Section 102113
2011-08-24Metal Toilet Compartments
Refer to “LEED Notes and Credits” page for additional guidance for LEED projects.
Delete LEED items if project:
.1is excluded by the Department’s policy on LEED, or
.2the Department has determined that the work of this Contract is not to attain a LEED rating.
Use this section to specify shopfabricated metal toilet, shower and dressing compartments, and screens, which are either overhead braced, floor anchored only, or ceiling hung.
For vandalism prone installations, partitions of more durable materials, e.g. steel and concrete, specifically designed to withstand anticipated abuse, should be detailed on drawings and specified. Where moisture or high humidity is anticipated, use Section 102114 to specify solid phenolic core plastic laminate partitions with corrosion-resistant hardware.
This Master Specification Section contains:
.1This Cover Page
.2LEED Notes and Credits
.3Data Sheet - General
.4Specification Section Text:
1.General
1.1Section Includes
1.2Related Work Specified in Other Sections
1.3Reference Documents
1.4Administrative Requirements
1.5Submittals
1.6Closeout Submittals
1.7Delivery, Storage, and Handling
2.Products
2.1Materials
2.2Hardware
2.3Bracing, Anchorage and Fasteners
2.4Fabrication
2.5Shop Finishing
3.Execution
3.1Examination
3.2Installation
3.3Overhead Braced Compartments
3.4Ceiling Hung Compartments
3.5Floor Anchored Compartments
3.6Screens
3.7Clean-up
3.8Schedule
BMS Basic Master SpecificationAlberta Infrastructure
Master Specification System / Page 0
LEED Notes and Credits
Section 102113
2011-08-24Metal Toilet Compartments
LEED Notes:
N/A
LEED Credits:
Contribution towards LEED credits in this section may apply as follows:
1.LEED Credit MR 4: Recycled Content.
.1The criteria is that the sum of post-consumer recycled content plus one-half of the pre-consumer content constitutes at least the percent(10% and 20%)of the total value of the materials in the project. Metal toilet compartment products contain recycled material. For example, steel, aluminum and stainless steel have post industrial as well as post consumer recycled components. Product data and/or LEED letters from manufacturers are required for verification.
2.LEED Credit MR 5:Regional Materials.
.1If fabricated regionally, products specified will applytowards this credit. The contractor will be required to submit documentation consisting of cost, weight, transportation service and distance the material has travelled to the construction site. There is a manufacturing facility in Calgary, AB.
BMS Basic Master SpecificationAlberta Infrastructure
Master Specification System / Page 0
Data Sheet - General
Section 102113
2011-08-24Metal Toilet Compartments
ComPartment TYPES
Floor anchored, overhead braced are recommended on structural concrete floors less than 75mm thick and on wood floors. This type has become the most common.
Ceiling hung partitions are typically specified where maintenance, hygiene and operating costs are paramount. Structural steel fabrications are required to adequately anchor this type of partition.
Floor anchored partitions require anchors penetrating minimum 50mm into minimum 75mm thick concrete floors; this type is not recommended for anchoring to wood floors.
Floor and ceiling anchored compartments are omitted from this Section but if required they may be specified using a combination of requirements for overhead braced and ceiling hung types.
PILASTERS
Pilasters at doors to barrier-free compartments, may require additional stiffening to eliminate vibration from door impact. One manufacturer suggests attachment of a perpendicular spline matching pilaster construction to the compartment side face of such pilasters. Another shows an additional pilaster perpendicular to the closed door position. Designers are advised to consider the options allowed in this Section and to decide whether to provide drawing details in order to control appearance.
TYPICAL Toilet Compartment SIZES
Panels and doors are typically made in standard heights of about 1450mm, located 305mm above floors. Height of overhead braced pilasters is typically 2160mm. Consult with manufacturers before deviating from standard dimensions.
Doors are typically 610mm wide, 813mm doors being typically specified for wheelchair accessibility. Pilasters are typically 300mm wide. When a greater degree of privacy is desired, deeper screens and doors can be specified to reduce, but not eliminate, the standard 305mm gap to floors. Coordinate with drawings.
