After Market Utility Power Equipment Brokerage
Mailto:
Turbine URL: http://CFASPower.com/Index.html
Reciprocating URL: http://CFASPower.com/Recips.html
GTG_1589BL_Cat3516.doc
11 x New Cat 1840Kw 60Hz Utility Grade Module Diesel Generator Sets
CONTENTS
System Overview 3 Main Generator Diesel Skid 3 Main Generator Diesel Engines 3 Instrument, Alarms and Automatic Start/Stop System 4 Main Generator Diesel Control Panel 4 Main Generators 5 Instrumentation & Control 5 Containerized Diesel Generator Sets 6 Emergency 440V Power Distribution Panel 7 Emergency Power Distribution Diagram - 440V 690V (but could be regulated @. 600v )Hyundai Generators Diagram 8 440V Hyundai Generators Diagram 9 Seller’s Procedures & Disclosure 10
Asking Price: US $5.5MM
Download Drawings Pdf
SYSTEM OVERVIEW
Genset Package
Containerized CAT 3516B Generator sets.
Generators are Lloyds Marine Certified Complete with all Controls and Switchgear. All Units are set up for land or marine use application. All Units are NEW 2008, never put into service, warranty transferable.
Product as follows:
· 8 / ea. Units 3516B rated @ 1,840-kW cont. 600 volt 60 HZ @ 1,800 rpm Hyundai Generators
· 3 / ea. Units 3516B rated @ 1,840-kW cont. 440 volt 60 HZ @ 1,800 rpm Hyundai Generators
· 1 / ea. Unit 3412C rated @ 500-kW emergency standby 440 volt 60 HZ @ 1,800 rpm CAT SR4B Generator
· 1 / ea. NEW CAT Synchro System for Gensets.
· General description of CAT / Hyundai Package Containerized Generator sets:
Main Engines:
· 8 / ea. 1,840-KW Prime 690 Volt Caterpillar Diesel Hyundai Generator Skids, Containerized equipped with ventilation insulation and exhaust.
Auxiliary Systems:
· 3 / ea. 1,840-kW Prime 440 Volt Caterpillar Diesel Hyundai Generator Skids, Containerized equipped with ventilation insulation and exhaust.
Emergency Systems:
1 / ea. 500-kW Prime 440 Volt Cat Diesel Cat Generator Skid, Containerized equipped with ventilation insulation and exhaust.
Main Generator Diesel Skid:
· Eight [8] Containers of A-0 in walls and roof to be delivered for Eight [8] Diesel Engine and Generator Skids for supply of Electrical Power 2,300 kVA, 690 V, 60 Hz.
· Free access distance between engine/generator and container walls to be preferable 600mm.
· Each Container shall have Two [2] A-0 Sliding Doors. One door installed on each side of the container. When the
· containers are placed alongside each other, the sliding doors to meet for entering from one container to the next one. The
· doors are not to protrude outside the container.
· Each Container has a Ventilation System with registers in and out.
· The Containers are arranged as separate Engine Rooms with Fuel System, external top-mounted Exhaust System, Lube Oil System, Cooling Water System based on Air-Cooled Radiator System with Internal Radiators, Starting System, Bilge System, Light, Fire Fighting System, Instrument, Alarms and Automatic Start/Stop System according to class requirement. Brackets for installation of Fire/Flame Detectors to be installed.
· Lifting Eyes for Chain Blocks are installed above all Diesel Engines in container for maintenance work such as lifting in/out pistons or cylinder liners.
· All of the Containers are supplied with One [1] set of Standard Tools for maintenance of the Diesel Engines. Tools are located at wall-mounted Tool Panel inside the containers.
· All the Containers are equipped with heating according to Class notation. This is to prevent frost damage of all installed equipment during lay up in winter season with an outside temperature of 20 deg C.
Main Generator Diesel Engines:
· A standard built-on factory supplied Fresh Water Cooling System based on Air-Cooled Radiator System with Fresh Water Pump, Radiator (in machinery space) with Electrical Driven Cooling Fans, Electrical Water Heater with Circulation Pump. (Flexible pipe connections to engine)
· A standard built-on factory supplied Fuel System with Fuel Injection Pump, Fuel Feed Pump, Primary Fuel Filter Duplex Element-Filter with Water Separator, Secondary Fuel Filter, double walled high pressure Fuel Lines, flexible fuel connections, Woodward Pro Act II Actuator mounted on engine, Woodward 2301 D (or similar) Electronic Governor.
