DUBLIN INSTITUTE OF TECHNOLOGY

Kevin Street, Dublin 8.

School Of Control Systems and Electrical Engineering

Solution SheetPage 1 of 7

Course/Year / DT009 Year 3 / Examination
Sitting / Semester 1
2005/2006
Subject / Control and Automation Minor
Examiner / Gavin Duffy
Question No. / 1

(i) Open loop - simple, inexpensive. Result of output not measured. Good knowledge of system required [2]

Suitable example[2]

Closed loop - more complicated but better. Output is measured and compared against setpoint to give an error. [2]

Suitable example[2]

(ii) Integral control -[2]

Remembers past history of the error and is used to remove the offset of a proportional controller[2]

Integral windup – a very large cumulative integral result occurs when the error cannot be corrected (e.g. faulty instrument, valve). [4]

(iii) Ultimate cycle - set controller to P control only; increase gain until oscillations develop; stop increasing gain when system becomes unstable [3]

Process reaction curve - place controller in manual mode; set output to a constant value and allow system to reach a steady state; make a step change in the output and record the process variable response with time [3]

Disadvantage of ultimate cycle is that operates on the borderline of instability - this could cause damage to plant and/or personnel [2]

(iv) Step 1 is Self Test – check for errors in hardware/software

Step 2 is Input Scan – Reads input values from input cards to the memory

Step 3 is Execute Logic – each ladder in program is executed and outputs are updated

Step 4 is Output Scan – Writes output values from memory to output cards[8]

(v) Types of pushbuttons: Start is normally open or press to close switch – done this way so that if wire breaks motor can’t start. Stop is normally closed or press to open switch – done this way so that if wire breaks the motor stops (it’s the same as pressing stop button). [4]

Ladder logic – two ways of doing this.

Option 1 is as follows:

Option 2:

Option 1 or 2[4]

Question No. / 2

(a)

(i) Convert to frequency domain as follows: Starting with:

Applying the Laplace transform to this equation gives:

[2]

The transfer function which is the output over the input is now easily determined:

[3]

(ii) We can replace the input TJ(s) in the Laplace transformed equation above with a/s, the Laplace transform of a step input of magnitude a. The equation now becomes:

[5]

(iii) Check the tables to find

[2]

In the above equation, b = 1/ and Ka is a constant so remains unchanged. Therefore:

[3]

(b)

Above code[6]

Comments[4]

Noise is reduced by using the averaged value from the card instead of the present value. [3]

This requires changing the buffer memory address to read the data from the averaged value and also requires sending down a number of averages to the buffer memory address for this information. [2]

Question No. / 3

(i) Convert the system into a single block to give the equation below:

the overall output over input = transfer function[4]

the static gain is above the line[4]

the time constant is the constant in the s term[4]

(ii)

i.e. proportional gain = 3[5]

At steady state we have:

Therefore, the error is 10% of the input.[5]

(iii) Proportional offset is the steady state error observed when using proportional control.[2]

It can be removed by adding integral action. The integral term acts on the integral of the error and removes any steady state error. [2]

(iv) Yes. A high gain may result in overshoot and undershoot oscillations which may not die off. This causes instability. [4]

Question No. / 4

(i) Block Diagram[9]

(ii) Error = SP – PV (PV = Temp in this case).[2]

When error is positive, heater is On. When error is negative, heater is Off.[2]

(iii) Advantages – cheap, easy to implement, simple, digital output instead of analog[2]

Disadvantages – can’t have PV exactly at setpoint. Frequent switching of output[2]

(iii) Add a deadband or hysteresis. Reduces frequency of switching on and off.[4]

(iv)

[6]

[3]