Chrysler LLC Construction Standards
12/17/04
SECTION 16140 - WIRING DEVICES
PART 1 - GENERAL
1.1 SUMMARY
- This Section includes receptacles, connectors, switches, and finish plates.
1.2 DEFINITIONS
- GFCI: Ground-fault circuit interrupter.
1.3 QUALITY ASSURANCE
- Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction.
- Comply with NEMA WD 1.
- Comply with NEMA WD 6.
- Comply with NFPA 70.
1.4 COORDINATION
- Receptacles for Equipment: Match branch circuit wiring and outlet configuration to plug configuration indicated on approved equipment submittals.
- Cord and Plug Sets: Match plug configuration indicated on approved equipment submittals.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
- Manufacturers: Unless otherwise directed, provide products by one of the following:
- 125 Volt and 250 Volt Wiring Devices
- Arrow Hart Div.; Cooper Industries.
- GE Company; GE Wiring Devices.
- Hubbell, Inc.; Wiring Devices Div.
- 480 Volt “Maintenance” Receptacles
- Crouse Hinds “Arktite”
- Russellstoll “Max-Gard”
- Square D
- Appleton
2.2 RECEPTACLES
- Straight-Blade and Locking Receptacles: Heavy-duty grade.
- Provide blade configurations per NEMA WD1.
- GFCI Receptacles: Feed-through type, with integral NEMA WD 6, Configuration 520R duplex receptacle.
- Connect to protect downstream receptacles on same circuit
- Receptacle suitable for installation in a 2-3/4-inch-deep box without adapter.
2.3 SWITCHES
- Snap Switches: Heavy-duty, quiet type, 125 Volt or 250 Volt rating, coordinated with the branch circuit.
- Incandescent Dimmer Switches: Modular, full-wave, solid-state units with integral, quiet on/off switches and audible and electromagnetic noise filters.
- Single-pole or three-way operation to suit connections
- Soft tap or other quiet operation ON/OFF switch
- Continuously adjustable slide control.
- Modular, full-wave, solid-state design
- Integral, quiet on/off switches
- Electromagnetic filter(s) to eliminate audible noise, RF, and TV interference;
- Color-coded, integral 5-inch wire connecting leads
2.4 WALL PLATES
- Single, combination and multi-gang types to match corresponding wiring devices.
- Material for finished spaces:
- 0.04-inch-thick, Type 302, satin-finished stainless steel.
- Provide cover plate securing screws with head color to match plate finish.
- Material for unfinished spaces:
- Galvanized steel.
PART 3 - EXECUTION
3.1 INSTALLATION
- Install devices and assemblies plumb and secure.
- Provide dimmer switches to achieve indicated rating after derating factors for ganging are applied, as instructed by manufacturer.
- Do not share neutral conductor on load side of dimmers installed on different branch circuits.
- Orientation of Devices: Unless otherwise indicated, mount flush, with long dimension vertical and grounding terminal of receptacles on top. Group adjacent switches under single face, multigang wall plates.
- Adjust locations of floor service outlets and telephone/power service poles to suit arrangement of partitions and furnishings.
- Install wall plates after painting is complete.
- Install devices after painting is complete, or protect devices during painting.
3.2 CONNECTIONS
- Connect wiring device grounding terminal to branch-circuit equipment grounding conductor.
- Tighten electrical connectors and terminals according to manufacturer’s published torque-tightening values. If manufacturer’s torque values are not indicated, use those specified in UL 486A and UL 486B.
3.3 FIELD QUALITY CONTROL
- Test receptacles for proper polarity and ground continuity.
- Test GFCI operation.
- Replace damaged or defective devices and components.
3.4 CLEANING
- Internally clean devices, device outlet boxes, and enclosures. Replace stained or improperly painted wall plates or devices.
END OF SECTION
WIRING DEVICES 16140 - 1 of 3