T – 1341 TARGET

FAIRFAX, VIRGINIA

SUMMARY

The Target Store T-1341at 13047 FairLakesShopping Center inFairfax, Virginia was inspected by Thomas Branham of Elevator Consulting Services, Inc. on May 4, 2017. My QEI number is 1339 and I am certified by NAESA. NAESA is the National Association of Elevator Safety Authorities. We have identified corrective items that in our opinion need to be addressed by the Elevator Contractor. They are free to offer an explanation or dispute any individual item within the report but we can offer a code, specification or reasonable reason for each and every negative evaluation. They are evaluated on and for the ASME 17.2 Code for Inspectors Manual and industry standards for acceptable installation and maintenance procedures.

Service Invoicer – ThyssenKrupp Elevator

PMT- Johnathon

Take 66 Westbound, exit 55B to 286 then go to Fair Lakes Parkway, turn right, go 6 lights and turn left into Fair Lakes Shopping center. Stay in right turn lane at 6th light, veer right as you enter shopping center.

Note:OLI = Outside Looking In

ILO = Inside Looking Out

T-1341 TARGET

FAIRFAX, VA

PASSENGER ELEVATOR 1

CORRECTIVE ITEMS

The following minimum items need corrective action taken. Documentation of completion is required. ANLT – 1-29-16

1.Start a current 2017 log / tasking sheet. Only 5 entries for 2016, none for 2017 yet except a line entry of the ANLT on 4-4-17 with no other documentation except the NEIS test sticker.

Completion Date______Initial_____

2.Door operation groan in the open at LL level. Clean the hoistway door tracks, replace spirator or hanger rollers to quiet them down.

Completion Date______Initial_____

T – 1341 TARGET

FAIRFAX, VA

FREIGHT ELEVATORS 2 & 3

CORRECTIVE ITEMS

The following minimum items need corrective action taken. Documentation on completion is required. ANLT 1 – 4-4-17

2 –4-4-17

Date / Count
05-04-17 / 38,679

General

7.Remove old line starter from the machine room.
Date Completed ______Initialed ______

Elevator Two – Starts – No ID

8.Clean the hoistway door tracks of all fuzz and dirt in between openings and all related door lock hardware.
Date Completed ______Initialed ______

9.Replace both gate chains on the right side (OLI) due to rust, frozen links. Link to measurement exceeds OEM limits.
Date Completed ______Initialed ______

10.Repair the safety edge conduit fitting. The 90 degree fitting is broken.
Date Completed ______Initialed ______

Elevator Three - Starts - 73,075 10/20/08110,58903/02/10

81,715 03/17/09129,32709/13/10

98,033 09/29/09148,32104/05/11

161,670 09/20/11177.71503/29/12
201,992 02/14/13235,27702/04/14

275,597 04/13/15297,56502/05/16

332,414 05/04/17

11.Flush the hoistway door chains of all rust and rouge with WD-40. Wipe off excess.
Date Completed ______Initialed ______

12.Clean the hoistway door tracks of all fuzz and dirt in between openings and all related door lock hardware.
Date Completed ______Initialed ______

13.Repair the hoistway access box on the LL level. Currently taped with electrical tape.
Date Completed ______Initialed ______

14.Replace the left (ILO) hoistway door chains on LL due to rust, stretch. Adjust lock gap.
Date Completed ______Initialed ______

15.Replace the left (ILO) hoistway door chains on UL due to rust, stretch. Adjust lock gap.
Date Completed ______Initialed ______

T – 1341 TARGET

RECOMMENDATIONS

Elevators 2 & 3

1.Provide knee bracing from the gate crossover angle back to the crosshead.

2.Upgrade the original single photo eye on the gate to a sequential scanner.

END OF REPORT