SEL-2411 Settings Sheets 45
SEL2411 Settings Sheets1
Instruction Manual
These settings sheets include the definition and input range for each setting in the device. You can access the settings from the device front panel and the serial ports.
· Some settings require an optional module (see Section4: Logic Functions for details).
· Some of the settings ranges may be more restrictive than shown, because of settings interdependency checks performed when new settings are saved. The settings are not case sensitive.
Group Settings (SET Command)
Device SettingsDevice Identification (16 characters) / DID / :=
Terminal ID (16 characters) / TID / :=
Transformer Settings
Current Transformer Ratio (1–5000) (4 ACI) / CTR / :=
Neutral Current Transformer Ratio (1–5000) (4 ACI) / CTRN / :=
Additional Current Transformer Ratio (1–5000) (3ACI/3AVI) / CTRX / :=
Potential Transformer Ratio (1.00–10000.00)
/ PTR / :=
For the following settings, x is the card position (3, 4, 5, or 6);
y indicates input number 1–8 for an 8AI card or 1–4 for a 4AI/4AO card.
Demand Metering1
Enable Demand Metering / EDEM / :=
Demand Meter Time Constant (5, 10, 15, 30, 60 min) / DMTC / :=
Analog Input x01 Settings
AIx01 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx01NAM / :=
AIx01 Type (I, V) / AIx01TYP / :=
If AIx01TYP = I
AIx01 Low (–20.480 to +20.480; mA) / AIx01L / :=
AIx01 High (–20.480 to +20.480; mA) / AIx01H / :=
If AIx01TYP = V
AIx01 Low (–10.240 to +10.240V) / AIx01L / :=
AIx01 High (–10.240 to +10.240V) / AIx01H / :=
Note: Set Warn and Alarm to a value between Engr Low and Engr High settings.
AIx01 Engineering Units (16 characters) / AIx01EU / :=
AIx01 Engineering Unit Low (–99999.000 to +99999.000) / AIx01EL / :=
AIx01 Engineering Unit High (–99999.000 to +99999.000) / AIx01EH / :=
AIx01 Low Warn Level 1 (OFF, –99999.000 to +99999.000) / AIx01LW1 / :=
AIx01 Low Warn Level 2 (OFF, –99999.000 to +99999.000) / AIx01LW2 / :=
AIx01 Low Alarm (OFF, –99999.000 to +99999.000) / AIx01LAL / :=
AIx01 High Warn Level 1 (OFF, –99999.000 to +99999.000) / AIx01HW1 / :=
AIx01 High Warn Level 2 (OFF, –99999.000 to +99999.000) / AIx01HW2 / :=
AIx01 High Alarm (OFF, –99999.000 to +99999.000) / AIx01HAL / :=
Analog Input x02 Settings
AIx02 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx02NAM / :=
AIx02 Type (I, V) / AIx02TYP / :=
If AIx02TYP = I
AIx02 Low (–20.480 to +20.480; mA) / AIx02L / :=
AIx02 High (–20.480 to +20.480; mA) / AIx02H / :=
If AIx02TYP = V
AIx02 Low (–10.240 to +10.240V) / AIx02L / :=
AIx02 High (–10.240 to +10.240V)
/ AIx02H / :=
AIx02 Engr Units (16 characters) / AIx02EU / :=
AIx02 Engr Low (–99999.000 to +99999.000) / AIx02EL / :=
AIx02 Engr High (–99999.000 to +99999.000) / AIx02EH / :=
AIx02 Low Warn 1 (OFF, –99999.000 to +99999.000) / AIx02LW1 / :=
AIx02 Low Warn 2 (OFF, –99999.000 to +99999.000) / AIx02LW2 / :=
AIx02 Low Alarm (OFF, –99999.000 to +99999.000) / AIx02LAL / :=
AIx02 Hi Warn 1 (OFF, –99999.000 to +99999.000) / AIx02HW1 / :=
AIx02 Hi Warn 2 (OFF, –99999.000 to +99999.000) / AIx02HW2 / :=
AIx02 Hi Alarm (OFF, –99999.000 to +99999.000) / AIx02HAL / :=
Analog Input x03 Settings
AIx03 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx03NAM / :=
AIx03 Type (I, V) / AIx03TYP / :=
If AIx03TYP = I
AIx03 Low (–20.480 to +20.480; mA) / AIx03L / :=
AIx03 High (–20.480 to +20.480; mA) / AIx03H / :=
If AIx03TYP = V
AIx03 Low (–10.240 to +10.240V) / AIx03L / :=
AIx03 High (–10.240 to +10.240V) / AIx03H / :=
