SECTION 08 87 13

SAFETY AND SECURITY FILM

Display hidden notes to specifier. (Don't know how? Click Here)

Copyright 2004 - 2008 ARCAT, Inc. - All rights reserved

** NOTE TO SPECIFIER ** Solar Gard®; Armorcoat and Panorama Safety and Security Films.
.
This section is based on the products of Solar Gard®, which is located at:
4540 View Ridge Ave
San Diego, CA 92123.
Toll Free: (877) 273-4364.
Tel: (858) 576-0200.
Fax: (858) 571-3605.
Email:
Web:
Web:
[Click Here] for additional information.
Saint-Gobain Solar Gard is the manufacturer of a high quality film designed to provide anti-penetration resistance to windows and glass doors from windstorms, accidents, explosions and vandalism. The security films can also offer a reduction of solar heat gain through the glazing surfaces of a building. The film is typically applied to the glazing surface on the inside of the structure by the use of a pre-applied application adhesive coated on the film and protected by a liner. Saint-Gobain Solar Gard is the first- and only- window film manufacturer to measure the net carbon impact of its architectural solar control window films and achieve a Climate Declaration. A complete Life Cycle Analysis was conducted on its Solar Gard and Panorama solar control films, providing evidence on how these films produce a net reduction in greenhouse gas emissions. The declaration registration number is S-EP-00207 and verification of the declaration and data was according to ISO 14025. The declaration can be accessed at
See our SpecWizard:Click Here

PART 1 GENERAL

1.1 SECTION INCLUDES

** NOTE TO SPECIFIER ** Delete items below not required for project.

A. Safety and Security film field applied to existing glass.

B. Safety and Security film factory applied to glazed surfaces.

1.2 RELATED SECTIONS

** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.

A. Section 08 11 13 - Custom Hollow Metal Doors and Frames.

B. Section 08 51 23 - Steel Windows.

C. Section 08 51 13 - Aluminum Windows.

D. Section 08 01 52 - Wood Window Restoration.

E. Section 08 44 00 - Curtain Wall and Glazed Assemblies.

1.3 REFERENCES

** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.

A. American Society for Testing Materials (ASTM)

B. American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE)

C. Association of Industrial Metallizers, Coaters and Laminators (AIMCAL)

D. American National Standards Institute (ANSI)

E. International Standards Organization (ISO)

F. International Window Film Association (IWFA)

G. Government Services Administration (GSA)

H. Consumer Products Safety Commission (CPSC)

I. Code of Federal Regulations (CFR)

1.4 PERFORMANCE REQUIREMENTS

A. Storm Testing: 8 mil Solar Gard Armorcoat safety films shall be capable of meeting the following tests:

1. ASTM E-1886, Standard Test Method for Missile Impact and Cycling On Exterior Windows, Shutters, Doors and Curtain Walls - Large Missile C.

2. ASTM E-1996, Standard Specification for Missile Impact and Cycling On Exterior Windows, Shutters, Doors and Curtain Wall - Large Missile C.

3. ASTM E-283-04, Test Method for Airflow through Exterior Windows, Shutters, Doors and Curtain Walls.

4. ASTM E-330-02 Test Method for Structural Performance of Exterior Windows, Shutters, Doors and Curtain Walls by uniform Static Air Pressure Difference.

5. ASTM E-331-00, Test Method for Structural Performance of Exterior Windows, Shutters, Doors and Curtain Walls by uniform Static Air Pressure Difference.

B. Bomb Blast Simulation: Independent testing of Solar Gard safety films with results from high-explosive tests evaluating the capability of Solar Gard window film in 4 mil to 14 mil thicknesses to reduce the hazards of flying glass shards during an explosion.

1. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied as a daylight application on 1/4 inch (6 mm) single pane annealed glass: 3B.

2. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied as a daylight application on 1/4 inch (6 mm) single pane tempered glass: 3B.

3. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied with Dow Corning 995 on 1/4 inch (6 mm) single pane annealed glass: 3A.

4. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) single pane tempered glass: 2.

5. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: 2.

6. ISO 16933 Hazard Rating with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane tempered glass: "Hazard Rating B (EXV33(B))" .