END OF DATA SHEET
BMS Basic Master SpecificationAlberta Infrastructure
Master Specification System / Page 0
Section 102113
Plan No:Metal Toilet Compartments
Project ID:Page 1
1.General
1.1SECTION INCLUDES
SPECNOTE:Delete this article if toilet compartments only are required. Edit to suit project.
.1This Section includes requirements for the following:
.1Toilet compartments.
.2Dressing compartments.
.3Urinal screens.
.4Privacy screens.
.5[].
1.2RELATED Work Specified in Other SECTIONS
.1[LEED Submittal FormsSection013216]
.2[LEED RequirementsSection013518]
.3[Environmental ProceduresSection013520]
.4Waste Management and DisposalSection017419
.5Masonry wall backup:Section042000
.6Steel supports above ceiling for typical ceiling anchorage:Section055000
.7Gypsum wallboard backup:Section092900
.8Washroom accessories and grab bars:Section102813
1.3REFERENCE Documents
SPEC NOTE: Edit this article to include only standards referenced within the edited version of this Section, including LEED documentation and sustainable practices.
.1American Society for Testing and Materials (ASTM):
.1 / ASTMA167-99 (2009) / Specification for Stainless and Heat Resisting Chromium Nickel Steel Plate, Sheet and Strip.2 / ASTMA653/ A653M-09 / Specification for Steel Sheet, Zinc Coated (Galvanized) or Zinc Iron Alloy Coated (Galvannealed) by the Hot Dip Process
.3 / ASTMA924/ A924M-09 / Specification for General Requirements for Steel Sheet, Metallic Coated by the Hot Dip Process
.2CanadaGreenBuilding Council (CaGBC):
.1 / LEED Canada 2009 Rating System / LEED Canada for New Construction and Major Renovations. LEED Canada for Core and Shell Development. Website:.3Canadian General Standards Board (CGSB):
.1 / CAN/CGSB1.81-M90 / Air Drying and Baking Alkyd Primer for Vehicles and Equipment.2 / CAN/CGSB1.88-92 / Gloss Alkyd Enamel Air Drying and Baking
.3 / CAN/CGSB1.104-M91 / Semigloss Alkyd Air Drying and Baking Enamel
.4Safety Codes Council of Alberta:
.1 / Barrier Free Design Guide, Fourth Edition, July 20081.4administrative requirements
.1Coordination:
SPECNOTE:Delete this article if ceiling anchorage is not specified.
.1Coordinate location of steel supports for ceiling anchorage with work of Section055000.
.2Provide templates for locating threaded studs through finished ceilings.
1.5SUBMITTALS
.1Product Data:
.1Submit manufacturer’s printed product literature, specifications and data sheets in accordance with Section013300 - Submittal Procedures.
.2Submit descriptive literature for hardware items, including, but not limited to, hinges, latch sets, coat hooks, brackets, fastenings and trim.
.2Shop Drawings:
.1Comply with requirements of Division 01.
.2Submit shop drawings, clearly indicating fabrication details, plans, elevations, edge details, hardware, and installation details.
.3Submit large scale details of all anchorages, clearly indicating components, materials, and finishes, and related work.
.3Samples:
.1Submit duplicate 200mmx200mm samples of partition types showing finish on both sides, two finished edges, corners, and core construction.
.4Sustainable Design Submittals:
SPEC NOTE: Use the following paragraph when LEED Submittals are required:
.1LEED Submittals: Submit documentation in accordance with Section013518 – LEED Requirements. Submit documentation for the following:
.1Materials & Resources:
SPEC NOTE: Delete LEED submittal item if project is not to attain LEED certification or if Credit MR 4 is not being sought.
.1MR Credit 4 - Recycled Content: [10%] [20%] (post-consumer + ½ pre-consumer)
SPEC NOTE: Delete LEED submittal item if project is not to attain LEED certification or if Credit MR 5 is not being sought.
