State Bank of India, Local Head Office, Chennai

State Bank of India, Local Head Office, Chennai

TECHNICAL SPECIFICATION

FOR AIR CONDITIONING WORKS

1.0.0 IMTENT OF THE SPECIFICATION:

A Laboratory complex is being set up at IFFCO, Chennai. It is proposed to provide air conditioning facilities with Variable Refrigerant Flow ( VRF or VRV) units.

The following paragraphs highlight the technical requirements of the same.

2.0.0 BASIS OF DESIGN:

The air conditioning system for the above areas shall be designed on the following design basis:

Outside Design Conditions / 40 deg C (DB) maximum temperature/ 27.8 deg C (WB) – May.
Inside conditions / 23 deg C +/- 1 deg C (DB)
RH not exceeding 60%.
Areas/ occupancy/ equipment loads etc / As furnished in the table below.
Plant operation / 9 AM to 5 PM.
Exposed roof / Insulated with 50mm thick thermocole or fiberglass.
Power supply / 415 V, 50c/s, 3 phase 4 wire system.

The areas requiring air conditioning and the proposed scheme is as per the drawing enclosed.

To meet the above requirement, it is proposed to provide a VRV unit of 12 TR ODU capacity with 10 nos. of 1 TR and 1 no. of 2 TR cassette units. The outdoor unit and the indoor unit will be connected by means of copper refrigeration piping. The unit shall be DAIKIN,LG,TOSHIBA,SANYO or O GENERAL make.

The estimated cost is attached.

IFFCO, Chennai.

SCHEDULE OF QUANTITIES FOR AIR CONDITIONING WORKS:

SI /

Description of Item

/ Quantity / Unit Rate Rs. / Total Rs.
1. / Supply, Installation, Testing and commissioning (SITC) of fully imported factory assembled variable refrigerant flow (VRF) unit. The unit shall be complete with the following:
- Multiple(minimum two) hermatic rotary/ scroll compressors.
- Air cooled condenser coil with fan, motor and starter.
- Interconnecting refrigerant piping and valves.
- Controls comprising HP/ LP cutout, cooling thermostats etc.
- Starter for the compressor motor.
- Interconnecting copper piping, power wiring, control wiring and earthing.
- Base frame with anti vibration mounts.
- Micro processor based unit mounted starter/ control panel with suitable rain protection covers.
The unit shall be of fully imported DAIKIN/ TOSHIBA/HITACHI/ L G make with 407 refrigerant.
Capacity 12 TR: / 1 set / 240000 / 240000
2. / Indoor units, complete with evaporator coil, fan with motor, drain pan with pump, air filters, electronic expansion valve etc.,
Four way Cassette type 24,000 BTU/hour:
Four way Cassette Type 12000 BTU/hour:
Chordless Remote for the above units: / 1 set
10 sets.
11 sets / 35000
30000
1450 / 35000
300000
15950
3
4 / Supply and laying of copper refrigeration piping, with all fittings, refnut connections, supports, insulation, painting etc. Piping upto 19 mm shall be seamless 18G copper and above 19mm shall be hard drawn with 1mml thickness.
32 mm copper pipe:
25 mm copper pipe:
20 mm copper piping:
15 mm copper piping:
Indoor unit connections from the header
NOTE: The piping system shall be designed by the successful tenderer based on the actual layouts. The pipe lengths, including all fittings, will be measured and paid at actual. / 30 M
60 M
75 M
75 M
11 set / 720
610
500
390
950 / 21600
36600
37500
29250
10450
5 / Control wiring from the outdoor units to the indoor units with multi core 1.5 sqmm armoured PVC copper cable:
Wiring from the 15 A switch to the indoor unit with 2.5 sqmm copper conductors: / 220 M
40 M / 110
80 / 24200
3200
6 / Rigid PVC drain piping, 4Kg rating, from the indoor units:
50 mm dia:
25 mm dia:
15 mm dia: / 30 M
30 M
30 M / 175
120
95 / 5250
3600
2850
GRAND TOTAL / 765450

Price in words: Seven Laks Sixty Five Thousand Four Hundred and Fifty.

The rate indicated above is to be inclusive of all taxes, duties, Customs Duty, Ocean Freight, Works contract tax, service tax, VAT as applicable, transportation to site, labour, wastages, insurance, erection tools and tackles and all sundries required for a complete job.

TENDERERS SIGNATURE WITH SEAL: