NEW MAIN CERTIFICATION FORM

PROJECT:

SITE LOCATION:

CONTRACTOR:

TAPPING CONTRACTOR:

DATE: TIME: WEATHER:

WATER MAIN FLUSH

YES NO / PRIOR TO ANY TESTING, ALL MAINS 6” DIA. AND LARGER SHALL HAVE A LINE SIZE SWAB PASSED THRU THE ENTIRE LENGTH OF THE LINE. NOTE: SWAB SHOULD BE PLACED IN 1ST JOINT OF NEW LINE. END OF MAIN SHOULD BE “TURNED UP” AT 45% AND EXTENDED SO THAT SWABBING AND A FULL BORE FLUSH CAN BE ACCOMPLISHED. BLOW-OFF ASSEMBLY CAN THEN BE PLACED. WHERE LINES BRANCH, SWABS WILL BE PLACED IN BRANCH LINES AND SEQUENTIALLY SWABBED AND FLUSHED.

CHLORINATE OF WATER MAIN

YES NO / THE RATE OF CHLORINE MIXTURE FLOW SHALL BE IN SUCH PROPORTION TO THE RATE OF WATER ENTERING THE PIPE SO THAT THE COMBINED MIXTURE SHALL CONTAIN 50 PPM OF FREE AVAILABLE CHLORINE, BUT NO MORE THAN 200 PPM OF FREE AVAILABLE CHLORINE. VALVES SHALL BE MANIPULATED SO THAT THE STRONG CHLORINE SOLUTION IN THE LINE BEING TREATED WILL NOT FLOW BACK INTO THE LINE SUPPLYING THE WATER. BACKFLOW PREVENTERS SHALL BE USED IF NECESSARY.

TOTAL INITIAL FREE CHLORINE: PPM.

CHLORINE FLUSHED

* BEFORE FLUSH, TOTAL OF FREE CHLORINE: PPM

* AFTER FLUSH, TOTAL OF CHLORINE: PPM

YES NO / BACTERIOLOGICAL SAMPLES HAVE BEEN APPROVED.
YES NO / ALL FORCE MAIN PIPE SHALL BE THOROUGHLY CLEANED AND FLUSHED PRIOR TO TESTING TO CLEAR THE LINES OF ALL FOREIGN MATTERS.

WATER / FORCE MAIN PRESSURE TEST

Note: Pressure testing must be completed by 12:00 noon due to thermal expansion.

Hydrostatic testing shall be performed at 100 psi, for force main and 150 psi for water main unless otherwise approved by the Utilities Engineer. Hydrostatic tests shall be for a period of not less than two hours. Maximum length for test must be less than 3000 feet or as allowed by the Utilities Engineer. Testing shall be in accordance with the applicable provisions as set forth in Section 13 of AWWA Standard C600. The allowable rate of leakage shall be less than the number of gallons per hour determined by the following formula:

L = SD[(P) ½]

148,000

Allowable leakage in gallons per hour = L

Length of pipe tested, feet = S

Nominal diameter of the pipe in inches = D

Average test pressure maintained during the

leakage test in pounds per square inch gauge. = P ______

Total Allowable = L X ______Hrs. Tested = ______

Water and Force Main Loss pounds within two hours.

Actual Leakage .

*Repump to starting pressure - Water required Gallons.

YES NO / SYSTEM TESTED. BLOWN OFF AT VARIOUS POINTS, BETWEEN IN-LINE GATE VALVE.
YES NO / PRESSURE GAUGE RETURNED TO 0 PSI.
MAIN EXTENSION PRESSURE TEST

TEST TO BE MADE VALVE TO VALVE 150 P.S.I. 2 HOUR MINIMUM TO 3 HOURS.

PIPE SIZE______TYPE OF PIPE: PRESSURE GAUGE ID#

START / 15 / 15 / 15 / 15 / 15 / 15 / 15 / 15 / 15 / 15
TIME / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN.
TIME
P.S.I.
TAPPING SLEEVE PRESSURE TEST

150 P.S.I. - 15 MINUTES MINIMUM PRESSURE GAUGE ID# .

SIZE AND TYPE OF PIPE TAPPED: SIZE & TYPE OF SLEEVE

START / 5 / 5 / 5 / 5 / 5 / 5 / 5 / 5 / 5 / 5
TIME / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN. / MIN.
TIME
P.S.I.

FPUA REPRESENTATIVE: CONTRACTOR’S REPRESENTATIVE: