Based on CSI MasterFormat 2010 & SectionFormat 2008 / SECTION 072115
SEMI-RIGID MINERAL WOOL INSULATION
SECTION 072115
SEMI-RIGID MINERAL WOOL INSULATION
***
This section specifies semi-rigid mineral wool thermal insulation for use in vented/ventilated cavity walls over an air/vapor barrier system as part of a veneer or cladding system with semi-rigid insulation and air/vapor barrier placed over the structural wall assembly.
Semi-rigid mineral wool is hydrophobic (does not absorb water) and is acceptable in lieu of rigid foam insulation for most cases. It may be required for FM Global financed projects at cavity walls.
Curtain wall insulation has been added to this section and could be further developed.
***
PART 1 GENERAL
1.1SUMMARY
***
Edit to project requirements.
***
- Section Includes:
- Semi-rigid mineral woolperimeter cavity wall thermal insulation.
- Semi-rigid mineral wool thermal insulation at curtain wall concealed spaces.
***
Edit related Sections to those referenced in body of specification section.
***
- Related Requirements:
- Section 033000-Cast-in-Place Concrete
- Section 042200-Concrete Unit Masonry
- Section 044219 -Strongback-Frame-Supported Stone Cladding
- Section 044350 -Stone Masonry
- Section 054000-Cold-Framed Metal Framing
- Section 072726-Fluid-Applied Membrane Air-Vapor Barriers
- Section 078400-Firestopping
- Section 084413-Glazed Aluminum Curtain Wall
- Section 084433-Sloped Glazing Systems
- REFERENCES
***
Edit reference standards to those referenced in body of specification section.
***
- Reference Standards: Conform to provision of Section 014219.
- ASTM International (ASTM):
- ASTM C303-Standard Test Method for Dimensions and Density of Preformed Block and Broad-Type Thermal Insulation.
- ASTM C518-Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus.
- [ASTM C553-Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications]
- ASTM C612-Standard Specification for Mineral Fiber Block and Board Thermal Insulation.
- [ASTM C665-Mineral Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing.]
- ASTM C1104-Standard Test Method for Determining the Water Vapor Sorption of Unfaced Mineral Fiber Insulation.
- ASTM C1338-Standard Test Method for Determining Fungi Resistance of Insulation Materials and Facings.
- ASTM E84-Test Method for Surface Burning Characteristics of Building Materials.
- [ASTM E96-Standard Test Methods for Water Vapor Transmission of Materials]
- DEFINITIONS
- Sorption: Refers to the taking up and holding of matter by other matter by various processes such as absorption andadsorption.
- Absorption: Refers to the taking up of matter in-bulk byother matter; for example, the penetration of substances intothe bulk of another solid or liquid.
- Adsorption: Refers to surface retention or adhesion ofan extremely thin layer of molecules to the surfaces of solids orliquids with which they are in contact.
- ADMINISTRATIVE REQUIREMENTS
***
Edit sections to include coordination and sequencing as needed for completion of work.
***
- Coordination: Conform to Section 013113 for coordination with work of other Sections.
- Section 044220 for installation at concrete masonry wall systems.
- Section 044219 for strongback-frame-supported stone cladding anchors installed into structural wall systems and projecting through semi-rigid mineral wool installation.
- Section 054000 for installation between cold-rolled steel girts and other framed wall systems.
- Section 072726 for coordination with installation of fluid-applied membrane air-vapor barriers.
- Section 084413 for mineral wool at curtain wall insulation [including spandrel panels and other concealed locations].
- Section 084413 for sloped glazing insulation.
- SUBMITTALS
- Submit under provisions of Section 013300.
- Product Data:Indicate product characteristics, performance criteria, and limitations.Include thermal resistance information.
- Test Data: UL certified test data for Class A.
- QUALITY ASSURANCE
- Provide thickness and R-Values shown on Drawings.
- DELIVERY, STORAGE, AND HANDLING
- Conform to provisions of Section 01657.
- Deliver insulation board in manufacturer’s protective packaging, labeled as to manufacturer, product, material, and product characteristics including thermal resistance, thickness, density, and applicable code compliance tests.
- Store materials in clean, dry place.
- Remove Plastic cover packaging from insulation board to allow ventilation.Cover to protect from as necessary moisture and damage.
- WARRANTIES
- Conform to Warranty provisions specified Section 017836.
- Manufacturer: Standard 3 year warranty against defectsin materials.
PART 2 PRODUCTS
***
Verify manufacturer availability at project location and contact information.
***
2.1MANUFACTURERS
- Semi-Rigid Mineral Wool:
- Thermafiber.
- Tel (503) 775-0438, Cell (503) 887-3109, Voice Mail 1-888-834-2371 Ext 290, Email (Jim Giger, Sales Mgr, Western North America). Local Representative: Dave Sommer Tel: (206) 226-2311 email:
- Tel 1-888-834-2371, Ext 290, Email Jim Shriver(Director of Technical Services)
- Tel 1-888-834-2371, Ext 295, Email: (Angie Ogino, Technical Mgr).
- Tel 1-888-834-2371, Ext 216 (Customer Service).
- Web Site
- Roxul, Inc.
- Cell (253) 561-4176, Tel (360) 886-5240, Email (JakeErickson, US Western Region Sales Mgr)
- Cell (905)699-4844-, Email (Rockford Boyer, Building Science & Codes Specialist).
- Cell (281) 979-6824, Email (Cary Roberson, PE, US National Sales Mgr)
- Web Site
- [Rock Wool Manufacturing Company, Delta.
- Tel (205) 699-6121
- Web Site ]
- [IIG Industrial Insulation Group.
- Tel 1800-444-4380 (Technical Information).
- Web Site
- Insulation Anchors:
- HILTI, Inc.
- Tel 1-800-879-8000 (Main Office).
- Web Site
***
OR
***
- Impaling Pins:Perforated Base Insulation Hangers.
- AGM Industries, Inc.,
- Tel 1-800-225-9990.
- Web Site
- Substitution Requests: Submit under provisions of Section 012500.
- REGULATORY REQUIREMENTS
- Conform to provisions of Section 014100.
- Mineral Wool Insulation at Fire-Resistive Assemblies: Classified by ULor other independent testing agency, approved by authorities having jurisdiction.
- PERFORMANCE CRITERIA
- Semi-Rigid Mineral Wool.
- Density: 4 psf [8 psf] as tested to ASTM C303.
- Surface Burning Characteristics: UL 723 Class A or IBC Class A, as tested to ASTM E84.
- Flame Spread: 0.
- Smoke Developed: 0.
- Combustion Characteristics: Passes ASTM E136, non-combustible.
- R-Value per Inch: Tested to ASTM C518.
- R - 4.2per inch thick at 75 degrees F.
- R - 10.4 at 2-1/2 inch thick at 75 degrees F.
- Moisture Resistance:
- Hydrophobic Treatment: Non-hydroscopic (does not absorb or hold water).
***
0.3 percent sorption is typical but ASTMC1104 specifies less than 1 percent.
***
- Sorption: 0.3 [Less than 1] percent or less, as tested to ASTM C1104.
- Absorption: Less than 1 percent, as tested to ASTM E136.
- Fungi and Bacteria: Does not promote growth, tested to ASTM C1338.
- Corrosion Resistance: Conform to ASTM C665.
- SEMI-RIGID MINERAL WOOLINSULATION BOARD
***
Mineral wool insulation is typically specified as unfaced. Facing may lower use temperature. Consult with manufacturer and define facing type when specified.
***
- Cavity Walls: ASTM C612, Type IVB, Category 1, Unfaced [Faced].
- Thermafiber.
- FireSpan 40, 4 pcf density.
- [FireSpan 90, 8 pcf density]
- Roxul:
- CavityRock, 4.4 psf density. Available in 16 by 48 inch and 24 by 48 inch sizes.
- [RockBoard 80, 8 pcf density]
- Delta:
- DELTA-CW4A Board, 4 pcf density. Available in 24 by 48 inch and 36 by 48 inch sizes.
- [DELTA-CW8A Board, 8 pcf density]
- Curtain Walls: ASTM C612 Type1A through Type IV, Category 1, Unfaced.
- INSULATION ANCHORS
- Concrete and Masonry:
- HILTI, IDP Insulation Anchor: IDP 6/8, and as instructed by manufacturer.
- Material: Polypropylene (Cover anchor head where exposed to direct sunlight).
- Insulation Thickness: 2-1/2[______] inch.
- Bit Diameter: 5/16 inch.
- Minimum Embedment: 1-1/8 inch.
- Average Ultimate Pull-Out:
1)Concrete: 110 pounds.
2)Concrete Unit Masonry: 45 pounds.
***
Verify - not found on Hilti Web Site
***
- [HILTI, XCR-L 72 P8S23 (Item #237454), powder actuated fastener with integral washer.
- Fastener Material: AISI Type 316 stainless steel.
- Washer Material: AISI Type 304, 16 gauge stainless steel,
- Pin Length: 2-7/8 inch.
- Shank Diameter: 0.145 inch.
- Washer Diameter: 0.905 inch.
- Conforming to ICC-ES AC70.]
***
Verify - not found on Hilti Web Site
***
- [Cold-Formed Steel Stud Framing:
- Fastener: HILTI, Kwik Flex, self-drilling screw, hex-head, Kwik-Cote corrosion-resistant finish, specified for type and quality. Conforming to ICC-ES ER-4780.
- Washer: Minimum 1 inch diameter, stainless steel or UV-resistant plastic, as accepted by Architect.]
***
Impaling pins are an option that could be used instead of fastening system specified by this Section. Verify use with manufacturer.
***
2.6IMPALING PINS
- AGM Industries, [TACTOO Perforated Base Insul-Hangers, specified for type andquality].
- Impaling Spindle:
- Minimum 12 gauge mild steel with corrosion resistant coating.
