Note: The whole of the planning scheme is identified as the assessment benchmark for impact assessable development. This specifically includes assessment of impact assessable development against this strategic framework. The strategic framework may contain intentions and requirements that are additional to and not necessarily repeated in zone, overlay or other codes. In particular, the performance outcomes in zone codes address only a limited number of aspects, predominantly related to built form. Development that is impact assessable must also be assessed against the overall outcomes of the code as well as the strategic framework.

9.4.3  Fire services in developments accessed by common private title code

9.4.3.1  Application

The code applies to assessing material change of use or reconfiguring a lot where indicated within Part 5 Tables of assessment and where the development:

(1) is in an urban area; and

(2) results in part of the development, or any dwelling, being more than 90 metres from the nearest located fire hydrant; and

(3) is for buildings, both attached and detached, not covered by other legislation or planning provisions mandating fire hydrants; and

(4) includes streets and common access ways within a common private title; and

(5) is in an area serviced by reticulated water.

Editor’s note – The term common private title covers areas such as access roads in community title developments or strata title unit access which are private and under group or body corporate control.

When using this code, reference should be made to Section 5.3.2 and, where applicable, Section 5.3.3, in Part 5.

9.4.3.2 Purpose

(1) The purpose of the Fire services in developments accessed by common private title code is to ensure that developments accessed by common private title have the appropriate fire hydrant infrastructure and unimpeded access to emergency services vehicles for the protection or people, property and the environment from fire and chemical incidents.

(2) The purpose of the code will be achieved through the following overall outcomes:

(a) Activities and buildings accessed by common private title have adequate fire hydrant infrastructure provided which is suitably located and identifiable for effective firefighting purposes.

(b) Fire emergency services vehicles have unimpeded access to all activities and buildings for effective firefighting purposes.

9.4.3.3 Specific benchmarks for assessment

Table 9.4.3-2: Fire services in developments accessed by common private title – for assessable development

Performance outcomes / Acceptable outcomes / Does the proposal meet the acceptable outcome?
If not, justify how the proposal meets either the performance outcome or overall outcome / Internal use
/
Hydrant location
po1
Hydrants are located in positions that will enable fire services to access water safely, effectively and efficiently. / AO1.1
Residential streets and common access ways within a common private title have hydrants placed at intervals of no more than 120 metres and at each intersection. Hydrants have at least a single outlet situated above ground.
AO1.2
Commercial and industrial streets and access ways within streets serving commercial properties such as factories, warehouses and offices are provided with above ground fire hydrants at not more than 90 metre intervals and at each street intersection. Hydrants have dual valved outlets.
Access ways in common private title
po2
Road widths and construction within the development are adequate for fire emergency vehicles to gain access to a safe working area close to dwellings and near water supplies whether or not on-street parking spaces are occupied. / AO2
Road access minimum clearances of 3.5 metres wide and 4.8 metres high are provided for safe passage of emergency vehicles.
Hydrant identification
po3
Hydrants are suitably identified so that fire services can locate them at all hours. / AO3
Hydrants are identified as specified in the South East Queensland Water Supply and Sewerage Design and Construction Code standard drawing SEQ-WAT-1300-1 ‘Typical valve and hydrant identification markers’.
Note: Standard drawing SEQ-WAT-1300-1 is available from http://www.seqcode.com.au/seq-water-supply-code/