AT&T ENGINEERING REQUIREMENT CHANGE NOTIFICATION - ATT-TP-76400-025
TO: ALL AT&T ENGINEERING SUPPLIERS Date: 09-03-08
EFFECTIVE DATE: 5 days from posted date or as per Supplier’s Contract
Submitter’s Name: Al Bergman
TP: TP76400 Subject: Lighting Rigid Conduit Fittings Action: Add Modification: Delete:
Section: 8 Section Title: Cable Rack, Auxiliary Framing and Lighting Systems
Subsection: 5 Section Title: Frame and Aisle Lighting – Fluorescent
Subsection: 5.2.7 Subsection Title: Engineering Requirements
Prior to Change:
5.2.7 All conduit and fittings shall be metallic and nonferrous.
Post Change:
5.2.7 Conduit runs shall be rigid aluminum conduit (RAC) connected by aluminum conduit bodies with threaded steel compression fittings. Lighting fixture final connections of 6 feet or less may be made with Liquidtight Flexible Metallic Conduit (LFMC), e.g. (Seal-Tite® UA or Liquatite® LA).
Questions relative to this IRCN should be addressed to Lawrence Lyles at (404) 927-7722.
Lawrence Lyles
Lead Network Engineering Manager, NP&E
Enterprise Technology Support
Access the TP's on the Extranet Site https://ebiznet.sbc.com/sbcnebs
Concurred
Senior Engineering Manager-Network Quality, West Date: 08-27-08
(Tim Harper)
Senior Engineering Manager-Network Quality, Southwest Date: 08-28-08
(Crissy Holmes)
Senior Engineering Manager-Network Quality, Midwest Date: 08-27-08
(Charles Stahulak)
Senior Engineering Manager-Network Quality, Midwest Date: 08-28-08
(Ray Coates, Jr.)
Lead Network Engineering Mgr. - Common Systems Power Date: 08-26-08
(Al Bergman)
Release Approved
Lead Network Engineering Manager Date: 09-02-08
(Lawrence E. Lyles)
Page 1 of 1