voltage or current to analog output terminals
- Analog Output (Optional) – Two analog outputs are provided for connection to remote recording devices; PPM analog output is for gas concentration; Channel analog output is for channel location(Figure 6). Connect 18 ga. twisted shielded pair as follows, maximum length 300 ft.:
Analog Output Range / Terminal Position
0-10VDC / V and GND
4 - 20mA / I and GND
Figure 5 - Analog Jumper Settings
- Auxiliary Input(VDC) – Five analog inputs (EXT INPUT 3-8) are provided for connection of remote input devices such as oxygen sensors, CO sensors, and flammables sensors
(Figure 6)
- Auxiliary Input(mA) – Two analog inputs (REMOTE IR INPUT 1&2) are provided for connection of Haloguard Remote Expansion Module (Figure 6)
- Uninterruptable Power Supply (Optional) – Make sure UPS is fully charged. Plug UPS into power supply, turn switch ON.Connect Haloguard III to UPS, with power cord provided
- On power-up, RESET/SILENCE and20 minute count downwill appearon LCD. For 20 minutes after power up all alarms and relays are automatically disabled. Whenever power is disrupted, RESET/SILENCE mode will be automatic (unless optional UPS is supplied) to protect against false alarms. Allow 1 hour for warm-up from cold start.
Figure 6 Circuit Board
SETUP and SYSTEM CONFIGURATION
Locate jumpers on Figure 6. Select configuration settings from the following:
JP / FUNCTIONRUN / Select run for normal operation
SETUP / Set gas type and number of active channels
TEST / Sequentially activates all alarm & Fault LED’s & relays
ALARM / Set Point Adjustment for Alarm 1, 2, and 3
CAL / Zero Calibration
SPAN / For use only with span gas and key
JP5 / Factory only
Figure 7 – Setup & Configuration Jumper Settings
1.RUN - Remove jumper to initiate other modes. Replace jumper when finished.
- SETUP - Gas type will be pre-set at the factory. Number of active channels will be the maximum possible for the instrument as supplied (Fig.12). To change gas type or number of active channels use jumper to initiate the set-up mode. Select channel with cursor by using the UP/DOWN/ENTER pushbuttons. Select gas type for each channel by using UP/DOWN pushbuttons. “NONE” selected in the gas type menu will skip channel
- TEST-Select test mode. Select alarm with cursor by using UP/DOWN/ENTER pushbuttons
4.ALARM -Alarm levels will be pre-set at the factory (Fig.12). To change select ALARM with cursor using UP/DOWN/ENTER pushbuttons. Change PPM using UP/DOWN/ENTER pushbuttons OFF selected turns alarm off.
5.CAL – Install optional activated charcoal filter in channel 1, follow on screen directions for zero calibration using ENTER pushbutton.
6.SPAN –Key and instructions for use are included with optional Span Gas Calibration Kit
7.JP5- Factory only.
System Configuration:
1.Relay Latch - Factory recommended setting is unlatched mode; e.g., the alarm LED’s and relays will return to a normal status when gas concentration goes below alarm setpoint. To select latched mode place jumper on ALARM setting. Select LATCH mode with the cursor using UP/DOWN/ENTER pushbuttons. LATCH ON appears on the LCD Display. Latched mode require manual RESET for all alarms
2.Analog Output (optional) is factory set at 0 - 5 VDC or 4 - 20mA as ordered. Use Analog trim pot (Figure 6) to adjust for up to 0-10VDC range
3.LCD display adjustmentpotentiometer changes brightness (Figure 6).
4.Two, Four, or Eight Point Scanner - (Optional) Scanner is factory installed. Scanner automatically sequences through each port (1-2, 1-4 or 1-8).
a.Manual Scan - While in RUN Mode,
- Press MAN SCAN button on side of controller. Each time the button is pressed, display will advance to next sample point. Controller will return to automatic sequencing within 2 minutes.
- Adjust Scan Rate - Rate is factory set at 4 seconds per point. Rate is adjustable from 3-10 seconds. To change scan display rate press ENTER from RUN mode; adjust UP/DOWN; press ENTER to return to RUN mode.
5. Installation of Optional Remote IR Expansion Module
Refer to FIGURE 4, 6, 8, and 9 before proceeding.
DO NOT CUT SUPPLIED CABLE
a.Controller is provided with 18” cable with DIN connector and expansion module is provided with 6-1/2’ cable. If cable extension is required we recommend 3 conductor 18 ga. cable with foil shield, Carol C2535 or equal. Use 3/4” conduit if required. Maximum length 1000 ft.
b.Remove 18” cable with DIN connector from controller circuit board. Splice or solder extension cable to end of 18” cable. Reconnect extended sensor cable to terminal block on circuit board of controller.
Terminal / ProvidedWire Color / Extension
Wire Color / Function
CHA / Red / Red / Scanner
SIG / White / White / Signal
GND / Blk/Blk / Black / Ground
Note - CHA Terminal is used for expansion modules with scanner Only.
Figure 8 – Remote Expansion Module Terminal Connection
To avoid nuisance alarms remove “AUDIBLE” alarm jumper before beginning.
c.To compensate for line losses adjust signal voltage with a digital VOM as follows:
1.Open cover on Remote IR expansion module. Move jumper from RUN to SETUP. Wait approximately 1 minute before proceeding .
2.Open cover on Haloguard III.
