BACnetSoftware Index
1. N3BACnet Programmable Functions List
A163: BACnetThe Station Number: 1 - 254A163: to set theBACnetthe station codes (TS) which are suitable for driving multi drop
situations on inverter networks.
A164: Baud Rate setting (bps): 0000: 48000001: 9600
0002: 19200
0003: 38400
A165: Stop Bit Selection: 0000:1 stop bit
0001:2 stop bit
A166: Parity Selection : 0000 :no parity
0001 : even parity
0002 :odd parity
A167: Data Format Selection: 0000 :8 bit data
0001 :7 bit data
1. RS-485 Communication:
(1)1 vs. 1 Control: to control one inverter by a PC or PLC or controller.(set A163 = 1~254)
(2)1 vs.Multiple Drop Control: to control more than one inverter by PC, PLC, or HostController.
2. RS-232communication: (RS232 interface is required)
(1)1vs1 control only: to control one inverter by a PC, PLC, or controller. (Set A163 = 1~254)
※Note:
a. The BAUD RATE (A164) of PC (or PLC or Controller) has to match the inverter baud rate setting.
Communication format (A165/A166/A167) should also be set as the same.
b. The inverter will confirm andacknowledge commands as PC modifies the parameters of theinverter.
A173: MODBUS / BACnet Selection: 0 - 1A173 : to set the communication mode
(1). Select 0 to choice Modbus mode
(2). Select 1 to choice BACnet mode
A174: BACnetDevice InstanceNumber: 1 - 254A174: to set the BACnetDevice Instance codes which are suitable for setting everyequipmentnumber.
PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT
BACnet Protocol Implementation Conformance Statement
Date: July 1 , 2011
Vendor Name: TECON3
Product Name: TECO N3
Product Model Number: N3
Applications Software Version: V1.4 Firmware Revision: V1.4 BACnet Protocol Revision: 5
Product Description:
The TECO N3 Drives is high performance products specifically designed for commercial automation application. The TECO N3 has a standard BACnet MS/TP network. This product may be controlled and monitored over BACnet. Some drive parameters are available for reading and writing.
BACnet Standardized Device Profile (Annex L):
BACnet Smart Actuator (B-SA)
List all BACnetInteroperabilityBuilding Blocks Supported(Annex K):
K.1.2 BIBB – Data Sharing – ReadProperty – B (DS–RP–B)
K.1.8 BIBB – Data Sharing – WriteProperty – B (DS–WP–B)
K.5.2 BIBB – Device Management – Dynamic Device Binding – B (DM–DDB–B)
Standard Object Types Supported:
■Device Object
■Analog Input■Analog Output■ Analog Value
■Binary Input■BinaryOutput■ BinaryValue
1. Whether objects of this type are dynamically creatable using the Create Object service.
CreateObject service is not supported.
2. Whether objects of this type are dynamically creatable using the Delete Object service.
DeleteObject service is not supported.
3. List of optional properties
See Table 1.1 – Objects and Properties Supported
4. List of all properties that are writable where not otherwise required by this standard
See Table 1.1 – Objects and Properties Supported
- List of proprietary properties and for each its property identifier , data , type and meaning
See Table 1.2 to Table 1. 9
- List of any property range restrictions
See Table 1.3 to Table 1. 9
Data Link Layer Option:
BACnet IP (Annex J)
BACnet IP (Annex J) Foreign Device
ISO8802–3 Ethernet (Clause 7)
ANSI/ATA 878.1, 2, 5Mb ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
MS/TP master (Clause 9), baud rate(s) :
MS/TP slave (Clause 9),baud rate(s) : 9600 , 19200 , 38400
Point-to-Point, EIA 232 (Clause 10) baud rate(s)
Point-to-Point modem (Clause 10) baud rate(s)
LonTalk (Clause 11) medium
Other
Device Address Binding:
Not supported.
