TARGET CORP

T-1849 TARGET

ATLANTIC TERMINAL

SUMMARY

The Target Store T-1849 at the Intersection of Flatbush Ave. and Atlantic Blvd., Atlantic Terminal in Brooklyn, NY. was inspected by Thomas Branham of Elevator Consulting Services, Inc. on May 6, 2015 to assess the equipment reliability and status. My QEI number is 1339 and am certified by NAESA. NAESA is the National Association of Elevator Safety Authorities. We have identified corrective items that in our opinion need to be addressed by the Elevator Contractor. They are free to offer an explanation or dispute any individual item within the report but we can offer a reasonable reason for each and every negative evaluation. They are evaluated on and for the ASME 17.2 Code for Inspectors Manual and industry standards for acceptable installation and maintenance procedures.

Store #: 718-290-1109 - TSC desk, Need when you go on the roof and you want to get back in, call this number for an LOD to reopen door..

Service Vendor: TEI

PMT – Michael 314-940-9530

Note: ILO – Inside Looking Out

OLI - Outside Looking In

Items in red suggest a higher degree of urgency to get resolved. May be a reliability, callback or safety issue that should be resolved quickly. .


T-1849 ATLANTIC TERMINAL

FREIGHT ELEVATORS 7, 8, 9

CORRECTIVE ITEMS

The following minimum items need corrective action taken. Documentation of completion is required.

CITY ID 7 – 3F6062 5 YR TEST 7 – 6-12 ANL Test 7 – 7-14

8 – 3F6063 8 – 6-12 8 –7-14

9 – 3F6064 9 – 6-12 9 – 7-14

Note: Cars 7 & 8 were shut down so some items in report could not be checked. They were left on based on balance of duplicate items.

Elevator 7

1.  Adjust leveling at G level, stops short ½”. REPEAT REQUEST
Date Completed ______Initialed ______

2.  Replace emergency light bulbs. REPEAT REQUEST
Date Completed ______Initialed ______

3.  Adjust leveling in down direction, short of floors ¾”. REPEAT REQUEST
Date Completed ______Initialed ______

4.  Secure all hoistway door tracks, several bolts are missing nuts. REPEAT REQUEST
Date Completed ______Initialed ______

5.  Flush all gate chains, front and rear, with WD-40 and wipe off excess. REPEAT REQUEST
Date Completed ______Initialed ______

6.  Provide a beam pad for the 2nd floor divider beam and tape the traveling cable, worn traveling cable jacket. REPEAT REQUEST
Date Completed ______Initialed ______

13.  Repair the position indicator in the fire command station to proper working order. REPEAT REQUEST

Date Completed ______Initialed ______

14.  Clean all the entrance tracks of all dirt and dust. Includes all lock hardware, junction box covers, retiring cam and related equipment. Pistons have been cleaned, looking for a more comprehensive cleaning. REPEAT REQUEST

Date Completed ______Initialed ______


Elevator 8

15.  The new hoist cables are dropping excessive metal filings on the machine bed and machine room floor. Vacuum up filings, replace ropes. May be wrong hoist ropes for the sheaves. Double check lang lay requirements. REPEAT REQUEST
Date Completed ______Initialed ______

16.  Secure the hoistway access boxes on 2nd floor. REPEAT REQUEST
Date Completed ______Initialed ______

17.  Adjust leveling, floor level at 4th floor. ¾” short of floor. REPEAT REQUEST
Date Completed ______Initialed ______

18.  The conduit to the 2nd floor zone switch has pulled out of the fitting. Reinsert and tighten set screw. REPEAT REQUEST
Date Completed ______Initialed ______

19.  Clean the car top. REPEAT REQUEST
Date Completed ______Initialed ______

20.  Flush all gate chains, front and rear, with WD-40 and wipe off excess. REPEAT REQUEST
Date Completed ______Initialed ______

21.  Secure the Car Operating Panel, only 1 screw out of 8 is holding the panel. REPEAT REQUEST
Date Completed ______Initialed ______

22.  Lower the weight containment clip on the counterweight. REPEAT REQUEST
Date Completed ______Initialed ______

23.  The bottom hoistway door track support has pulled away from the wall. Properly secure. REPEAT REQUEST
Date Completed ______Initialed ______

