DEPARTMENT OF TRANSPORT FIRE FIGHTING

APPLIANCES SERVICING STATION STANDARDS

(DOTFAS)

Date of inspection: ......

Name of Service Station: ......

Name:

Address: ...... Telephone: ......

...... Fax: ......

...... E-mail: ......

Alternative address: ......

......

Service Vehicle  YES NO

(operates on a daily basis from its base)

Mobile Service Station YES NO

(A mobile station is one operating away from its’ base for more than 1 day)

REGISTRATION

Company Registration No.: ......

SABS APPROVAL (Govt Notice R1591 04/10/1996 refers)

Hand-Held fire extinguishers

1)No user shall use, require or permit the use of a hand held fire extinguisher unless designed, constructed, filled, recharged, reconditioned, modified, repaired, inspected or tested in accordance with a safety standard incorporated into these regulations in terms of section 44 of the Act.

2)No person shall fill, recharge, recondition, modify, repair, inspect or test any hand held fire extinguisher unless a holder of a permit issued bt the South African Bureau of Standards in terms of SABS 1475.

SANS 1475Approval  YES  NO

Approval date ......

(Without SANS 1475 approval, DOTFAS approval cannot be issued)

2

INSURANCE

Company ...... Policy No......

Public Liability Cover Amount (Rands) ......

HIGH PRESSURE TESTING OF CYLINDERS

SANAS ApprovalYES  NO

SANAS Authorisation is mandatory.

SANAS approval date ......

Radiation Control Authority (Dept. Of Health) No......

Ultrasonic Equipment (state type) ......

Are all relevant Certificates displayed e.g. SABS,

Classification Society, SANS, SAQCC  YES  NO

MANUALS, PUBLICATIONS AND RECORDS

DOTFAS Code Book  YES  NO

SANS 1910 (portable refillable fire extinguishers)

(2006 1.01)  YES  NO

SANS 1475-1 & SANS 1475-2 - The production of reconditioned

Fire fighting equipment. Part 1 : Portable and wheeled mobile

Rechargeable fire extinguishers.

Part 2 : Production of reconditioned fire fighting equipment.

Fire hose reels, hydrants and booster connections YES NO

SANS 1567–Portable rechargeable fire extinguishers –

CO2 type extinguishers (2003 – 2nd edition) YES NO

SANS 11601–wheeled fire extinguisher – performance

& construction Edition 1 2005 edition  YES  NO

SANS 1739 - Low pressure welded steel cylinders for

fire extinguishers (1998 Edition)  YES  NO

SANS 543 – 2004 Edition  YES  NO

Fire hose reels (with semi Rigid Hose)

- 3 -

SANS 10105 –Part 1 : 2005 3rd Edition-The use and

control of fire fighting Equipment, portable and wheeled

mobile fire extinguishers.

Part 2 : 2005 3rd Edition- The use and control of fire fighting

Equipment- fire hose reels, hydrants and booster  YES NO

Connections.

Occupational Health & Safety Act 1993  YES  NO

Record of pressure tests  YES  NO

FSS Code (International Code for Fire Safety Systems IMO) YES  NO

PREMISES

Total area ...... m²  YES  NO

Pressure test area ...... m² [H.P. to have safety notice]  YES  NO

Dry powder or CO² areas ...... m²  YES  NO

Dry powder storage receptacles  YES  NO

Are areas clean ?  YES  NO

EQUIPMENT

YES NO

Cylinder cleaning equipment
Cylinder handling equipment
Proper tools
Spares - “O” rings, cartridges, rubber hoses, nozzles etc
Equipment to view internal surfaces of cylinders (probe light, dental mirror, etc)

Nitrogen supply with regulator for stored pressure cylinders  YES  NO

CALIBRATION OF SCALES AND PRESSURE GAUGES

YES NO

Calibration Certificates for gauges or for a master test gauge (annually)
No...... Date ......
Calibration Certificates for scales (annually)
No...... Date ......
Test Weight Certificates for test weights (annually) (5kgs 10kgs) (1 kg)
No...... Dates ......