7. ISO 16933 Hazard Rating with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: "Hazard Rating C (EXV33(C))".

8. ASTM F 1642 Hazard Level with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: "No Hazard".

9. ASTM F 1642 Hazard Level with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane tempered glass: "No Hazard".

10. UFC 4-010-01 Protection Level with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: "High Level of Protection".

11. UFC 4-010-01 Protection Level with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane tempered glass: "High Level of Protection".

C. Impact Resistance: Solar Gard safety films shall be capable of meeting the following tests:

1. 4 mil Solar Gard safety films:

a. Passes ANSI Z 97.1 (100 - 150 ft lb).

b. Passes CFR 1201, Category I (150 ft lb impact).

2. 7 mil and thicker Solar Gard safety films:

a. Passes ANSI Z 97.1 (100 - 150 ft lb).

b. Passes CFR 1201, Category II.

1.5 SUBMITTALS

A. Submit under provisions of Section 01 30 00.

B. Product Data: Manufacturer's data sheets on each product to be used, including:

1. Physical properties and independent testing agency reports showing compliance with specified tests.

2. Preparation instructions and recommendations.

3. Storage and handling requirements and recommendations.

4. Installation methods.

C. Shop Drawings: Detailing installation of film, anchoring accessories, and sealant.

D. Verification Samples: For each finish product specified, two samples, minimum size 6 inches (150 mm) square, representing actual product, color, and patterns.

E. Manufacturer's Certificates: Certify products meet or exceed specified requirements.

F. Manufacturer's warranty information.

1.6 QUALITY ASSURANCE

A. Manufacturer Qualifications: Solar film manufacturer shall be the standard product of a manufacturer regularly engaged in the manufacture and distribution of such products in satisfactory use for a minimum of 5 years. Manufacturing facility shall be ISO 9001-2000 and ISO 14001-2004 standard registration.

B. Installer Qualifications: Documented experience in the application of self-adhesive window films with at least 3 applications of similar size and complexity, and approved by the solar film manufacturer.

** NOTE TO SPECIFIER ** Include a mock-up if the project size and/or quality warrant taking such a precaution. The following is one example of how a mock-up on a large project might be specified. When deciding on the extent of the mock-up, consider all the major different types of work on the project.

C. Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship.

1. Apply film to one window designated by Architect.

2. Do not proceed with remaining work until workmanship and color, is approved by Architect.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Store products indoors in manufacturer's unopened packaging until ready for installation.

1.8 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

** NOTE TO SPECIFIER ** Delete the following paragraphs if no warranties are required or if the work is covered under the terms of a general project warranty specified elsewhere.

1.9 WARRANTY

A. See Section 01 78 23 - Preventative Maintenance Instructions.

B. Provide film manufacturer's limited warranty against failure of film, including change of color, peeling, bubbling, rippling, cracking, delamination and demetalization; include cost of material and labor for removal and reinstallation. Duration of warranty shall be as follows:

** NOTE TO SPECIFIER ** Delete the products not used on the project from the following paragraphs.

1. Twelve Year Limited Warranty for the following safety and security film products:

a. Solar Gard Armorcoat 4 mil Stainless Steel 50

b. Solar Gard Armorcoat 4 mil Stainless Steel 35

c. Solar Gard Armorcoat 4 mil Stainless Steel 20

d. Solar Gard Armorcoat 8 mil Stainless Steel 50

e. Solar Gard Armorcoat 8 mil Stainless Steel 35

f. Solar Gard Armorcoat 8 mil Stainless Steel 20

g. Solar Gard Armorcoat 10 mil Stainless Steel 35

h. Solar Gard Armorcoat 4 mil Solar Bronze 20

i. Solar Gard Armorcoat 4 mil Solar Bronze 35

j. Solar Gard Armorcoat 4 Mil Silver 20

k. Solar Gard Armorcoat 8 mil Silver 35

l. Solar Gard Armorcoat 8 mil Silver 20

m. Solar Gard Armorcoat 10 Mil Silver 20

n. Solar Gard Armorcoat 4 Mil Clear

o. Solar Gard Armorcoat 7 Mil Clear

p. Solar Gard Armorcoat 8 Mil Clear

q. Solar Gard Armorcoat 10 Mil Clear

r. Solar Gard Armorcoat 11 Mil Clear

s. Solar Gard Armorcoat 14 Mil Clear

t. Panorama 8 Mil Hilite 70

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturer: Solar Gard®, which is located at: 4540 View Ridge Ave.; San Diego, CA 92123; Toll Free Tel: 877-273-4364; Tel: 858-576-0200; Fax: 858-571-3605; Email:; Web:

** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.

B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of Section 01 60 00.