.2MR Credit 5 - Regional Materials: [20%] [30%] Extracted and Manufactured Regionally
1.6Closeout Submittals
.1Operation and Maintenance Data:
.1Provide data describing maintenance of finishes recommended by finish manufacturers for incorporation into Maintenance and Operation Manual.
1.7delivery, storage, and handling
.1Waste Management and Disposal:
.1Separate waste materials for [reuse] [and] [recycling] in accordance with Section017419 – Management and Disposal.
2.Products
2.1MATERIALS
.1Sheet steel:commercial grade, stretcher leveled, sheet steel to ASTMA653M, with Z275 zinc coating.
.2Minimum steel thickness:
.1Panels and doors:...... 0.80mm.
.2Pilasters:...... 1.00mm.
.3Reinforcement:...... 3.00mm.
.4Headrails:...... 1.00mm.
2.2HARDWARE
.1Hardware not specifically designed for partitions by a metal partition manufacturer shall be subject to approval by Minister.
.2Material: one of the following:
.1Chrome-plated nonferrous, die-cast zinc alloy.
.2Clear anodized aluminum castings and extrusions.
.3Stainless steel, polished or brushed finish.
.3Hardware shall operate smoothly, quietly and consistently.
.4Latch Set, Door Bumper, Brackets: manufacturer's standard for type of partitions.
.5Hinges shall be adjustable to automatically return inswinging doors from any position to nominal 30degrees from closed position, and shall return outswinging doors to closed position.
.6Hardware for compartments designed for barrier-free access shall be suitable for pilaster orientation indicated on drawings and shall conform to barrier-free design requirements of Alberta Building Code.
.7Each type of hardware item shall be consistent as to type and finish.
2.3BRACING, ANCHORAGE AND FASTENERS
SPECNOTE:Edit this article to suit project requirements. Specify stainless steel anchorage and fasteners for shower compartments.
.1Overhead Bracing:extruded aluminum with [clear anodized] [] finish, stainless steel with No.4 or No.6 finish [, or galvanized steel with acrylic finish to match pilasters and doors], of gripdeterring design.
.2Floor Anchorage, Including Fasteners:
.1Concealed: [steel, hot dip galvanized] [stainless steel].
.2Exposed: stainless steel, No.4 or No.6 finish.
.3Ceiling Anchorage: [steel, hot dip galvanized] [stainless steel].
.4Anchorage Concealment: stainless steel sheet, type 302, polished or brushed finish, formed to manufacturer's standard profile.
.5Exposed Fasteners:[cadmium plated steel] [stainless steel], tamper-resistant type.
.6Concealed Fasteners: [steel, hot-dip galvanized] [stainless steel].
2.4FABRICATION
.1Fabricate doors, panels and pilasters of sheet steel faces pressure bonded to sound deadening core, to manufacturer's standard heights and to plan dimensions as indicated on drawings.
.2Standard compartment doors shall be 610mm wide; doors to barrier-free compartments shall be minimum 800wide.
SPECNOTE:Ensure that standard specified above or door widths are indicated on drawings, but not both.
.3Door, Panel and Pilaster Thickness:
.1Doors and Panels:25mm.
.2Pilasters: 32mm.
.4Provide formed and closed edges for doors, panels, headrails, and pilasters. Miter and weld corners and grind smooth.
.5Provide internal reinforcement at areas of attached hardware and fittings. Temporarily mark locations of reinforcement for tissue holders, grab bars, receptacles, coat hooks and other accessories.
2.5SHOP FINISHING
.1Clean, degrease and neutralize steel components with a phosphate or chromate treatment.
.2Spray apply primer to CAN/CGSB1.81, 1 coat.
.3Spray apply finish enamel to CAN/CGSB1.88, Type2gloss] [CAN/CGSB1.104, Type2, semigloss], 1 coat.
.4Finish:Doors and pilaster/panels [same colour] [different colours]. Minister will select colour [from manufacturer's standard range] [from specially selected nonstandard colours] [with a total of [] colours for this project].
