Rif: SP693PE.DOC

Rev 0 OF 14.02.06

GRAPHIC USER INTERFACE BOARD

‘TFT WITH TOUCH SCREEN’

HW UG2BIO - SW PE_USG, GEOUSG

PRELIMINARY TECHNICAL SPECIFICATION

Ref:SP693PE.DOC

First Issue:13.02.06MNS

Rev. 2of 26.06.06MNS

INDEX

1.INTRODUCTION

2.RELATED DOCUMENTS

3.HARDWARE CHARACTERISTIC

3.1SYSTEM ARCHITECTURE

3.2BOARD DESCRIPTION

3.3CONNECTION

4.MOUNTING INSTRUCTION

5.SW SPECIFICATION

5.1PROGRAMMING INSTRUCTIONS

5.2CONTROL

5.3ALARMS

5.4VISUALIZATION

5.4.1USER

5.4.2SYNOPTIC

5.4.3GRAPHIC

5.4.4CONFIGURATION

5.4.5F1, F2, F3

5.5DATE & TIME

5.6SETUP

6.GEOCLIMA PERSONALIZATION

6.1Sw Version

6.2Logo Screen

6.3Main Mask

6.4SYNOPTIC

6.4.1CHILLER

6.4.2COMPRESSOR

6.5TRENDS

6.6LANGUAGE

6.7CONFIGURATION

6.8ALARM HISTORY

7.REVISION HISTORY

1.INTRODUCTION

The object of this specification is the a graphic TFT LCD with touch screen user interface board to be used with a controller using a serial connection.

Note: TBD means To Be Defined, TBC means To Be Confirmed.

2.RELATED DOCUMENTS

Wiring diagram A-UG2.PDFTBC

3.HARDWARE CHARACTERISTIC

The UG2 board is a graphic user interface 320x200 pixel, 16 colors, with a touch screen driver.

3.1SYSTEM ARCHITECTURE

3.2BOARD DESCRIPTION

1 display grafic 5,7” TFT 320x200

1 slot per hardware key

RTC a bordo scheda con batteria

interfaccia con connettore per touch panel 4

1 connettore per scheda PE UDA

1 ANOUT

2 ANIN

2 COM (1 rs232 e uno slot IS)

3.3CONNECTION

There are 2 serial interface connection.

COM1: To be connected at the controller/gw board

COM0: To be connected to a PC, Printer, Modem

4.MOUNTING INSTRUCTION

5.SW SPECIFICATION

5.1PROGRAMMING INSTRUCTIONS

To Program the Board:

  • Turn off the board
  • Close the Jumper PRG.
  • Change the Jumper JU3 configurationfrom

JU3 C C O

To

JU3 O CC

O = Open

C = Closed

  • Connect the the RS 232 cross cable from PC To COM1.
  • Turn on the System
  • Use the serial programming file for Renesas Micro (M16c Flasher, FlahSta or others)

5.2CONTROL

5.3ALARMS

5.4VISUALIZATION

Note: The pictures on this specification are draft. The keys icon can be customized.

At the start up on the display will appear the following mask:

On the center of the screen

a big logo of the customer.

In the high part of the screen will be displayed 4 Keys.

USER

SYNOPTIC

GRAPHICS

CONFIGURATION

In the low part of the screen will be displayed the following 4 Keys

F1 (optional)

F2 (optional)

F3 (optional)

TIME & DATE

5.4.1USER

Pressing the USER Key we enter in the standard user interface mode (like a normal remote display panel). The keys are drawn on the touch screen.

5.4.2SYNOPTIC

From this mask it is possible to see a synoptic with the most important measurement (temperature, pressure, etc.) in real time. The measurement can be located in the right place of the synoptic (ex. Evaporator Temperature closed to the evaporator).

Details to be defined

5.4.3GRAPHIC

From this mask it is possible to record and see the graphic of a measurement (temperature, Pressure etc.). In the configuration menu will be decided the measurement to be recorded and the sample time.