2.2 SAFETY AND SECURITY FILM

A. Film shall be manufactured from polyethylene terepthalate (polyester) and combined with sputtered metal coatings to achieve the desired performance and aesthetic characteristics. The finished film shall be self adhesive and include a coating to reduce the effects of scratching and abrasions that occur in normal daily activity and also include absorbers and inhibitors for the purpose of reducing ultra violet rays.

** NOTE TO SPECIFIER ** Delete from the following list the safety and security films not used on the project. If more than one type is required add a description of where the films are to be located or locate the types used on the Drawings.

B. Solar Gard Armorcoat 4 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance: 39 percent.

b. Solar Absorptance: 50 percent.

c. Solar Reflectance: 11 percent.

d. Visible Light Transmittance: 46 percent.

e. Visible Light Reflectance: (Exterior) 13 percent.

f. Visible Light Reflectance: (Interior) 11 percent.

g. Emissivity: .90.

h. U-Factor (Winter): 1.12.

i. Shading Coefficient: .62.

j. Solar Heat Gain Coefficient: .53.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent

l. Total Solar Energy Rejected: 46 percent.

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 4.0 mils (100 microns).

b. Peel Strength: 2,500 g/in (984 g/cm)

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 120 lbs/in (22 kg/cm).

e. Elongation at Break: Greater than 100 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

i. Meets GSA Level C criteria (3B at 4 psi, 28 psi/milliseconds)

C. Solar Gard Armorcoat 4 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 43 percent

b. Solar Absorptance 46 percent

c. Solar Reflectance 12 percent

d. Visible Light Transmittance 47 percent

e. Visible Light Reflectance (Exterior) 13 percent

f. Visible Light Reflectance (Interior) 11 percent

g. Emissivity: .90.

h. U-Value (Winter) 1.07.

i. Shading Coefficient .65.

j. Solar Heat Gain Coefficient .56.

k. Ultraviolet Light Blocked (300-380 nanometers) Greater than 99 percent

l. Total Solar Energy Rejected 44 percent

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 4.0 mil (100 micron)

b. Peel Strength: 2,500 g/in (984 g/cm)

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 120 lbs/in (22 kg/cm).

e. Elongation at Break: Greater than 100 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

D. Solar Gard Armorcoat 4 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 39 percent

b. Solar Absorptance 48 percent

c. Solar Reflectance 14 percent

d. Visible Light Transmittance 42 percent

e. Visible Light Reflectance (Exterior) 16 percent

f. Visible Light Reflectance (Interior) 13 percent

g. Emissivity: .87.

h. U-Factor (Winter) 1.05.

i. Shading Coefficient .61.

j. Solar Heat Gain Coefficient .53.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent

l. Total Solar Energy Rejected 47 percent

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 4.0 mils (100 microns).

b. Peel Strength: 2,500 g/in (984 g/cm)

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 120 lbs/in (22 kg/cm).

e. Elongation at Break: 160 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

E. Solar Gard Armorcoat 4 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 36 percent

b. Solar Absorptance 52 percent

c. Solar Reflectance 12 percent

d. Visible Light Transmittance 42 percent

e. Visible Light Reflectance (Exterior) 14 percent

f. Visible Light Reflectance (Interior) 14 percent

g. Emissivity: .87.

h. U-Factor (Winter) 1.03.

i. Shading Coefficient .60.

j. Solar Heat Gain Coefficient .51.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.

l. Total Solar Energy Rejected 87 percent

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 4.0 mils (100 microns).

b. Peel Strength: 2,500 g/in (984 g/cm)

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 120 lbs/in (22 kg/cm).