· The Fuel Oil System includes: Internal separate A60 insulated Fuel Tank in each container for 8-hours running at 100% load. Internal A60 insulated Fuel Tank for 18-hours running at 100% load installed in the Emergency Diesel Generator Container.
· A standard built-on factory supplied Lube Oil System consisting of direct-driven Lube Oil Pump, Duplex Lube Oil Filter, Bypass Lube Oil Filter, Lube Oil Cooler, Electrical Lube Oil Priming Pump, also prepared to drain the Oil Sump, Starter Cabinets.
· A standard built-on factory supplied dry Exhaust Gas System equipped with Air Inlet Filters, Turbocharger, Charging Air Cooler, insulated Exhaust-Manifold, flexible Expansion Joints, and Exhaust Silencer 35 dBA with Spark Arrestors. Combustion Air Intake is arranged outside.
· Turning Motor or Turning Gear with handle.
· Flexible high elastic coupling fitted to Engine Flywheel and Generator Shaft
· The power stated is valid for conditions in accordance with ISO 3046/1
· Lifting Eyes for transport and installation
· A standard built-in on factory supplied Starting System consisting of Electrical Starting Motors, Charging Rectifier, Starting Batteries in battery boxes separate starting system for each engine.
· The Diesel Engines have a starting battery capacity for a minimum of 3 starts of each engine. The Emergency Generator has a minimum starting battery capacity for a minimum of 6 automatic starting attempts and 3 manual starting attempts.
Instrument, Alarms and Automatic Start/Stop System
Main Generator Diesel Control Panel:
Alarm Sensor for:
· Low Lube Oil Pressure High Lube Oil Temperature High Diff. Pressure over Lube Oil Filter High Water Temperature Low Cooling Water Flow Fuel leaks in double walled Fuel Lines Low Cooling Water Level in Expansion Tank Charging Air Pressure High Exhaust Gas Temperature after Turbocharger
Auto-Stop Device for:
· Low Lube Oil Pressure High Water Temperature Over Speed
Automatic Start and Shut Down System with following functions:
· LCD display showing voltage, rpm, oil pressure and temperature, water temperature, Charge air pressure and exhaust temperature after turbo.
· Automatic start attempts according to class requirement.
· Automatic shutdown for low oil pressure, high water temperature and over speed
· Start Switch
· Stop Switch
· Hour Meter
· Converter for serial communication
· Common Alarm and Shutdown Alarm
· Stop System
· 24 V Stop Solenoid Valve. The Control System includes interface prepared for a Dynamic Position Keeping System and a Power Management System arranged according to Lloyds Rules & Regulations.
Additional Information:-
Diesel Oil:
The Diesel Engine complies with conditions in accordance with ISO 3046/l
Lubricating Oil:
Lubricating oil shall comply with the Diesel Engine manufacturer’s recommendation. Viscosity Class SAE 40 (ISO VG 150). Content of additives should meet the requirements of MIL-L-2104 C or API Service CD.
Turbocharger:
The oil may be mineral oil or synthetic oil having a viscosity of 30-55 cSt/50deg.C.
Caterpillar 3516B Generator Package Page 4 of 10
Output particulars: 8 / ea. Engines: Engine output Min 1,920-kW Output speed: 1,800 rpm
3 / ea. Engines are dedicated to the Auxiliary Power Systems: Engine output Min 1,920-kW Output speed: 1,800 rpm
Main Generators:
All the Generators are supplied with:
· Automatic Voltage Regulator
· Equipment for parallel operation
· Anti Condense Heater
· PT-100 temperature sensors in windings
· PT-100 temperature sensors in bearings
· MCT Brattberg cable entry in container
· Termination Box for power cables
· Foundations.
· All Auxiliary Engines and Emergency Generator are as follows:
· Engines and Generators are lined up on a common steel frame (skid), designed for being lifted in/out of machinery space for transport ashore in case of engine/generator breakdown.