Details to be defined

5.4.4CONFIGURATION

This is a menu used to configure the graphic user interface.

A password will protect the parameters.

Details to be defined

5.4.5F1, F2, F3

These keysare for custom function. They are optional.

Some ideas can be:

PRINT the Graphics

SHOW a graphic rappresentation of a setup parameter

SEND SMS with the actual values of the controller

SEND by SMS the controller setup

LOAD the controller setup

SAVE the controller setup

5.5DATE & TIME

Date and time can be displayed. To change date and time go to the config menu.

5.6SETUP

6.GEOCLIMA PERSONALIZATION

6.1Sw Version

The sw version for the Geoclima/Zamil personalization is GEOUSGXX.YY

6.2Logo Screen

When the board is turned off and each time we change screen the following mask is showed:

6.3Main Mask

The Main Mask is the User Mask and from here it is possible to control the chiller completely.

From User Mask is possible to go to all the other Mask.

The Mask is the following:

6.4SYNOPTIC

6.4.1CHILLER

To Enter in this menu from the User Menu press the Chiller icon

One chiller synoptic with LWT, RWT,SET POINT, chiller status, chiller capacity calculated (TBC)

6.4.2COMPRESSOR

To Enter in this menu from the User Menu press the Chiller icon

For each compressor a synoptic table with all circuit values

SP, DP, ELL, ST, SUPERHEAT, EEV%, FAN%, CP CAPACITY, CP CURRENT, DISCHARGE TEMPERATURE

6.5TRENDS

It is possible to have a graphic visualization of 3 values. They can be selected in the confiugration setup (service level).

Mininum and maximum y value are automatically calculated (autoscale).

Data can be showed at interval of 30’, 3h, 6h, 24h.

Data before 24h can not be showed

Data are memorized only in RAM sowhen the board is turned off the they are lost.

6.6LANGUAGE

In this mask it is possible to select the language to use.

6.7CONFIGURATION

It is only in English.

To Enter in this menu from the User Menu press the CONFIG icon

From this menu it is possible to set the following parameters. The parameters are protected by a password (the same used in the connected SB2 board).

LCD VISUALISATION / Description / Range / Level
ANAIN 1 FOR GRAPHICS / Channel 1 to show in the trend / Service
ANAIN 2 FOR GRAPHICS / Channel 2 to show in the trend / Service
ANAIN 3 FOR GRAPHICS / Channel 3 to show in the trend / Service
FAN PRESENCE / Inidcate if the fan is present (for the synoptic) / YES/NO / Manufacturer
CUR PRESENCE / Indicate if the Current has to be showed in the synoptic / YES/NO / Manufacturer
SETTING CLOCK HOUR / Set the hour of the actual time / 0 – 23 / User
SETTING CLOCK HOUR / Set the hour of the actual time / 0,23 / User
SETTING CLOCK DAY / Set the Day of the actual time / 1,31 / User
SETTING CLOCK MONTH / Set the Month of the actual time / 1,12 / User
SETTING CLOCK DAY / Set the Day of the actual time / 0,31 / User
SETTING CLOCK YEAR / Set the Year of the actual time / 0,50 / User
CONNECTED SW 0=GEOTUR, 1=ZAM2CH / Select the connecte sw / 0,1 / Manufacturer
LOGO: 0=PE 1=GEO 2=ZAMIL / Select the logo to show / 0,2 / Manufaturer
DEMO MODE? / Select always 0 (1 is only for demo mode of project engineering) / 0,1 / Manufacturer

6.8ALARM HISTORY

TBC

7.REVISION HISTORY

  • Rev. 0 - MNS – 14.02.06
    First Issue
  • Rev.1 MNS – 31/05/06
    sw vers. PE_USG03.00
    Add configuration parameters.
  • Rev.2 MNS 28/06/06
    Sw Version GEOUSG01
    Changed geoclima personalization: added language selection, autoscale for trends, analog channels selection for trend, password for configuration setup.

1 /12