Networking Options:
Router (Clause 6) – List all routing configurations
Annex H – BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by foreign devices? □Yes □No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI X3.4 IIBM/Microsoft DBCSISO 8859-1
ISO 10646 (UCS - 2)ISO 10646 (UCS – 4)JIS C 6626
If this product is a communication gateway, describe the types of non-BACnet equipment / network(s) that the gateway supports:
N/A
Table 1.1 – Objects and Properties Supported
Property / Device(DEV) / Analog
Input
(AI) / Analog
Output
(AO) / Analog
Value
(AV) / Binary
Input
(BI) / Binary
Output
(BO) / Binary
Value
(BV)
Object_Identifier / V / V / V / V / V / V / V
Object_Name / V / V / V / V / V / V / V
Object_Type / V / V / V / V / V / V / V
System_Status / V
Vendor_Name / V
Vendor_ Identifier / V
Model_Name / V
Firmware_Revision / V
Applocation_Software_Supported / V
Protocol_Version / V
Protocol_Revision / V
Protocol_Services_Supported / V
Protocol_Object_Type_Supported / V
Object_List / V
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
Max_Masters / V
Max_Info_Frames / V
Device_Address_Binding
Location / V
Presnent_Value / V / V / V / V / V / V
Status_Flags
Event_State
Relibility
Out_Of_Service
Units / V / V / V
Priority_Array
Relinquish_Default
Polarity
Inactive_Text
Active_Text
Table 1.2 – List of device Properties
Property / Device(DEV)
Object_Identifier / DEV
Object_Name / TECO N3
Object_Type / 8
System_Status / 0
Vendor_Name / TECO N3
Vendor_ Identifier / 461
Model_Name / TECO.Inc
Firmware_Revision / 1.4
Applocation_Software_Supported / 1.4
Protocol_Version / 1
Protocol_Revision / 5
Protocol_Services_Supported / { readProperty , writeProperty , who is }
Protocol_Object_Type_Supported / { Analog_Input , Analog_Output, Analog_Value
Binary_ Input, Binary_Output, Binary_Value, Device}
Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
Max_Masters / 127
Max_Info_Frames / 1
Device_Address_Binding
Location / U.S.A
Presnent_Value
Status_Flags
Event_State
Relibility
Out_Of_Service
Units
Priority_Array
Relinquish_Default
Polarity
Inactive_Text
Active_Text
Table 1.3 – List of AnalogInput Properties(READ)
Instance ID / Object Name / Description / Unit / Present_ValueAccess Type / range restrictions
AI0 / TM2 AIN / AIN / Volt / R / 0 - 10
AI1 / TM2 AIN2 / AlN2 / Volt / R / 0 - 10
AI2 / Error code / Error Description / No Units / R / 0 – 45
AI3 / Freq cmd / Speed Control / HZ / R / 0 - 60
AI4 / Frequency / Output Frequency / HZ / R / 0 - 60
AI5 / Current / Output Current / Amps / R
AI6 / Control Mode / Control Mode / No Units / R / 0 - 2
AI7 / Motor R-Volt / Motor Rated Voltage (Vac) / Volt / R
AI8 / Motor R-HP / Motor Rated Power (HP) / horsepower / R
AI9 / Motor R-RPM / Motor Rated Speed (RPM) / No Units / R
AI10 / Motor R-Hz / Motor Rated Frequency (Hz) / HZ / R
AI11 / ResetMode / Reset Mode Setting / No Units / R / 0 - 1
AI12 / CarrierFreq / Carrier Frequency (kHz) / KiloHertz / R / 4 - 16
AI13 / Comm Station / Comm Station Number / No Units / R / 1 - 254
AI14 / BaudRate / Baud Rate Setting (bps) / No Units / R / 0 - 3
AI15 / BacnetSel / MODBUS/Bacnet select / No Units / R / 0 - 1
AI16 / DevInstance / Bacnet Device Instance / No Units / R / 1 - 254
Table 1.4 – List of Analog Output Properties(READ/WRITE)
Instance ID / Object Name / Description / Unit / Present_ValueAccess Type / range restrictions
AO0 / Set frequency / Set frequency / HZ / R/W / 0 - 60
AO1 / FM+ / Analog output / Volt / R / 0 - 10
AO2 / Motor R-Amp / Motor Rated Current (Amp) / Amps / R/W / 0-65535
AO3 / Starting Sel / Starting Method Selection / No Units / R / 0 - 1
AO4 / PwrL Sel / Momentary Power Loss and Restart / No Units / R / 0 - 2
AO5 / PwrL T / Momentary Power Loss Ride-Thru Time (Seconds) / seconds / R / 0 – 2
AO6 / DirStartSel / Direct Run After Power-Up / No Units / R / 0 - 1
AO7 / DirStartDelay / Delay-ON Timer (Seconds) / seconds / R / 0 - 300
AO8 / Auto Restart / Auto Restart Method / No Units / R / 0 - 1
AO9 / RestartSel / Number of Auto Restart Attempts / No Units / R / 0 – 10
AO10 / RestartDelay / Auto Restart Delay Time (Seconds) / seconds / R / 0 - 800
AO11 / FreqCommand1 / Frequency Command 1 (Hz) / HZ / R/W / 0 - 400