24.  Tape the hoistway door astragal on 2nd floor. 10” slice on right side (OLI). REPEAT REQUEST

Date Completed ______Initialed ______

25.  The car operating panel is held in by one screw, 7 are missing. Secure to faceplate properly. REPEAT REQUEST

Date Completed ______Initialed ______

26.  Remove service panel door or fix it. REPEAT REQUEST

Date Completed ______Initialed ______

27.  Door close button on 2nd floor does not work. REPEAT REQUEST
Date Completed ______Initialed ______

28.  Replace the damaged hall access box on ‘G’ level, left side. (OLI). REPEAT REQUEST

Date Completed ______Initialed ______

29.  Clean all the entrance tracks of all dirt and dust. Includes all lock hardware, junction box covers, retiring cam and related equipment. Pistons have been cleaned, looking for a more comprehensive cleaning. REPEAT REQUEST

Date Completed ______Initialed ______

Elevator 9

30.  Door close button on 2nd floor does not work. REPEAT REQUEST
Date Completed ______Initialed ______

31.  Secure the hoistway access boxes on 2nd floor. REPEAT REQUEST
Date Completed ______Initialed ______

32.  Adjust leveling in down direction, short of floors. REPEAT REQUEST
Date Completed ______Initialed ______

33.  Repair the Position Indicator in the car. REPEAT REQUEST
Date Completed ______Initialed ______

34.  Repair the position indicator in the hall. REPEAT REQUEST
Date Completed ______Initialed ______

35.  Clean the car top. REPEAT REQUEST
Date Completed ______Initialed ______

36.  Flush all gate chains, front and rear, with WD-40 and wipe off excess. REPEAT REQUEST
Date Completed ______Initialed ______

37.  Flush all hoistway door chains, front and rear, with WD-40 and wipe off excess. REPEAT REQUEST
Date Completed ______Initialed ______

38.  Replace the missing door lock cover at 3rd floor. REPEAT REQUEST
Date Completed ______Initialed ______

39.  Replace the missing door lock cover at G level. REPEAT REQUEST
Date Completed ______Initialed ______

40.  The Phase I key switch is pushed into the hall fixture faceplate. Secure it properly. REPEAT REQUEST
Date Completed ______Initialed ______

41.  Repair the emergency light to proper working order. REPEAT REQUEST
Date Completed ______Initialed ______

42.  Repair the position indicator in the fire command station to proper working order. REPEAT REQUEST

Date Completed ______Initialed ______

43.  Replace the 4th floor hall button light. REPEAT REQUEST

Date Completed ______Initialed ______

44.  Clean all the entrance tracks of all dirt and dust. Includes all lock hardware, junction box covers, retiring cam and related equipment. Pistons have been cleaned, looking for a more comprehensive cleaning. REPEAT REQUEST

Date Completed ______Initialed ______

Item / Check
Freights 7,8,9 / A17.1 1996 Section/Rule / A17.1- 2000/
B44-00 Requirements / A17.3 Section/Parts / OK / NI / N/A /
MACHINE ROOM
2.3 / Lighting and receptacles / 101.5a,
101.5c,
1001.2(b)(3) / 2.7.5.1,
8.11.2.1.2(c) / 2.2.3 / X
2.4 / Machine room / 100.3c,
100.3d,
100.5,
101.1a,
101.2,
101.8, 10001.2(b)(4) / 2.1.3.3,
2.1.3.4,
2.1.5,
2.7.1.1,
2.7.2.1,
2.7.8,
8.11.2.1.2(d) / 2.2.1,
2.2.6 / X
2.5 / Housekeeping / 1001.2(b)(5),
1206.2b,
1206.9 / 8.11.2.1.2€,
8.6.4.8,
8.6.10.3 / X
2.6 / Air Conditioning / 101.5b,
102.4
1001.2(b)(6) / 2.7.5.2,
2.8.4,
8.11.2.1.2(f) / 2.2.4 / X
2.7 / Fire Extinguisher / 1001.2(b)(7),
1206.1h / 8.11.2.1.2(g),
c8.11.2.1.2(g),
8.6.1.6.5 / X
2.14 / Code Data Plate / 215,
1200.6
309,
1200.6 / 8.9,
8.7.1.8 / X
2.17 / Drive Machine Brake / 207.2b,
207.8,
(NR 2.24.8)
210.8,
1001.2(b)(15),
[NR 8.11.2.3.10(b)],
1002.3d / 2.16.2.2,
2.16.8,
2.24.8,
2.26.8,
8.11.2.1.2(o),
8.11.2.3.1.10(a),
8.11.2.3.4 / 3.8.4 / X
2.30 / Hydraulic Power Unit / 304,
1004.2(b)(13),
1206.5 / 3.24,
8.11.2.1.2(m),
8.6.5 / X
2.31 / Testing
a.  ANLT Current / 308,
303.1,
303.2,
303.4b,
1004.2(b)(13),
1005.2a,
1006.2b,
Definitions / 3.28,
3.19.1,
3.19.2,
3.19.4.2,
8.11.3.1.2(m),
8.11.3.2.1,
8.10.3.2.2(m),
1.3 (Definitions) / 4.4.1 / X
b.  ANLT Tagged / X
c.  5 Yr Test Tagged / X
2.32 / Control Valve / 303,
1004.2(b)(15) / 3.19,
8.11.2.1.2(o) / 4.4 / X
2.34 / Flexible hydraulic hose and fitting assemblies / 303.3c,
1004.2(b)(17),
1005.2d / 3.19.3.3,
8.11.2.1.2(g),
8.11.3.2.4 / X
2.35 / Supply line and shutoff valve / 303 / 3.19 / 4.4.4 / X
2.40 / Maintenance Records
a.  Tasking Log / 8.6.1.4,
c8.6.12.2.5,
8.6.10.1 / X
b.  Oil Monitoring sheet / X
c.  Call Back Log / X
d.  Fire Service Log / X
INSIDE OF CAR
1 / Check Scanner / 112, 1001.2(a)(1) / 2.13, B.11.2.1.1(a) / X
1.5 / a.  Car Lighting and receptacles / 204.7,
1001.2(a)(5) / 2.14.7,
8.11.2.1.1(e) / 3.4.5,
3.4.6 / X
b.  Emergency Light / X
1.6 / Car Emergency Signal
a.  Phone Operational / 211.1,
1001.2(a)(6) / 2.27.1,
8.11.2.1.1(f) / 3.11.1 / X
1.18 / Restrictor / 111.12,
1001.2(a)(18) / 8.11.2.1.1(r) / 2.7.4 / X
1.19 / Car Ride / 200,
203.2,
1001.2(a)(18) / 2.23,
2.15.2,
8.11.2.1.1(s) / X
CAR TOPS/HOISTWAYS
3.16 / Traveling Cables and Junction Boxes / 102.1,
1001.2(c)(22) / 2.8.1,
8.11.2.1.3(v) / X
3.17 / Door and gate equipment / 110,
111,
210.1e,
1001.2(c)(23) / 2.11,
2.12,
2.26.1.6,
8.11.2.1.3(w) / 2.6,
2.7 / X
3.23 / Hoist Rope / 212,
206.7,
1001.2(c)(29)(a),
1200.5,
1202.12,
1203.9,
1004.2(c) / 2.20,
2.18.7,
8.11.2.1.3(cc)(1),
8.6.3,
8.7.2.21,
8.7.3.25,
8.11.3.1.3(v) / X
4.2 / Hoistway Doors / 110,
111.7,
210.2,
1001.2(d)(2) / 2.11,
2.12.7,
2.26.2,
8.11.2.1(b) / 3.10.4 / X
4.6 / Power Closing of Hoistway doors / 112,
1001.2(d)(6) / 2.13,
8.11.2.1.4(f) / X
PIT
5.1 / Pit Access
a.  Pit Lighting / 102,
103.2,
106.1,
210.2(g),
1001.2(e)(1),
1206.2a / 2,8.
2.3.2,
2.26.2.7,
8.11.2.1.5(a),
8.6.4.7 / X
b.  Pit Housekeeping / X
c.  Jack Packings / X
5.3 / Rupture Valve / 209.3,
1001.2(e)(4),
1003.2e / 2.25.3,
8.11.2.1.5(d),
8.10.2.2.5(c),
c8.10.2.2.5(c)(6) / X
T-1849 ATLANTIC TERMINAL

PASSENGER ELEVATORS 1, 2, 3

CORRECTIVE ITEMS

The following minimum items need corrective action taken. Documentation of completion is required. CITY ID 1 – 3P11299 2 YEAR TEST 1 - 3/08 ANLT 1 – 2-15

2 – 3P11300 2 - 3/08 2 – 2-15

3 – 3P11301 3 - 3/08 3 – 2-15

General

16. Lube the bottom roll pin of sill mounted closure device. Flush the rust out. Follow up with a higher viscosity oil on all elevators.

Completion Date______Initial_____

17. Properly dispose of the box of oily rags and garbage outside the machine room door. (It is down from the elevator machine room).