- 4 -

MAKE / CAPACITY OF SCALES (List)

1......

2......

3......

4......

5......

PRESSURE TESTING

Note that SANAS approval is required for high pressure testing.

Low pressure cylinders to 3000 or 5000 KPA.

What type of pumps are available ?

1......

2......

What is the maximum test pressure available ? ...... KPA

Maximum gauge reading ...... - This reading must not exceed twice the test pressure being utilised / checked (this should obviate reading errors).

Pressure gauge tester or duplex master pressure gauge  YES  NO

(see previous section regarding calibration certificates)

What type of cylinders can be tested ?

Low pressure 3000KPA  YES  NO

High pressure 24000 KPA (CO² & cylinders)  YES  NO

(note SANAS certificate is required for high pressure)

Breathing apparatus cylinders (high pressure)  YES  NO

DRYING RACKS FOR CYLINDERS

Drying racks fitted with fan / air blower  YES  NO

Hot air generator  YES  NO

- 5 -

DEMONSTRATIONS

SATISFACTORY / UNSATISFACTORY / N/A
Low pressure cylinder test
- by hand pump
- by mechanical means
High pressure cylinder test (SANAS approval is required)
Name of demonstrator
......
Service of portable foam extinguishers
(demonstrate filling & then activate same)
ID stamping / date on cylinders tested
(ID stamping for HP only)
(on CO² only - neck only)

FIRE HOSES

Are fire hoses tested ?  YES  NO

(Minimum 1.5 x 4 Bar. Utilise pump pressure x 1.5 Bar. ie 7 Bar Test to 1.5 x 7 Bar)

How are hoses tested ? ......

Is there a suitable facility for drying hoses ?  YES  NO

Pressure to which hoses may be tested ? ......

BREATHING APPARATUS

List types / makes serviced MANUFACTURES MANUAL

YES NO

1......
2......
3......
4......
5......

- 6 -

Is there equipment for vacuum and break testing of masks ? YES  NO

Do you refill cylinders ?  YES  NO

(SANAS approval required)

SUBCONTRACTING

The following work is subcontracted:

1...... to ......

2...... to ......

3...... to ......

Provide proof i.e. fax, letter etc that  YES  NO

subcontractor has appropriate accreditation

DESIGNATED PERSONS

Name: ...... I.D. No: ......

Position in the Company : ......

Qualifications (to be registered with the South African Qualifications Committee - SAQCC) ......

......

......

Relevant Marine experience (minimum 4 yrs - 2 of which must be in marine industry) ......

......

......

Relevant Training (list)

a)......

b)......

c)......

d)......

- 7 -

COMPETENT PERSONS

NAME / POSITION / REG. NO. WITH SAQCC / TRAINING & EXPERIENCE
YEARS / COMPANY

NOTE that SAQCC becomes invalid if the person leaves the Company whom he was registered with.

Re-registration is then required.

TYPE OF WORK FOR WHICH THE STATION WILL BE REGISTERED

Pressure Testing of Low Pressure Cylinders only
Pressure Testing of All Cylinders and Cartridges (SANAS approval required)
Servicing of Portable Extinguishers (Water, Powder, foam & CO2 )
Pressure Testing and Maintenance of Fire Hoses
Installation and maintenance of Fixed Fire Detecting and Extinguishing Systems **
Alarm systems
Maintenance of B.A. sets (Types - see list on page 6)
Filling of B.A. set air bottles (SANAS approval required)

** Show that competent persons for this type of work are either registered engineers or have a minimum of 10 years experience in servicing such appliances or attending manufacturers approval for particular systems e.g. Kidde etc

- 8 -

EXCEPTIONS / SPECIAL CIRCUMSTANCES / OBSERVATIONS

......

......

......

......

......

DECLARATION BY DESIGNATED PERSONS

I hereby declare that the above particulars are true and correct.

......

SignaturePrint Name

SAMSA Surveyor (as witness and audit inspector)

......

SignaturePrint Name

......

Date