Additional wireless power monitor, single phase
EN-P
User Guide
Version 1.0
For further details, please contact:
Enistic Limited, 4 Isis Business Centre, Pony Road, Oxford, OX4 2RD
© Copyright 2014 Enistic Limited.
Contents
Overview
Hardware architecture
Wiring Guide
Pairing Transmitter With a Ethernet Receiver – Photograph
Battery Replacement
Current Transformer Connection – Photograph
Current Transformers Dimension
Specifications
Document history
Version / Date / Author / Notes1.0 / 19 Jan 2015 / Wasil Ali / Preliminary release of alpha test details.
Overview
Additional wireless power monitor, single phase(EN-P) is a meter that reads data from current clamps and sends back to the Ethernet wireless receiver (EN112). It is a low cost solution and suitable for office and industrial monitoring applications. EN-P has one input to attach Current Sensor (CT5 – CT3000) supporting readings from devices up to 3000A. It communicates with the controller through the Wireless communications (RF 433MHz ISM band). It comes in a small enclosure and can be mounted on a wall. Simple to Install and easy to configure.
• Suitable for residential, commercial and industrial monitoring purposes.
• Manufactured to comply with IEC 60687/61036/61268 and IEC 62053-21/62053-22/62053-23.
• Single receiver can handle multiple transmitters.
• Plug and play. Easy to install on site.
• Wireless, low power operation.
Features
• Highly accurate design
• Manufactured to comply with international standards IEC 60687/61036/61268 and IEC 62053-21/62053-22/62053-23
• Connects with controller on 433 MHz Band
• Encrypted communications for secure operation
• Good range
Order codes
EN-P - Additional wireless power monitor, single phase
EN126 - Battery 3.6V, AA, 2600mAh
Split core current sensor sizes for EN-P with order code in bold:
EN114 - CT5,EN115 - CT10,EN116 - CT15,EN117 - CT30,
EN118 - CT60,EN119 - CT100,EN120 - CT200, EN121 - CT400,
EN122 - CT600, EN123 - CT1500, EN124 - CT3000
Hardware architecture
Figure 1: Hardware Architecture
Wireless power monitor, single phase is built of a processor and RF transceiver to communicate with the controller. This device is responsible for taking the readings from Current Clamps and send readings to the controller via RF link. Frequency off the link is 433MHz. It transmits reading to the receiver (EN112) every 5 minutes
Wiring Guide
Figure 2: Activity LED “Green”
Figure 3: Current Transformer Connection
Figure 4: Non-Rechargeable Battery
Pairing Transmitter With a Ethernet Receiver– Photograph
In order to pair each transmitter (EN-P) with the receiver (EN112) press the pairing mode button at the back of the receiver (EN112). During pairing mode the radio activity and server activity LEDs start flashing for about one minute. While receiver is in pairing mode connect the battery in the transmitter and wait so that it pairs with the receiver. Once it pairs you will see the radio activity and server activity LEDs stop flashing.
You need to repeat the above step each time if you have multiple transmitters (EN-P).
Figure 5: Ethernet Receiver Connection Layout
Battery Replacement
Figure 6: Battery Replacement
Battery Details
- Nominal Voltage 3.6V
- Nominal Capacity 2.6 Ah (2600mAh)
- Nominal Current 2mA
- Maximum Continuous Discharge Current 70mA
- BatteryWeight 17g
- TemperatureRange –60°C ...+85 °C
- Diameter 14.65mm
- Length 50.3mm
- Order Code: EN126
Current Transformer Connection– Photograph
Figure 7: Current Transformer
Figure 8: Current Transformer Connection
Current Transformers Dimension
Specifications
Electrical
Item / Value / UnitBattery for EN-P / 3.6 / Vdc
Battery Type / Lithium Thionyl Chloride
Battery Capacity / 2600 / mAh
Power Consumption (Typical / Maximum) / 9 / 250 / mW
Physical
Item / Value / UnitSize (l x w x h) / 110x71x42 / mm
Fitting / Wall mount
Storage temperature (min -> max) / -10 -> +30 / °C
Operation temperature (min -> max) / -10 –> 85 / °C
Measurements and Metrology
Item / Value / UnitChannels / 1
Nominal Current / 5-3000* / A
Min. Current / 0* / A
Min. Current 1% ** / 0.05-150* / A
Max. Current / 5-3150* / A
Max. Current 1% ** / 4.95-2850* / A
Probe Cable Length / 1000-1500* / mm
Communication
Item / Value / UnitStandard / RF / -
Frequency / 433 / MHz
MaximumRange between Tx and Rx (LOS) / 100 / m
Encryption / Yes
Miscellaneous and Standards
Item / Value / UnitCountry of Design / Manufacture / UK
Packaging / Cardboard box
1