AIx03 Engr Units (16 characters) / AIx03EU / :=
AIx03 Engr Low (–99999.000 to +99999.000) / AIx03EL / :=
AIx03 Engr High (–99999.000 to +99999.000) / AIx03EH / :=
AIx03 Low Warn 1 (OFF, –99999.000 to +99999.000) / AIx03LW1 / :=
AIx03 Low Warn 2 (OFF, –99999.000 to +99999.000) / AIx03LW2 / :=
AIx03 Low Alarm (OFF, –99999.000 to +99999.000) / AIx03LAL / :=
AIx03 Hi Warn 1 (OFF, –99999.000 to +99999.000) / AIx03HW1 / :=
AIx03 Hi Warn 2 (OFF, –99999.000 to +99999.000) / AIx03HW2 / :=
AIx03 Hi Alarm (OFF, –99999.000 to +99999.000) / AIx03HAL / :=
Analog Input x04 Settings
AIx04 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx04NAM / :=
AIx04 Type (I, V) / AIx04TYP / :=
If AIx04TYP = I
AIx04 Low (–20.480 to +20.480; mA) / AIx04L / :=
AIx04 High (–20.480 to +20.480; mA) / AIx04H / :=
If AIx04TYP = V
AIx04 Low (–10.240 to +10.240V) / AIx04L / :=
AIx04 High (–10.240 to +10.240V) / AIx04H / :=
AIx04 Engr Units (16 characters) / AIx04EU / :=
AIx04 Engr Low (–99999.000 to +99999.000) / AIx04EL / :=
AIx04 Engr High (–99999.000 to +99999.000) / AIx04EH / :=
AIx04 Low Warn 1 (OFF, –99999.000 to +99999.000) / AIx04LW1 / :=
AIx04 Low Warn 2 (OFF, –99999.000 to +99999.000) / AIx04LW2 / :=
AIx04 Low Alarm (OFF, –99999.000 to +99999.000) / AIx04LAL / :=
AIx04 Hi Warn 1 (OFF, –99999.000 to +99999.000) / AIx04HW1 / :=
AIx04 Hi Warn 2 (OFF, –99999.000 to +99999.000) / AIx04HW2 / :=
AIx04 Hi Alarm (OFF, –99999.000 to +99999.000) / AIx04HAL / :=
Analog Input x05 Settings
AIx05 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx05NAM / :=
AIx05 Type (I, V) (Doesn’t apply to Extended Range) / AIx05TYP / :=
If AIx05TYP = I
AIx05 Low (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx05L / :=
AIx05 High (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx05H / :=
If AIx05TYP = V
AIx05 Low (–10.240 to +10.240V)
(–300 to +300V Extended Range) / AIx05L / :=
AIx05 High (–10.240 to +10.240V)
(–300 to +300V Extended Range) / AIx05H / :=
AIx05 Engr Units (16 characters) / AIx05EU / :=
AIx05 Engr Low (–99999.000 to +99999.000) / AIx05EL / :=
AIx05 Engr High (–99999.000 to +99999.000) / AIx05EH / :=
AIx05 Low Warn 1 (OFF, –99999.000 to +99999.000) / AIx05LW1 / :=
AIx05 Low Warn 2 (OFF, –99999.000 to +99999.000) / AIx05LW2 / :=
AIx05 Low Alarm (OFF, –99999.000 to +99999.000) / AIx05LAL / :=
AIx05 Hi Warn 1 (OFF, –99999.000 to +99999.000) / AIx05HW1 / :=
AIx05 Hi Warn 2 (OFF, –99999.000 to +99999.000) / AIx05HW2 / :=
AIx05 Hi Alarm (OFF, –99999.000 to +99999.000) / AIx05HAL / :=
Analog Input x06 Settings
AIx06 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx06NAM / :=
AIx06 Type (I, V) (Doesn’t apply to Extended Range) / AIx06TYP / :=
If AIx06TYP = I
AIx06 Low (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx06L / :=
AIx06 High (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx06H / :=
If AIx06TYP = V
AIx06 Low (–10.240 to +10.240V)
(–300 to +300V Extended Range) / AIx06L / :=
AIx06 High (–10.240 to +10.240V)
(–300 to +300V Extended Range) / AIx06H / :=
AIx06 Engr Units (16 characters) / AIx06EU / :=
AIx06 Engr Low (–99999.000 to +99999.000) / AIx06EL / :=
AIx06 Engr High (–99999.000 to +99999.000) / AIx06EH / :=
AIx06 Low Warn 1 (OFF, –99999.000 to +99999.000) / AIx06LW1 / :=
AIx06 Low Warn 2 (OFF, –99999.000 to +99999.000) / AIx06LW2 / :=
AIx06 Low Alarm (OFF, –99999.000 to +99999.000) / AIx06LAL / :=
AIx06 Hi Warn 1 (OFF, –99999.000 to +99999.000) / AIx06HW1 / :=
AIx06 Hi Warn 2 (OFF, –99999.000 to +99999.000) / AIx06HW2 / :=
