14001 SHELDON TOTAL EXPERIENCE II LABORATORY CENTER

EDUCATIONAL REQUIREMENTS - Generally a four-student activity center of lineal space, and protective raised perimeter edge. Services located on outer perimeter allowing all students easy access.

Support structure is designed to have formed recesses to accept relocatable suspended cubicle storage in limitless combinations of apparatus/material cubicles or individual containers like carryalls and tray drawers. Fully enclosed sides and bottom protecting service piping and electrical wiring. Removable access panels on underside located immediately below service connections.

Full-length trough with service turrets on each end. Trough designed to accept accessories; chemical dispensing rack for chemistry and trough covers to provide flush work surface for physics(included only when specified).

Center steel pedestal allows for attaching support structure at various heights to provide finished work heights from (32" to 38 ½”) at time of installation. Specify low range (32” to 34 ¼”) or high range , 56”L x 28”W x 34” H (35” to 38 ½”).

PHYSICAL REQUIREMENTS - Work top 56" square, 67-3/8" across corners (minimum 3,020 square inches of student work area); top of 1" thick Shelresin with raised perimeter edge.

Pedestal base of 10 gauge formed steel cubicle 14-3/4" square with 3/4" radius corners. Steel L-shaped straps 13-1/4" X 3/16" attached to pedestal interior for bolting pedestal to floor. Two (2) access panels (minimum 12" X 25") secured to pedestal to be removable for access to services.

Series of bolt holes in pedestal base allows for attaching top support structure at various heights to provide different finished work heights at time of installation and in the future as educational requirements dictate.

Top support structure of molded glass fiber reinforced structural polyester with 3/4" radius on all exterior corners. Top support structure to fully enclose service piping and wiring. Removable access panels on underside of top support structure located immediately below plumbing and electrical service connection. Top support structure shaped and reinforced to accept suspended cubicle storage.

One-piece molded Shelresin trough with service turret at each end. Trough (minimum 55" X 9" X 5-1/4" at center, 4-3/4" at ends I.D.) and service turrets (minimum 9-1/2" X 4-1/2" above work surface). Service turret designed to position outlet of water fitting, minimum of 15" above trough bottom so as to accommodate large containers and other large objects within trough.

Two (2) G.F.I. electrical outlets located in top support structure. Two (2) Unicast combination cold water and double gas cock fittings located on service turret. Two (2) sets of upright rod sockets with one (1) set on each side of trough.

Activity center, when combined with pedestal base, top support structure and top are properly bolted to floor, shall support 250 lbs. live load at the center perimeter. Sheldon Model #14001. Internal piping and wiring not included .