3.Execution
3.1EXAMINATION
.1Examine site conditions where the work is to be installed and ensure acceptability of existing room finishes for a complete and satisfactory installation.
3.2INSTALLATION
.1Install partitions secure, plumb and square.
.2Leave 12mm space between walls and panels, and walls and pilasters.
.3Fasten anchoring brackets as follows:
.1To masonry and concrete surfaces using screws and expansion anchors.
.2To hollow walls using bolts and toggle type anchors.
.3[To steel supports with threaded rods in threaded holes].
.4Attach panels and pilasters to brackets with through-type sleeved bolt and nut.
.5Provide for concealed adjustment of [floor] [ceiling] variations with screw jack through steel saddles made integral with pilaster. Conceal [floor] [ceiling] anchorage with stainless steel covers secured in position.
.6Equip each door with hinges, latch set, and coat hook. Adjust and align hardware for easy, proper function.
.7Set inswinging doors to open position at 30° from closed. Set outswinging doors to return to closed position.
.8Install door pulls on out-swinging doors in conformance with barrier-free design requirements of Alberta Building Code.
3.3OVERHEAD BRACED COMPARTMENTS
SPECNOTE:Specify this type of anchorage for typical installations.
.1Attach pilasters to floor with pilaster supports and level. Plumb and tighten installation with levelling device.
.2Secure headrail to pilaster face with not less than two fasteners per face.
.3Set tops of doors parallel with overhead brace when doors are in closed position.
3.4CEILING HUNG COMPARTMENTS
SPECNOTE:Ensure that supporting steel, hangers, threaded rods through ceiling, etc., are specified in Section055000 and shown on drawings. Specify plaster key to be installed at plaster ceilings.
.1Secure pilasters to supporting structural framing using pilaster hangers.
.2Assure pilaster hangers do not transmit load to finished ceiling.
.3Secure pilaster shoe in position.
.4Set bottoms of doors level with bottom of pilasters when doors are in closed position.
3.5FLOOR ANCHORED COMPARTMENTS
SPECNOTE:Specify only where other types of anchorage are unacceptable and anchorage to structural concrete floors is possible.
.1Secure pilasters to floor with pilaster supports anchored with minimum 50mm penetration in structural concrete floor.
.2Level, plumb and tighten installation with levelling devices.
.3Set tops of doors level with tops of pilasters when doors are in closed position.
3.6SCREENS
SPECNOTE:Delete this article if not applicable. Edit to suit project requirements.
.1Provide screens at urinal stalls as indicated on drawings.
.2Provide screens at [washroom] [] entrances, consisting of panels and [floor to ceiling pilasters] [, pilasters and headrails], as indicated on drawings.
.3Anchor screens to wall [and to [posts consisting of tubular headrail stock and end sockets] [pilasters]], with minimum [2] [3] panel brackets or continuous channel bracket per post or pilaster. Anchor posts and pilasters to floor [and ceiling].
SPECNOTE:Screens at urinals are relatively narrow and, where vandalism is not anticipated, are typically secured to walls only.
.4Provide supplementary anchorage above ceiling finish to receive [posts] [ pilasters].
3.7CLEAN-UP
.1Remove protective maskings and clean surfaces, leaving them free of oil and imperfections.
.2Field touchup of scratches or defaced enamel finish will be permitted only if approved by the Minister. Otherwise defective materials shall be rejected and replaced with new materials.
3.8SCHEDULE
SPECNOTE:Schedule may be deleted if project requires only one type of anchorage and only one colour/pattern. Edit schedule to suit project requirements.
Location / Function / Anchorage Type / Colour/PatternRm. [] / Toilets / [Overhead braced] / []
[Ceiling hung]
[Floor anchored]
Rm. [] / Showers / [Overhead braced] / []
[Ceiling hung]
Rm. [] / Dressing / [Overhead braced] / []
[Ceiling hung]
[Floor anchored]
Rm. [] / Urinal screens / [As specified] / []
Rm. [] / Privacy screens / [As specified] / []
Rm. [] / [] / [] / []