3.With VOM on 5 VDC scale, place VOM probe on SIG (+) and GND (-) Test points on Controller (see Figure 6).
Adjust potentiometer on Haloguard III Main Board, with screwdriver until it reads 4.975 +/-0.025 VDC.
Display will show FAULT if out of range and SETUP, if trimmed to 4.975+/-0.025 VDC.
4. If Remote expansion module is provided with scanner it will be necessary to lock the scanner on channel 1 using the jumper provided (Figure 9).
5.Replace jumper in RUN mode. Replace AUDIBLE jumper to activate alarm.
CALIBRATION
Haloguard III monitors are factory calibrated to the primary gas of interest. Field calibration is not required for operation in typical machine room environments during the first twelve months of operation unless a change in gas type is required
For those who wish to check the factory calibration or change the gas type an optional Span Gas Kit is available. Instructions for use are included with kit
TESTING
The Haloguard IIITM should be tested at start-up, after any changes to alarm protocol, and after each alarm level condition has been corrected.During testing, display will indicate ALARM TEST
a.Alarm Test –Enter TEST mode with jumper, select alarm with cursor by using UP/DOWN/ENTER pushbuttons. Check all alarms sequentially. Alarm relays, lights, audible and remote alarms (if equipped) will activate if selected.
b.Reset Test - Push RESET/SILENCE button; alarm relays, audible and remote alarms (if equipped) will become inactive for 20 minutes. Display will read RESET/SILENCE and indicate minutes to completion of reset period.
TROUBLESHOOTING
The most frequent cause of nuisance and fault alarms is improper set-up, primarily due to:
a. Failure to install in accordance with instructions.
b.Not allowing sufficient warm-up time.
c.Poor sensor location.
To check Zero Calibration, fill a clean plastic trash bag with clean outside air, tie off with twist-tie, let sample stabilize inside for 15 - 20 minutes. Insert sample tube into bag . For models equipped with scanner allow up to 2.5 minutes per channel for clean air sample analysis
.
Observe LCD response, if displayed PPM value drops lower Haloguard III is detecting the presence of the gas of interest or another gas which absorbs infrared light at the same frequency.
Remove sample tube from bag and observe LCD response. If displayed PPM value moves higher, look for refrigerant leaks or possible sources of interfering gases (See “Before Installation). and relocate sample point.. Keep in mind that the Haloguard III is much more sensitive than hand held leak detectors, it may detect a leak when hand held units show no response
We wish to aid with any problems you might experience with the Haloguard III. When contacting Thermal Gas Systems, Inc. Service Department, please have the following information ready
1.Model Number and Serial Number.
2.Description of the problem.
3.Remove cover. Place jumper on Alarm function and record settings. Place jumper on Setup function and record settings.
4.Advise the condition of all LED’s and all information displayed on the LCD.
MAINTENANCE
There is no scheduled maintenance for the first 12 months operation; after 12 months the internal and external filters should be changed and the instrument should be gas tested in accordance with the instructions. Self-diagnostics will indicate the cause of any unusual malfunction. To obtain spare or replacement parts please contact Thermal gas Systems, Inc.
1
Rev.1/26/01
Description / Part No.Internal Filter, element / A702
External Filter, element / A703
Switcher Valve / A501
Pressure Switch / A708
Scanner, 2-station / A501
Scanner, 4-station / A502
Scanner, 8-station / A503
Power Supply; 120/230VAC / A707
Pump / A709
Figure 10 – Replacement Parts
Description / Part No.Audible alarm, local / A603
Strobe alarm, local / A607
Audible alarm, remote / A605
Strobe alarm, remote / A606
Combination audible/strobe alarm, / A604
Zero Gas Scrubber
Span Gas Kit / A204
Fig. 11- Accessories
1
Rev.1/26/01
SPECIFICATIONS
1
Rev.1/26/01
Technology:Wide band Photoacoustic Infrared
Electrical Supply:115-230 VAC, 50-60Hz
Output Signal:Std. 4x3A Dry Contact SPDT
Opt. 7x10A. Dry Contact SPDT
Analog OutputOpt. 0 - 5 VDC or 4 - 20mA
Opt. RS232/485 Serial
Alarm Outputs:Std. Three Level Contact Closure
Opt. Seven Level Contact Closure
Readout:Digital LCD; Displays Channel,PPMGas Type, and Fault Diagnostics
Display accuracy:1ppm 10 - 100 ppm Range
10ppm 100 - 1000 ppm Range
Range:0 - 1000 ppm R-11, 12, 22, 123,134a,
Operating Conditions:
+40oF to +120oF Non-condensing
Fault Diagnostics:Indicator LED and LCD Readout
(See Figure 5)
Enclosure: NEMA 250 Std. NEMA 4/12 Opt.
Weight: 15 lbs.
Dimensions: 12” W x 14” H x 4.5” D
Sample Rate 1.0 Liter/min.
Response Time:< 1 Minute single point
< 2.5 Minutes per point with optional scanner.
1
Rev.1/26/01
Initial factory settings are:
Function / SettingChannel
1 2 3 4 5 6 7 8Gas
Alarm 1
Alarm 2
Alarm 3
Figure 12 - Initial Factory Settings
GAS / TLV-TWA* / CEIL / PELR-11 / 1000
R-12 / 1000 / 1000
R-22 / 1000 / 1000
R-123 / 50
R-134a / 1000 / 1000
Figure 13- Refrigerant Exposure limits
1
Rev.1/26/01