· Vibration Dampers for mounting between skid frame and container floor. This to avoid vibrations in supporting structures.
· Hyundai made Generators to the Diesel Engines are summarized:
· Eight [8] Generators for Prime Power
· Location: Indoors
· Electrical Rating: 1,840-kW
· Speed: 1,800 rpm
· Frequency: 60 Hz
· Power Factor: 0.8
· No of phase: 3 ph
· Supply Voltage: 690 V
· Excitation: Self excited
· AVR: included
· Mounting / Enclosure
· Protection: IP 23
· Bearings: Re-greasable
· Cooling: Air Cooled
· Accessories / Fittings
· Temp sensing: 6 off stator RTD (PT 100) in windings
· 1 off RTD (PT 100) per bearing
· 1 off RTD Cooling air in
· 1 off RTD Cooling air out
· Anti Condensation Heater: 2 x 100 W, 220 V, 1 ph
· Water leakage detection: included
Instrumentation & Control:
· The Eleven [11] Auxiliary Engines are configured to be controlled and monitored from a central Integrated Control System (ICS).
· Interfaces are realized by means of distributed I/O modules communicating over a redundant bus system. Local Control of all main functions for the engines with Auxiliary Systems is included.
· The Control System is laid out also to monitor and interface all critical failures and alarm situations for the Engines, Generators and Auxiliary Systems.
Containerized Diesel Generator Sets
Item List Diesel Generator Sets:
· [8] off 690 Volt CAT Diesel - Hyundai Generator Skids. Containerized equipped with ventilation insulation and exhaust.
· [3] off 440 Volt CAT Diesel - Hyundai Generator Skids. Containerized equipped with ventilation insulation and exhaust.
· [1] off 440 Volt CAT Diesel - CAT Generator Skid. Containerized equipped with ventilation insulation and exhaust.
Emergency 440V Power Distribution Panel:
One [1] Emergency Power Distribution Panel
· Floor-Mounted Cabinet
EMERGENCY POWER DISTRIBUTION PANEL - 440V
EIGHT [8] OFF - 690V HYUNDAI GENERATORS DIAGRAM
THREE [3] OFF - 440V HYUNDAI GENERATORS DIAGRAM
SELLER’S PROCEDURES & DISCLOSURE
PURCHASE • PRICE • INSPECTION TERMS – NEW EQUIPMENT
EQUIPMENT INSPECTION: Any site inspection must have prior approval by the Seller. All prospective buyers need to submit their intent to inspect via written request/letter or email. Seller may request that the buyer show proof of ability of funding through bank authorized Letter of Credit and/or BCL. [Any refundable inspection deposit (subject to inspection and approval) will be refundable minus any showing expenses -such as out of area travel expenses and/or any other pertinent costs associated with the inspection].
PURCHASE PRICE: Purchase Price subject to change with or without notice.
◆PAYMENT: 10% down payment with balance due upon closing of executed Purchase Agreement. All payments must be through Electronic Wire Transfer or Cashiers Check, issued through a US Bank or recognizable/verifiable International Bank. Letters of Credit will not be considered as payment [unless otherwise specified].
BILL OF SALE: No Bill of Sale or changes of ownership shall occur until the Seller has received the full payment of the purchase price.
DELIVERY • SHIPPING: Delivery and shipping costs shall be the sole responsibility of the Buyer. Any price quotes, or pricing discussed, will not include shipping costs. Seller may, at Seller's own discretion, elect to assist buyer in coordinating shipping from the Ex-Works (at site) location of the equipment to the nearest port.
TAXES: Any taxes shall be the sole responsibility of the buyer. Any price quotes, or pricing discussed, will not include any taxes due any authority - both domestic and/or international.
PRIOR SALE: All Equipment subject to prior sale, availability and sold As-Is, Where-Is [unless otherwise specified] on a First-Come, First-Serve basis [with or without notice] as per First Party Wire Transfer.
WARRANTY: ALL WARRANTIES ARE FACTORY ISSUED WARRANTIES IN FULL FORCE AND EFFECT [FULL COVERAGE, LESS MAINTENANCE ITEMS] – As per end user application and approval by OEM.