AIx06 Hi Alarm (OFF, –99999.000 to +99999.000) / AIx06HAL / :=
Analog Input x07 Settings
AIx07 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx07NAM / :=
AIx07 Type (I, V) (Doesn’t apply to Extended Range) / AIx07TYP / :=
If AIx07TYP = I
AIx07 Low (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx07L / :=
AIx07 High (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx07H / :=
If AIx07TYP = V
AIx07 Low (–10.240 to +10.240V)
(–300 to +300V Extended Range) / AIx07L / :=
AIx07 High (–10.240 to +10.240V)
(–300 to +300V Extended Range) / AIx07H / :=
AIix07 Engr Units (16 characters) / AIx07EU / :=
AIx07 Engr Low (–99999.000 to +99999.000) / AIx07EL / :=
AIx07 Engr High (–99999.000 to +99999.000) / AIx07EH / :=
AIx07 Low Warn 1 (OFF, –99999.000 to +99999.000) / AIx07LW1 / :=
AIx07 Low Warn 2 (OFF, –99999.000 to +99999.000) / AIx07LW2 / :=
AIx07 Low Alarm (OFF, –99999.000 to +99999.000) / AIx07LAL / :=
AIx07 Hi Warn 1 (OFF, –99999.000 to +99999.000) / AIx07HW1 / :=
AIx07 Hi Warn 2 (OFF, –99999.000 to +99999.000) / AIx07HW2 / :=
AIx07 Hi Alarm (OFF, –99999.000 to +99999.000) / AIx07HAL / :=
Analog Input x08 Settings
AIx08 Instrument Tag Name (8 characters 0–9, A–Z, _) / AIx08NAM / :=
AIx08 Type (I, V) (Doesn’t apply to Extended Range) / AIx08TYP / :=
If AIx08TYP = I
AIx08 Low (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx08L / :=
AIx08 High (–20.480 to +20.480; mA)
(Doesn’t apply to Extended Range) / AIx08H / :=
If AIx08TYP = V
AIx08 Low (–10.240 to +10.240V)
(–300 to +300V Extended Range) / AIx08L / :=
AIx08 High (–10.240 to +10.240V)
(–300 to +300V Extended Range)
/ AIx08H / :=
AIx08 Engr Units (16 characters) / AIx08EU / :=
AIx08 Engr Low (–99999.000 to +99999.000) / AIx08EL / :=
AIx08 Engr High (–99999.000 to +99999.000) / AIx08EH / :=
AIx08 Low Warn 1 (OFF, –99999.000 to +99999.000) / AIx08LW1 / :=
AIx08 Low Warn 2 (OFF, –99999.000 to +99999.000) / AIx08LW2 / :=
AIx08 Low Alarm (OFF, –99999.000 to +99999.000) / AIx08LAL / :=
AIx08 Hi Warn 1 (OFF, –99999.000 to +99999.000) / AIx08HW1 / :=
AIx08 Hi Warn 2 (OFF, –99999.000 to +99999.000) / AIx08HW2 / :=
AIx08 Hi Alarm (OFF, –99999.000 to +99999.000) / AIx08HAL / :=
Analog Output x01 Settings
AOx01 Analog Quantity (Analog Quantity Value) / AOx01AQ / :=
AOx01 Instrument Tag Name (8 characters 0–9, A–Z, _) / AOx01NAM / :=
AOx01 Type (I, V) / AOx01TYP / :=
AOx01 Analog Quantity Low (–99999.000 to +99999.000) / AOx01AQL / :=
AOx01 Analog Quantity High (–99999.000 to +99999.000) / AOx01AQH / :=
If AOx01TYP = I
AOx01 Low Output Value (–20.480 to +20.480 mA) / AOx01L / :=
AOx01 High Output (–20.480 to +20.480 mA) / AOx01H / :=
If AOx01TYP = V
AOx01 Low Output Value (–10.240 to +10.240V) / AOx01L / :=
AOx01 High Output Value (–10.240 to +10.240V) / AOx01H / :=
Analog Output x02 Settings
AOx02 Analog Quantity (Analog Quantity Value) / AOx02AQ / :=
AOx02 Instrument Tag Name (8 characters 0–9, A–Z, _) / AOx02NAM / :=
AOx02 Type (I, V) / AOx02TYP / :=
AOx02 Analog Quantity Low (–99999.000 to +99999.000) / AOx02AQL / :=
AOx02 Analog Quantity High (–99999.000 to +99999.000) / AOx02AQH / :=
If AOx02TYP = I
AOx02 Low Output Value (–20.480 to +20.480 mA) / AOx02L / :=
AOx02 High Output (–20.480 to +20.480 mA) / AOx02H / :=
If AOx02TYP = V
AOx02 Low Output Value (–10.240 to +10.240V) / AOx02L / :=
AOx02 High Output Value (–10.240 to +10.240V) / AOx02H / :=
Analog Output x03 Settings
AOx03 Analog Quantity (Analog Quantity Value) / AOx03AQ / :=
AOx03 Instrument Tag Name (8 characters 0–9, A–Z, _) / AOx03NAM / :=
AOx03 Type (I, V) / AOx03TYP / :=
AOx03 Analog Quantity Low (–99999.000 to +99999.000) / AOx03AQL / :=
AOx03 Analog Quantity High (–99999.000 to +99999.000) / AOx03AQH / :=
If AOx03TYP = I
AOx03 Low Output Value (–20.480 to +20.480 mA) / AOx03L / :=
AOx03 High Output (–20.480 to +20.480 mA) / AOx03H / :=
If AOx03TYP = V
AOx03 Low Output Value (–10.240 to +10.240V) / AOx03L / :=
AOx03 High Output Value (–10.240 to +10.240V) / AOx03H / :=
Analog Output x04 Settings
AOx04 Analog Quantity (Analog Quantity Value) / AOx04AQ / :=
AOx04 Instrument Tag Name (8 characters 0–9, A–Z, _) / AOx04NAM / :=
AOx04 Type (I, V) / AOx04TYP / :=
AOx04 Analog Quantity Low (–99999.000 to +99999.000) / AOx04AQL / :=
AOx04 Analog Quantity High (–99999.000 to +99999.000) / AOx04AQH / :=
If AOx04TYP = I
AOx04 Low Output Value (–20.480 to +20.480 mA) / AOx04L / :=
AOx04 High Output (–20.480 to +20.480 mA) / AOx04H / :=
If AOx04TYP = V
AOx04 Low Output Value (–10.240 to +10.240V) / AOx04L / :=
AOx04 High Output Value (–10.240 to +10.240V) / AOx04H / :=
Internal RTD
RTD1 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD1TY / :=
RTD2 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD2TY / :=
RTD3 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD3TY / :=
RTD4 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD4TY / :=
RTD5 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD5TY / :=
RTD6 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD6TY / :=
RTD7 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD7TY / :=
RTD8 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD8TY / :=
RTD9 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD9TY / :=
RTD10 TYPE (PT100, NI100, NI120, CU10, NONE) / IRTD10TY / :=
External RTD Via SEL-2600 Devices
RTD1 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD1TY / :=
RTD2 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD2TY / :=
RTD3 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD3TY / :=
RTD4 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD4TY / :=
RTD5 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD5TY / :=
RTD6 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD6TY / :=
RTD7 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD7TY / :=
RTD8 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD8TY / :=
RTD9 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD9TY / :=
RTD10 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD10TY / :=
RTD11 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD11TY / :=
RTD12 TYPE (PT100, NI100, NI120, CU10, NONE) / ERTD12TY / :=
RTD/TC from Universal Input Temp Card
TEMP1 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP1TY / :=
TEMP2 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP2TY / :=
TEMP3 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP3TY / :=
TEMP4 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP4TY / :=
TEMP5 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP5TY / :=
TEMP6 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP6TY / :=
TEMP7 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP7TY / :=
TEMP8 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP8TY / :=
TEMP9 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP9TY / :=
TEMP10 TYPE
(PT100, NI100, NI120, CU10, J, K, T, E, NONE) / TEMP10TY / :=
Enable TC 3—Sample Averager for Thermocouples / ESAMPAVG / := Y
Logic Settings (SET L Command)