COE Installation Quality Bulletin
Installation Quality Bulletin Number: 06-02
To: All Installation Suppliers / Central Office Operations Representatives / Design Engineering Representatives / Quality Managers / Field Engineering Representatives / AMC Representatives
Date:Monday, March6, 2006
From: QWEST Installation Quality Assurance
Subject: Hilti™ floor anchor assembly (temporarily) approved for use within Toll/Switch areas of Qwest Central Offices
Action Required:
YES: / / NO:Description of Bulletin:
The purpose of this Quality Bulletin is to provide installation instuction for anchoring equipment in the central office environment. Qwest’s standard toll anchor bolt assembly (Hilti part number 002307122, Qwest PID 2285841) has been manufacturer discontinued and will no longer be available. Qwest AMC group has temporarilyapproved, an alternate Hilti anchor bolt for use within all Toll/Switch/Power areas of Qwest central offices until a new standard anchor bolt assembly for Qwest has been finalized. Details regarding this interim anchor assembly are defined within this bulletin. Substitution of any other anchor assembly to be used in Qwest facilities is strictly prohibited.
Temporarily-Approved Central Office Toll/Switch Floor Anchors
Approved Applications for Use:
- Anchoring all telecommunications equipment frames/cabinets/stanchions installed in Toll, Power, and/or Switch areas of the CO - All Earthquake Zones.
- Anchor quantities listed in Qwest Technical Publication 77351, Chapter 2, Section 2.5.6 remain unchanged. The anchor’s description wil not be revised until after a final decision regarding the Qwest standard anchor is formally made.
- Must be used to anchor battery stands requiring shimming due to uneven floors. Battery stands that do not ned to be shimmed will continue to use the Qwest standard power anchor (Hilti Part No. 97413007) as defined in Qwest Technical Publication 77350, Par. 3.21.
Kit Part Number:
- Each Hilti 284912 kit includes 2 complete anchor bolt assemblies.
- Each kit includes 2 complete anchor bolt assemblies and the all necessary components as follows:
Hilti Sales Number: 284912
HSL – I M12/65 80RW Assembly Set (Refer toSK-A)
No. / Item No. / Quantity / Description1 / 355672 / 1 / ANCHOR ASSEMBLY HSL-M12 65/
2 / 66652 / 1 / WASHER M12 HSL
3 / 216148 / 1 / NUT, TORQUE ASSY M12
4 / 355899 / 1 / THREADED ROD M12X80 SLTD, 8.8
5 / 271991 / 1 / WASHER 50X50X5X18
6 / 269250 / 0.5 / SETTING TOOL HSL-1
Installation Requirements (Refer to SK-B):
- Hilti installation instructions must be adhered to in order to prevent invalidation of the anchor warranty. Hilti’s installation instructions can be found affixed to each anchor bolt kit.
- Only an 18mm drill bit will be used. Substituting a drill bit of any other size is prohibited.
- The installer will drill the anchor pilot hole to a depth of 75mm (2.95”) and remove 100% of the debris prior to anchor placement . A pilot hole exceeding this maximum depth is prohibited.
- In regard to the setting tool; only the short side (designed for 65mm embedment depth) will be used for placing the anchor in Qwest facilities.
- Upon completion of the installation, the top anchor base must not protrude above floor level.
- Any problems noted during unpacking or installation of the Hilti Kit No. 284912 floor anchor (or floor-related problems) must be reported to the Qwest AMC representatives responsible for Common Systems requirements.
- Anchor shall be tightened to 60 foot pounds where the torque indicating top nut should shear off.
- When installing the Hilti anchor, the small round washer will ALWAYS be placed between the square washer and the torque indicating nut. The square washer will be located directly on top of the frame base (or battery stand foot where shimming is required).
SK-A
SK-B
Acknowledgements to Diana Unser (AMC) and to Kacey Burton of the Hilti™ Corp. for their contributions to the technical content of this Bulletin.
Qwest Installation Quality Assurance
Jeff Bostow
612-798-2460
mailto: