The following Safety Message was issued today, Friday 17 January 2003. Can
you forward it to all CECOM LARs world-wide.
Subject: CECOM GROUND PRECAUTIONARY MESSAGE (GPM) (CECOM GPM 2003-007);
15KW AND 30KW DIESEL ENGINE DRIVEN, GENERATOR SETS: SEE PARAGRAPH
Importance: Low
UNCLAS
SUBJECT:CECOM GROUND PRECAUTIONARY MESSAGE (GPM)
(CECOM GPM 2003-007); 15KW AND 30KW DIESEL ENGINE DRIVEN, GENERATOR
SETS: SEE PARAGRAPH 2C FOR COMPLETED LISTING.
*********************************************************************
* WARNING: *
* IF ACTIONS SPECIFIED IN THIS MESSAGE ARE NOT IMPLEMENTED *
* SERIOUS PERSONNEL INJURY COULD OCCUR! *
*********************************************************************
DISTRIBUTION: NOTE THIS IS A GPM AND HAS NOT BEEN TRANSMITTED
TO YOUR SUBORDINATE UNITS. MACOM COMMANDERS WILL
IMMEDIATELY RETRANSMIT THIS MESSAGE TO ALL SUBORDINATE
UNITS, ACTIVITIES, OR ELEMENTS AFFECTED OR CONCERNED.
RETRANSMITTAL SHALL REFERENCE THIS MESSAGE. MACOM
COMMANDERS WILL IMMEDIATELY VERIFY AND RETRANSMIT THIS
MESSAGE VIA DMS TO:
C:US,O:U.S.Government,OU:DoD,OU:Army,OU:Organizations,
L:CONUS,L:FORT MONMOUTH NJ,OU:CECOM STAFF,OU:SAFETY, OU:DIR
SAFETY MONMOUTH(n).
1. REFERENCES.
A. OPERATOR AND ORGANIZATIONAL MAINTENANCE MANUALS FOR:
15KW, DIESEL ENGINE DRIVEN, GENERATOR SET, MEP-004A, MEP-103A
AND MEP-113A: ARMY TM5 6115-464-2, AIR FORCE TO-35C2-3-445-1,
MARINE CORPS TM 07523A-12; 30KW.
DIESEL ENGINE DRIVEN, GENERATOR SET: MEP-005A, MEP-104A AND
MEP-114A: ARMY TM5 6115-464-12, AIR FORCE TO-35C2-3-446-1, MARINE
CORPS TM -06858B/06859D-12
60KW, DIESEL ENGINE DRIVEN, GENERATOR SET: MEP-006A, MEP-105A
AND MEP-115A: ARMY TM5 6115-545-12, AIR FORCE TO-35C2-3-444-1,
MARINE CORPS TM 00386-12.
2. PROBLEM DISCUSSION.
A. SUMMARY: THERE IS A POTENTIAL TO COME IN CONTACT WITH
ROTATING FAN BLADES WHILE TIGHTENING OR LOOSENING THE FUEL
LINE AT THE INJECTOR, DURING INJECTOR TESTING.
B. FINDINGS: THE INJECTOR TEST MUST BE PERFORMED WHILE THE
ENGINE IS RUNNING SO THAT THE TESTER CAN HEAR CHANGES IN THE
ENGINE AS THE FUEL LINE IS LOOSENED. A WARNING NEEDS TO BE
ADDED TO THE PROCEDURE IN THE TECHNICAL MANUALS ABOUT THE
HAZARD OF THE ROTATING FAN BLADES.
C. ITEMS AFFECTED: 15KW, DIESEL ENGINE DRIVEN, GENERATOR SET:
MEP-004A, NSN 6115-00-18-1241, MEP-103A, NSN 6115-00-118-1425, MEP-
113A, NSN 6115-00-118-1244; 30KW, DIESEL ENGINE DRIVEN, GENERATOR
SET: MEP-005A, NSN 6115-00-118-1240, MEP-104A, NSN 6615-00-118-1247,
MEP-114A, NSN 6615-00-118-1248; 60KW, DIESEL ENGINE DRIVEN,
GENERATOR SET: MEP-006A, NSN 6115-00-118-1243, MEP-105A, NSN
6615-00-118-1252, MEP-115A, NSN 6615-00-118-1253.
3. USER ACTIONS: STRICTLY OBSERVE TO THE FOLLOWING WARNING:
WHEN PERFORMING THE INJECTOR TEST, USE CARE TO PREVENT
HANDS FROM COMING INTO CONTACT WITH THE ROTATING FAN
BLADES. FAILURE TO OBSERVE THIS WARNING MAY CAUSE PERSONAL
INJURY.
4. PM/CECOM ACTIONS: THE WARNING WILL BE ADDED TO THE
APPLICABLE MANUALS AT THE NEXT REVISION.
5. POCS: FOR QUESTIONS REGARDING THIS MESSAGE:
A. TECHNICAL POINT OF CONTACT: MR. RICHARD G. RUSSELL, CECOM,
POWER AND ENVIRONMENTAL DIVISION, DSN 654-3367, CML(703)704-
3367, MILNET ADDRESS:
B.LOGISTICS POINT OF CONTACT: MR. GREG YOULL, CECOM LRC,
DSN 992-4748, CML (732)532-4748; MILNET ADDRESS:
MS. KIM M. GORE, PM-MEP, DSN 654-3469, CML (703) 704-3469; MILNET
ADDRESS:
C. SAFETY POINT OF CONTACT: GAINES C. HO, CECOM
DIRECTORATE FOR SAFETY, DSN 654-2093, OR CML (703)704-2093;
MILNET ADDRESS:
6. THIS MESSAGE HAS BEEN COORDINATED WITH PM-MEP, CECOM
POWER AND ENVIRONMENTAL DIVISION, AND THE CECOM LRC.