AO12 / FreqCommand2 / Frequency Command 2 (Hz) / HZ / R/W / 0 - 400
AO13 / FreqCommand3 / Frequency Command 3 (Hz) / HZ / R/W / 0 - 400
AO14 / FreqCommand4 / Frequency Command 4 (Hz) / HZ / R/W / 0 - 400
AO15 / FreqCommand5 / Frequency Command 5 (Hz) / HZ / R/W / 0 - 400
AO16 / FreqCommand6 / Frequency Command 6 (Hz) / HZ / R/W / 0 - 400
AO17 / FreqCommand7 / Frequency Command 7 (Hz) / HZ / R/W / 0 - 400
AO18 / FreqCommand8 / Frequency Command 8 (Hz) / HZ / R/W / 0 - 400
AO19 / RunSource / Run Command Source Selection / No Units / R/W / 0 - 2
AO20 / RunMode / Run/Stop-Forward/Reverse Operation Mode with External Terminals / No Units / R/W / 0 - 2
AO21 / ReverseOper / Reverse Prohibit operation / No Units / R/W / 0 - 1
AO22 / StoppingSel / Stopping Method Selection / No Units / R/W / 0 - 1
AO23 / FrequenceComm / Frequency Command Source Selection / No Units / R/W / 0 - 5
AO24 / FreqUpperLim / Frequency Upper Limit (Hz) / HZ / R/W / 0 - 400
AO25 / FreqLowerLim / Frequency Lower Limit (Hz) / HZ / R/W / 0 - 400
AO26 / Acc Time1 / Acceleration Time # 1 (Seconds) / seconds / R/W / 0 - 3600
AO27 / Dec Time1 / Deceleration Time # 1 (Seconds) / seconds / R/W / 0 - 3600
AO28 / Password / Parameter Lock(except B010) / No Units / R/W / 0 - 1
Table 1.5 – List of AnalogValue Properties(READ/WRITE)
Instance ID / Object Name / Description / Unit / Present_ValueAccess Type / range restrictions
AV0 / PID – P Gain / Proportional Gain / No Units / R/W / 0 - 10
AV1 / PID – I Time / I Time / No Units / R/W / 0 - 100
AV2 / PID – D Time / D Time / No Units / R/W / 0 – 10
Table 1.6 – List of Binary Input Properties(READ)
Instance ID / Object Name / Description / Inactive / Active / Present_ValueAccess Type / range restrictions
BI0 / Run/Stop / Indicates whether the drive is running or stopped / Stop / Run / R / 0 - 1
BI1 / Direction / Indicates whether the drive’s Direction is FWD or REV / FWD/REV / R / 0 - 1
BI2 / ststus / Inverter operation prepare state / OK/Fault / R / 0 - 1
BI3 / Abnormal / Indicates if a fault is active / Close/Open / R / 0 - 1
BI4 / DI_1 status / S1 status / Close/Open / R / 0 - 1
BI5 / DI_2 status / S2 status / Close/Open / R / 0 - 1
BI6 / DI_3 status / S3 status / Close/Open / R / 0 - 1
BI7 / DI_4 status / S4 status / Close/Open / R / 0 - 1
BI8 / DI_5 status / S5 status / Close/Open / R / 0 - 1
BI9 / DI_6 status / S6 status / Close/Open / R / 0 - 1
Table 1.7 – List of Binary Output Properties (READ/WRITE)
Instance ID / Object Name / Description / Inactive / Active / Present_ValueAccess Type / range restrictions
BO0 / RY1 status / Relay Output 1 status / Close/Open / R / 0 - 1
BO1 / RY2 status / Relay Output 2 status / Close/Open / R / 0 - 1
Table 1.8 – List of Binary Value Properties (READ/WRITE)
Instance ID / Object Name / Description / Inactive / Active / Present_ValueAccess Type / range restrictions
BV0 / RUN/STOP / RUN/STOP / Stop / Run / R/W / 0 - 1
BV1 / FWD/REV / FWD/REV / FWD/REV / R/W / 0 - 1
Table 1.9 AI2 - Error Description
Error number / Object Name / Description0 / Normal / The inverter is normal
1 / CPF / Program abnormal
2 / EPR / EEPROM abnormal
3 / OV / Over voltage
4 / LV / Under voltage
5 / OH / Inverter over heat
10 / OC-D / Proportional Gain
11 / OC-A / Over current during decelerating
12 / OC-C / Over current during accelerating
13 / OV-C / Over current at constant speed
14 / OH-C / Inverter over heat at constant speed
15 / OVSP / Inverter over speed
16 / CTER / CPU interrupted
17 / OC_S
20 / OC / Over current at stop
21 / OL1 / Motor over load
22 / OL2 / Inverter over load
23 / OL3 / Over torque detected
24 / LV-C / Under voltage during running
30 / STP0 / Stop at 0 Hz
31 / STP1 / Direct start disable
32 / STP2 / Control panel emergency stop
33 / E.S / Emergency stop
34 / bb / External BB
35 / ATER / Auto testing error
36 / PDER / PID feedback signal loss
37 / EFO / Communication error
38** / ECER** / Encoder signal loss **
39 / Err4 / Analog converting error
40 / LOC / Parameter locked
41 / Err1 / Keypad operation error
42 / Err2 / Parameter setting error
43 / Err5 / Modifying the parameter incommunication
44 / Err6 / Communication failure
45 / Err7 / Parameter setting error