5313UBUSG BORAL SHEET CEILING SYSTEMS
1.GENERAL
This section relates to the manufacture, supply and installation of USG Boral proprietary, concealed and suspended or direct fixed ceiling systems.
It includes:
-USG Boral ScrewFix® furring channel system
-USG Boral Drywall Grid T grid system
-USG Boral Sheetrock® Ceiling Batten system
-all elements offered by the manufacturer to complete the systems.
All three systems support screw fixed sheet materials.
1.1RELATED WORK
Refer to 5113UB USG BORAL PLASTERBOARD LININGS for ceiling lining.
1.2ABBREVIATIONS AND DEFINITIONS
Refer to the general section 1232 INTERPRETATION & DEFINITIONS for abbreviations and definitions used throughout the specification.
The following abbreviations apply specifically to this section:
STCSound transmission class
IICImpact insulation class
AWCINZAssociation of Wall and Ceiling Industries of New Zealand Inc
Documents
1.3DOCUMENTS
Refer to the general section 1233 REFERENCED DOCUMENTS. The following documents are specifically referred to in this section:
NZS 1170.5Structural design actions - Earthquake actions - New Zealand
AS 1397Steel sheet and strip
AS 1530.4Methods for fire tests on building materials, components and structures - Methods of tests on building materials, components and structures - Fire-resistance test of elements of construction
AS/NZS 2589Gypsum linings - Application and finishing
AS/NZS 2785Suspended ceilings - Design and Installation
AS 2946Suspended ceilings, recessed luminaires and air diffusers - Interface requirements for physical compatibility
NZS 4219Seismic performance of engineering systems in buildings
AS/NZS 4600Cold-formed steel structures
1.4MANUFACTURER/SUPPLIER DOCUMENTS
Manufacturer's and supplier's documents relating to this part of the work:
USG Boral ScrewFix® Plasterboard Suspension System
USG Boral Sheetrock® Ceiling Batten System
USG Boral Drywall Grid Suspension System
USG Boral Warranty
USG Boral Plasterboard Installation Manual - NZ
USG Boral Sheetrock® Brand Ceiling/Wall Board 10mm
USG Boral Sheetrock® Brand Standard Board 13mm
USG Boral Firestop® Board
USG Boral Wet Area Board™
USG Boral Soundstop™ Board
USG Boral Multistop™ Board
USG Boral Fiberock® Aqua-Tough™ gypsum fibreboard
USG Boral Sheetrock® Paper Face Metal Bead and Trim
Manufacturer/supplier contact details
Company:USG Boral Building Products NZ
Web:
Email:
Telephone:0800 USGBORAL, 0800 874 26725
Requirements
1.5NO SUBSTITUTIONS
Substitutions are not permitted to any specified USG BORAL systems, system components, plasterboard, associated products or accessories.
1.6SAMPLE SECTION
Provide a sample section of the suspended / direct fixed ceiling system offered. Subject to confirmation in writing, the sample section may form part of the completed installation.
Refer to SELECTIONS for location of sample section.
1.7SUSPENSION SYSTEM
To AS/NZS 2785, AS/NZS 4600, AS 1397 and USG Boral's requirements. Installation by a competent installer, using the manufacturer's technical services. Installers must be members of the AWCINZ. Provide evidence of experience, listing completed projects of similar size and complexity.
Also to NZS 4219, where services are involved.
Performance
1.8LOADING CODE REQUIREMENT
Comply with the requirements of NZS 1170.5, section 8.
1.9CERTIFICATION
Provide:
-certification of compliance with NZS 1170.5, section 8 for evaluation
-certificates and other evidence that the system offered complies with the standards of performance specified
-a Producer Statement on completion.
1.10ACOUSTIC REQUIREMENTS
Provide evidence the specified system achieves published data and submit the results for acceptance. Refer to SELECTIONS.
2.PRODUCTS
Materials
2.1SUSPENSION SYSTEM
Manufactured by a member of the AWCINZ. Hot-dip galvanized steel elements to AS/NZS 4600, AS 1397 and AS/NZS 2785 for carrying ceiling sheets, light fixtures and air distribution elements and complying with NZS 1170.5, section 8.
2.2DIRECT FIX SYSTEM
Manufactured by a member of the AWCINZ, wall and suspended ceiling division. Hot-dip galvanized steel elements to AS/NZS 4600, AS 1397 and AS/NZS 2785, including furring channels / batten, T grid and direct fix brackets for fixing to timber, steel and concrete.
2.3PLASTERBOARD SHEET
Refer to 5113UB USG BORAL PLASTERBOARD LININGS section.
Components
2.4FASTENERS SUSPENSION SYSTEM
Join furring channels and C channels using proprietary system clips, pop rivets or 8g-16 x 12mm (minimum) self drilling wafer head screws as per manufacturer's details.