Completion Date______Initial_____

Elevator One – Up Starts

597,260 09/18/08 652,973 02/04/09 801,646 08/19/09

982,285 09/02/10 1,083,982 02/04/11 1,221,828 10/05/11

1,296,529 05/11/12 1,343,174 09/30/12 1,366,264 12/11/12

1,399,501 03/12/13 1,470,095 08/14/13 22,436 10/07/13

92,128 01/23/14 218,390 07/24/14 2,532 10/27/14

98,958 05/06/15

Elevator One

18. Provide auto call registration. Required as part of Target standards. Store guests have had this for ten years, getting confused over not working. REPEAT REQUEST

Completion Date______Initial_____

19. Finish hooking up of the battery rescuvator per specifications. REPEAT REQUEST

Completion Date______Initial_____

20. Provide elevator identification tactile on the main egress landing. REPEAT REQUEST

Completion Date______Initial_____

21. Pin the clutch release roller assemblies with a tek. REPEAT REQUEST

Completion Date______Initial_____

22. Provide and install SEES enforcer gibs. Part of project, at least on fast speed doors. Check with Peder Baukol for scope. REPEAT REQUEST

Completion Date______Initial_____

23. Secure the front door operator greenfield to the adjacent ½ greenfield run with ty wraps. REPEAT REQUEST

Completion Date______Initial_____

24. Put the scanners in fail safe mode. If an obstruction exists, let the doors remain open. Remove nudging in normal operation. REPEAT REQUEST

Completion Date______Initial_____

Elevator Two – Up Starts

621,160 09/18/08 680,437 02/04/09 760,859 08/19/09

923,455 09/02/10 988,721 02/04/11 1,152,894 05/11/12

1,205,134 09/30/12 1,235,192 12-11-12 1,272,312 03/12/13

1,335,437 08/14/13 1,358,583 10-07-13 1,404,598 01/24/14

1,469,892 07/24/14 18,569 10-27-14 119,234 05/06/15

Elevator Two

25. Provide auto call registration. Required as part of Target standards. Store guests have had this for ten years, getting confused over not working. REPEAT REQUEST

Completion Date______Initial_____

26. Finish hooking up of the battery rescuvator per specifications. REPEAT REQUEST

Completion Date______Initial_____

27. Provide elevator identification tactile on the main egress landing. REPEAT REQUEST

Completion Date______Initial_____

28. Pin the clutch release roller assemblies with a tek. REPEAT REQUEST

Completion Date______Initial_____

29. Provide and install SEES enforcer gibs. Part of project, at least on fast speed doors. Check with Peder Baukol for scope. REPEAT REQUEST

Completion Date______Initial_____

30. Secure the front door operator greenfield to the adjacent ½ greenfield run with ty wraps. REPEAT REQUEST

Completion Date______Initial_____

31. Put the scanners in fail safe mode. If an obstruction exists, let the doors remain open. Remove nudging in normal operation. REPEAT REQUEST

Completion Date______Initial_____

32. Clean up the oil on the floor in front of the controller. Appears to be from the oil cooler. Seal up source.

Completion Date______Initial_____

33. Need to turn the oil cooler 45 degrees. The fan blows hot air from cooling the oil right back onto the tank unit it is trying to cool. Just doesn’t make sense. It is currently heating the oil more than cooling it.

Completion Date______Initial_____

Elevator Three – Up Starts

522,337 09/18/08 569,793 02/04/09 645,397 08/19/09

789,886 09/02/10 832,363 02/04/11 20,462 10/05/11 New

91,163 05/11/12 132,143 09/30/12 154,489 12-11-12

180,950 03/12/13 219,476 08/14/13 1,486,022 10-07-13

1,511,719 01/24/14 1,550,690 07/24/14 25,471 10-27-14

82,885 05/06/15

45.  Provide auto call registration. Required as part of Target standards. Store guests have had this for ten years, getting confused over not working. REPEAT REQUEST

Completion Date______Initial_____

46.  Finish the wiring of the battery rescuvator. Ground is not hooked up. REPEAT REQUEST

Completion Date______Initial_____

47.  Put the scanners in fail safe mode. If an obstruction exists, let the doors remain open. Remove nudging in normal operation. REPEAT REQUEST

Completion Date______Initial_____

48.  Strap the rear door operator motor greenfield. REPEAT REQUEST

Completion Date______Initial_____

49.  Provide elevator identification tactile on the main egress landing. REPEAT REQUEST

Completion Date______Initial_____

50.  Pin the clutch release roller assemblies with a tek. REPEAT REQUEST

Completion Date______Initial_____