- 1/2 inch longer than thickness of insulation board and as required to suite installation.
- Base Plate: [Stainless][Galvanized]steel, perforated.
- Self Locking Washers:[Stainless] [Galvanized] steel.Size and type capable of securely and rigidly fastening insulation board in place and supporting insulation board weight.Assume 3 pounds maximum weight per hanger assembly.
- Impaling Pin Adhesive:
- AGM, TACTOO, Adhesive GPA-72.
- Mon-Eco Industries, Inc., MEI Eco-Hanger Grip Adhesive.
- ACCESSORIES
- Provide miscellaneous and accessory materials, fasteners, adhesives, tools, and equipment as needed for completion of insulation board work.
- Clips and Fasteners: As required to hold mineral fiber rigid insulation board in place.
- Construction Tape: Owens Corning, BILD-R-TAPE, nominal 2 inch wide, waterproof, pressure sensitive, UV resistant sealing tape, specified for type and quality.
PART 3 EXECUTION
3.1EXAMINATION
- Verify installation conditions as satisfactory to receive work of this Section.
- Verify substrates dry and free of oils, dirt, particulates, spalls, and other bond breakers and conditions unsuitable for permanent installation.
- PREPARATION
- Install strong-back wall anchor system components to project through installed insulation prior to beginning work of this Section.
- INSTALLATION
- Conform to manufacturer's instructions and provisions of Contract Documents.
- Install semi-rigid mineral wool insulation over [fluid-applied] air/vapor barriermembrane, specified by Section [072726].
- CAVITY WALL SEMI-RIGID MINERAL WOOL INSULATION FASTENERS AND WASHERS
- Install insulation fastenersand washers as follows and as instructed by manufacturer and manufacturer’s ICC-ES Report.
- Maximum 16 inch on center each way, 4 inch from edge of insulation, and as necessary to support weight of insulation board.
- Minimum 1-1/8 into concrete and concrete unit masonry.
- Minimum 3/8 into cold-formed metal framing.
- Install semi-rigid mineral wool to fit snugly against adjacent joints, framing, and other adjacent constructionand tape joints to form a uniform thermal barrier.
***
Impaling pins are an option. Verify method with manufacturer instructions and project requirements.
***
3.5[CAVITY WALL SEMI-RIGID MINERAL WOOL INSULATION INSTALLED WITH IMPALING PINS
- Install impaling pins to concrete, concrete unit masonry, and wall sheathing at cavity walls prior application to fluid-applied air/vapor barrier membrane.
- Install impaling pins at maximum 16 inch on center each way, 4 inch from edge of insulation, and as necessary to support weight of insulation board.
- Apply adhesive to perforated base plate, twist, and press firmly into place.
- Install semi-rigid mineral wool to fit snugly against adjacent semi-rigid insulation, framing, and other construction.
- When insulation is in place, install retainer clips and slightly compress, as needed to maintain insulation in complete contact with wall substrate.
- Clip or cut pins within 1/2 inch of retainer pins.]
- CURTAIN WALL SEMI-RIGID MINERAL WOOL INSULATION
***
Specify additional requirements for curtain wall at spandrels and within concealed spaces in curtain wall above floor slab as required to prevent flames from jumping from floor to floor through curtain wall system.
Mineral wool is a better choice than semi-rigid fiberglass at curtain wall subject to fire exposure.
Specify firestopping at open space between curtain wall and perimeter floor slab under Section 078400.
***
- [Insulation System: Classified by UL, or other independent testing agency approved by authorities having jurisdiction.]
- [Curtain Wall Perimeter Fire Containment System:] [2 hour].
- [ ]
- Install as fire-resistive rated insulation at curtain wall, specified Section 084413[in lieu of] [, as option to]fiberglass semi-rigid curtain wall insulation,[and as shown on Drawings].
- Install and fit tightly at curtain wall locations as required to thermally insulate curtain wall panels and as a fire-resistive containment system against hot air and flame movement between floor levels.
- Install to fit tightly and continuously at spandrel panels.
- Mechanically fasten in place using clips and attachments designed and suited for purpose.
- OTHER SEMI-RIGID MINERAL WOOL INSTALLATIONS
- Tightly pack construction voids at interior wall, floor, and ceiling concealed spaces.
- Use in conjunction with metal form closure strips at steel stud construction [specified Section 053100][or][blocking at wood framed construction][, specified by Section 061000].
- Tightly pack steel decking flute voids spanning over acoustical and exterior walls.
- FIRE STOPPING ANDFIRE SAFING
- Conform to Section 078400 where firestopping is required at construction joints to maintain fire-resistive rated wall and floor assemblies.
- Do not use as fire-safing to meet fire-stopping requirements, except as provided under work of Section 078400.
- ADJUSTING
- Repair and replace installations that do not make a continuous thermal enclosure. Tape and seal joints and other locations to provide closure and prevent thermal wicking.
- CLEANING
- Leave installation clean and free from debris and residue resulting from work of this Section.
END OF SECTION