2.5FASTENERS DIRECT FIX
8g-16 x 25mm (minimum) self drilling wafer head screws to steel or timber, or 30mm clouts for fixing to timber only, as per manufacturer's details.
3.EXECUTION
Conditions
3.1CO-ORDINATE SERVICES
Co-ordinate and co-operate with electrical and mechanical work to avoid conflict between suspension members and light fittings, diffusers, pipework and ducting to NZS 4219. Confirm the provision of extra hangers and fixings as required:
-Surface mounted light fittings or similar point loads up to 15kg may be supported on the ceiling battens providing batten does not span more than 900mm.
-Surface mounted light fittings or similar point loads up to 7kg may be supported on the ceiling battens providing batten does not span more than 1200mm, and is screwed back to back with 8g - 16 x 12mm self-drilling wafer head screws at 150mm centres, as per manufacturer's details.
-Surface mounted point loads are to be directly fixed to ceiling batten, not to lining.
Refer to PENETRATION clause for penetration fittings.
3.2SITE CONDITIONS
Do not begin installation until the building is closed in, fully glazed, the roof watertight, and mechanical and electrical duct work above the ceiling completed.
3.3COMPLY
Comply with AS 2946 for interface requirements for physical compatibility.
3.4RESPONSIBILITY
Ensure that conditions are suitable for the ceiling installation. Arrange for the programming of the work to suit required practice.
Installation
3.5INSTALL
Install the system to AS/NZS 2785 minimum standards and USG Boral's requirements. Adjust all clips by string line or laser level until they are all level.
3.6ACCESSIBILITY
Provide access hatches where required to the ceiling system for the in-ceiling and above-ceiling services so that maintenance and removal of any part can be carried out without damage to the ceiling system or lining.
3.7PENETRATIONS
Accommodate recessed light fittings, air conditioning outlets and other electrical and/or mechanical services that are fixed to or pass through the ceiling system. Provide independent support for these as necessary.
3.8FLUSH CEILING - SUSPENDED
Install the selected suspension system to AS/NZS 2785 minimum standards. Screw-fix sheets to either the furring channel sections or Drywall Grid face at the centres required by the ceiling lining manufacturer. Stagger joints and fully support on sections, with framing and suspension centres to suit the load and USG Boral's requirements. Refer to 5113UB USG PLASTERBOARD LININGS section.
3.9FLUSH CEILING - DIRECT FIX
Install the direct fix system to AS/NZS 2785 minimum standards. Screw or nail direct fix brackets to either purlins, joists or truss bottom chords. Screw-fix sheets to either batten sections or Drywall Grid face at the centres required by the ceiling lining manufacturer. Stagger joints and fully support on sections, with direct fix brackets at centres to suit the load and USG Boral's requirements. Refer to 5113UB USG BORAL PLASTERBOARD LININGS section.
Note: The direct fix clips DFS200 for the USG Boral Drywall Grid System will need to be preloaded on to the Main Tee before attachment to the purlins or joists. Ensure there are sufficient numbers to support the required load at the purlin / joist centres.
3.10BULKHEADS
Form bulkheads to USG Boral's requirements. Diagonally brace at regular intervals to provide lateral stability.
3.11PROTECT EXISTING WORK
Protect adjacent existing work from damage during the installation.
Completion
3.12REPLACE
Replace damaged or marked elements.
3.13LEAVE
Leave work to the standard required by following procedures.
3.14REMOVE
Remove debris, unused elements and elements from the site.
3.15CLEAN
Clean soiled or marked units.
4.SELECTIONS
For further details on selections go to
Substitutions are not permitted to the following, unless stated otherwise.
4.1SAMPLE SECTION
Location of sample section: ~
Performance requirements
4.2ACOUSTIC REQUIREMENTS
STC:~ minimum
IIC:~ minimum
Materials
4.3USG BORAL SUSPENSION SYSTEM - SCREW FIX
Location:~
Brand:USG Boral
System:ScrewFix®
Furring Centres:~
4.4USG BORAL SUSPENSION SYSTEM - DRYWALL GRID
Location:~
Brand:USG Boral
System:Drywall Grid
Tee centres:~
4.5USG BORAL DIRECT FIX SYSTEM - SHEETROCK BATTEN
Location:~
Brand:USG Boral
System:Sheetrock® Batten
Batten centres:~
4.6USG BORAL PLASTERBOARD SHEET
Refer to 5113UB USG PLASTERBOARD LININGS section.
4.7ACCESS HATCHES
Location:~
Brand/type:~
Material:~
Finish/colour:~
Size:~mm x ~mm to suit grid
© CIL Masterspec 2015 SEP5313UB USG BORAL SHEET CEILING SYSTEMS Page 1