86-1_A04-20-18__2015
Page 1 of 4
Page 1 of 4
Section 86-1. Use to modify the requirements for the schedule of values, testing location for material and equipment,pull box cover markings, warning tape, signal interconnect cable, circuit breakers capacity and mounting, cabinet components, telephone demarcation cabinets, signal face material, push button housing.
1. Use to modify the number of days for submitting a schedule of values. Delete if not used.
Replace 15 in the 6th paragraph of the RSS for section 86-1.01C(1) with:
______
2. Use to modify the testing location for material and equipment. Insert the address of the testing location. Delete if not used.
Replace the 1st paragraph of the RSS for section 86-1.01D(3) with:
Deliver the material and equipment for testing to the following location:
____________
______
3. Use to specify additional markings for pull box covers. Insert the additional cover markings. Delete if not used.
Add to the list in the 4th paragraph of the RSS for section 86-1.02C(1):
14.______
15.______
16.______
4. Use for warning tape. Insert phone number. Delete if not used.
Replace the 8th row in the table in the 1st paragraph of the RSS for section 86-1.02D(3) with:
Printed message content / CAUTION: CALTRANS FACILITIES BELOWCALL 1-XXX-XXX-XXX
5. Replace 6 with 3 in the 1st sentence if 3-pair signal interconnect cable is required. Delete if not used.
86-1.02F(3)(d)(v) Signal Interconnect Cables
Signal interconnect cable must be a 6-pair type with stranded, tinned, copper no. 20 conductors. The insulation for each conductor must be color-coded polypropylene with a minimum 13-mils nominal thickness. The conductors must be in color-coded, twisted pairs. Each pair must be wrapped with an aluminum polyester shield and have a no. 22 or larger, stranded, tinned, copper drain wire inside the shielded pair.
6–7. Use to change the minimum interrupting capacity of the circuit breakers for a service equipment enclosure. Delete if not used.
6. Insert therequired minimum interrupting capacity. Delete if not used.
Replace 10,000 in the 14th paragraph of the RSS for section 86-1.02P(2) with:
______
7. Use if circuit breakers are used as disconnects. Delete if not used.
Replace the 14th paragraph of section 86-1.02P(2) of the RSS with:
Circuit breakers used as disconnects must have a minimum interrupting capacity of 42,000 A, rms, for 120/240 V(ac) services and 30,000 A, rms, for 480 V(ac) services.
8. Use to specify the required circuit-breaker mounting for a service equipment enclosure. Edit as needed. Delete if not used.
Replace the 1st sentence of the 15th paragraph of section 86-1.02P(2) of the RSS with:
The interior of the enclosure must accept cable-in/cable-out circuit breakers. The circuit breakers must be mounted on nonenergizedclips and vertically with the up position of the handle being the ONposition.
9-13. Use to specify the cabinet components. Delete if not used.
9. Edit the components as needed.
Add to the endof section 86-1.02Q(3) of the RSS:
The cabinet components include:
1.Multiple AC outlet strip
2.RJ-11 modular jack
3.RJ-45 modular jack
4.DC terminal block
10. Use to specify a multiple AC outlet strip.
86-1.02Q(3)(a) Multiple AC Outlet Strip
The multiple AC outlet strip must:
1.Be 19 inch, rack mountable
2.Have a minimum of 6 receptacle outlets
3.Be rated for 15 A, 125 V(ac)
4.Have internal 12 A, 125 V(ac) circuit breaker
5.Rated for 36,000 A surge current protection Hot to Neutral
6.UL 1449 rating for 400 V minimum
7.Cord 6 feet minimum
11. Use to specify an RJ-11 modular jack.
86-1.02Q(3)(b) RJ-11 Modular Jack
The RJ-11 modular jack must:
1.Be DIN rail mounting
2.Have 6 interface positions
3.Be rated for 120 V and 1 A
4.Have dimensions of 2 inches (D) by 1.5 inches (W) by 3.25 inches (H)
5.Have a screw clamp connection
12. Use to specify a RJ-45 modular jack.
86-1.02Q(3)(c) RJ-45 Modular Jack
The RJ-45 modular jack must:
1.Be DIN rail mounting
2.Have 8 interface positions
3.Be rated for 120 V and 1 A
4.Have dimensions of 2 inches (D) by 1.5 inches (W) by 3.25 inches (H)
5.Have a screw clamp connection
13. Use to specify a DC terminal block.
86-1.02Q(3)(d) DC Terminal Block
The DC terminal block must:
1.Be rated for 250 V(ac)/DC voltage and 30 A current
2.Have an operating temperature from -13 to 122 degrees F
3.Have a maximum size of 3.9 inches (D) by 2.7 inches (W) by 2.7 inches (H)
4.Have a wire size for the input terminals of 26-10 AWG solid/strand
5.Have a wire size for the output terminals of 26-12 AWG solid/strand
6.Have a torque of at least 4.4 in-lb
14–23. Use for alternative types of telephone demarcation cabinets. Delete if not used.
14–16. Use if a Type A telephone demarcation cabinet is required. Delete if not used.
14
Replace Reserved in section 86-1.02Q(4)(b) of the RSS with:
A Type A telephone demarcation cabinet consists of mounting boards, a junction box, a circuit breaker, outlets, a terminal block, and an outlet plate.
15
The mounting backboard, bottom shelf, and shelf supports must be made of 1/2-inch-thick, ACX-grade plywood.
16
The cabinet and hinged cover must be a NEMA 3R type with a minimum material thickness of 0.080 inch. The cabinet must have a hasp lock and a bolted slip fitter that allows mounting to a 4-1/2-inch-diameter steel pedestal.
17–23. Use if a Type C telephone demarcation cabinet is required. Delete if not used.
17
Replace Reserved in section 86-1.02Q(4)(d) of the RSS with:
A Type C telephone demarcation cabinet consists of mounting boards, a thermostat, fan, an outlet box, a circuit breaker, and an outlet plate.
18
The mounting panel must be 3/4-inch-thick, ACX-grade plywood.
19
The cabinet must be made of 0.125-inch-thick anodized aluminum.
20
Ventilation louvers must be located on the door.
21
The cabinet door must be secured with drawn latches, lockable with a padlock
22
The fan must be located in a ventilator housing and be controlled thermostatically. The thermostat control must have a range from 80 to 130 degrees F.
23
The thermostat and fan circuit must be protected with a fuse rated for 175 percent of the motor capacity. The fan capacity must be a minimum of 25 cfm.
24. Use if a specific material is required for the signal face. Insert metal or plastic. Delete if not used.
Add to the list in the 2nd paragraph of section 86-1.02R(4) of the RSS:
4.Be made of ______
25. Use if a plastic push button housing is required. Delete if not used.
Replace the 1st sentence in the 1st paragraph of section 86-1.02U of the RSS with:
The housing for a push button assembly must be made of UV-stabilized, self-extinguishing structural plastic.