e. Elongation at Break: 160 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

F. Solar Gard Armorcoat 4 Mil Stainless Steel 20 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 19 percent.

b. Solar Absorptance 61 percent.

c. Solar Reflectance 20 percent.

d. Visible Light Transmittance 22 percent

e. Visible Light Reflectance (Exterior) 26 percent.

f. Visible Light Reflectance (Interior) 25 percent.

g. Emissivity: .85.

h. U-Factor (Winter) 1.09.

i. Shading Coefficient .42.

j. Solar Heat Gain Coefficient .37.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.

l. Total Solar Energy Rejected 63 percent.

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 4.0 mils (100 microns).

b. Peel Strength: 2,500 g/in (984 g/cm).

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 120 lbs/in (22 kg/cm).

e. Elongation at Break: greater than100 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

G. Solar Gard Armorcoat 4 Mil Stainless Steel 20 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 21 percent.

b. Solar Absorptance 56 percent.

c. Solar Reflectance 23 percent.

d. Visible Light Transmittance 22 percent.

e. Visible Light Reflectance (Exterior) 27 percent.

f. Visible Light Reflectance (Interior) 25 percent.

g. Emissivity: .85.

h. U-Factor (Winter) 1.11.

i. Shading Coefficient .43.

j. Solar Heat Gain Coefficient .37.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.

l. Total Solar Energy Rejected 63 percent.

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 4.0 mils (100 microns).

b. Peel Strength: 2,500 g/in (984 g/cm).

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 120 lbs/in (22 kg/cm).

e. Elongation at Break: greater than100 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

H. Solar Gard Armorcoat 8 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 40 percent.

b. Solar Absorptance 49 percent.

c. Solar Reflectance 11 percent.

d. Visible Light Transmittance 44 percent.

e. Visible Light Reflectance (Exterior) 14 percent.

f. Visible Light Reflectance (Interior) 11 percent.

g. Emissivity: .88.

h. U-Factor (Winter) 1.06.

i. Shading Coefficient .62.

j. Solar Heat Gain Coefficient .54.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.

l. Total Solar Energy Rejected 46 percent.

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 8.0 mil (200 microns).

b. Peel Strength: 2,500 g/in (984 g/cm).

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 240 lbs/in (43 kg/cm).

e. Elongation at Break: greater than100 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

I. Solar Gard Armorcoat 8 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 37 percent.

b. Solar Absorptance 53 percent.

c. Solar Reflectance 10 percent.

d. Visible Light Transmittance 43 percent.

e. Visible Light Reflectance (Exterior) 13 percent.

f. Visible Light Reflectance (Interior) 11 percent.

g. Emissivity: .88.

h. U-Factor (Winter) 1.11.

i. Shading Coefficient .60.

j. Solar Heat Gain Coefficient .51.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.

l. Total Solar Energy Rejected 48 percent.

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 8.0 mil (200 microns).

b. Peel Strength: 2,500 g/in (984 g/cm).

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 240 lbs/in (43 kg/cm).

e. Elongation at Break: greater than100 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

J. Solar Gard Armorcoat 8 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.

1. Film Performance Results, Nominal:

a. Solar Transmittance 34 percent.

b. Solar Absorptance 52 percent.

c. Solar Reflectance 14 percent.

d. Visible Light Transmittance 38 percent.

e. Visible Light Reflectance (Exterior) 16 percent.

f. Visible Light Reflectance (Interior) 13 percent.

g. Emissivity: .88.

h. U-Factor (Winter) 1.05.

i. Shading Coefficient .57.

j. Solar Heat Gain Coefficient .50.

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.

l. Total Solar Energy Rejected 50 percent.

2. Physical and Thermal Properties, Nominal:

a. Film Thickness: 8.0 mil (200 microns).

b. Peel Strength: 2,500 g/in (984 g/cm).

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).

d. Break Strength; 240 lbs/in (43 kg/cm).

e. Elongation at Break: greater than100 percent.

f. Combustion Rate: Negligible.

g. Melting Point: 260-265 degrees C.

h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

K. Solar Gard Armorcoat 8 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.

1. Film Performance Results, Nominal: